Text only (DECISIONS, DOCS, CHANGELOG): a step load alarms on the same cycle
as before; a steadily rising load alarms a little later; with peak_margin_w 0
a period can end up to 10 W over the limit without this alarm, as for 'Load
too high' (SAFETY-81). Owner accepted 2026-10-31.
test_safety126.py part 2: after a real overrun ends, _peak_landing()'s latch
is reset and the night's later landings are quiet (review F3).
Co-Authored-By: Claude <noreply@anthropic.com>
During the night grid charge under the peak reserve the guard alarmed
(ERROR PEAK_GUARD_FLOOR_LIMITED, "Battery stopped limiting the peak") and the
Batteries "Why" said "The peak limit needs power" at quarter ends, while every
quarter landed on the aim. The charge lands the period 0-7 W over the aim and
excess_w()'s 900 / remaining turns that into tens of kW in the last second;
with nothing able to give, check_peak_floor_limited() alarmed on any
wanted > 0.
Each cycle the guard wants power, _peak_landing() asks misses_aim(): with the
batteries at 0 W, does the period end more than ALARM_MISS_W over the aim? If
not, the decision is within_aim: no reserve alarm, no red peak row, no "Why"
peak. The claim and the commands are unchanged. A real overrun under the
reserve alarms on the same cycle as before.
Co-Authored-By: Claude <noreply@anthropic.com>