adminandClaude Opus 5.5 7b723a6cd5 SAFETY-85 review: grade discharge only, over the plant's settle time
checks / unit (pull_request) Successful in 25m47s
infra-pin / fresh (pull_request) Successful in 2s
Rule 2 graded each battery against last cycle's command and graded charges
too. On plantsim's battery (10 s lag) at the 2 s meter it warned at every
drain or charge start and 15 times an hour under the peak guard at N=2; a
charge tapering near full warned 11 times in 50 min (SAFETY-42 section 7).
Now a discharge is graded against the least it stood at over SHORT_CYCLES /
SHORT_SPAN_S. DOCS lists `mode-bound` under Loop reason. test_safety85 part 7:
peak guard with a dead battery, lagging plant, taper; part 3: the bound ends
with maintenance.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-10-01 20:25:41 +02:00
glenn schrooyenandClaude Opus 5.5 4b81387908 SAFETY-85: no false 'not keeping up' while maintenance or the peak guard sets the battery
checks / unit (pull_request) Successful in 25m35s
infra-pin / fresh (pull_request) Successful in 2s
The loop's integrator bound counts only on a cycle the loop decided. A battery
another owner set (maintenance, the peak guard, a safety limit) alarms only
when it gives more than saturation_w less than told for saturation_cycles
cycles. At N>=2 the loop is bounded while maintenance holds a battery, so it
does not wind and control comes back one slew step a cycle. The status row
counts episodes, not cycles. Digests re-pinned where behaviour changed on
purpose; DECISIONS/SAFETY-85-no-false-not-keeping-up.md has the list.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_019DBUfvndgHwaV339Fvd2gr
2026-10-01 19:05:27 +02:00
adminandClaude Opus 5.5 e0b578756f UX-10 review: the line as logged gets the red-alarm shape, clamp lines at 30 words, plain HA 400
checks / unit (pull_request) Successful in 9m3s
infra-pin / fresh (pull_request) Successful in 2s
Part 6 checked the quoted reason alone, so title + reason + tails logged
as 4+ sentences. It now also checks the whole line (at most 3 sentences,
none over 30 words); 25 lines failed and are rewritten (one-sentence
wrappers, two-sentence circulation and peak reasons, STALE_READING's
fixed limits on a DEBUG line). The clamp lines for one inverter are
pinned at 30 words with OUTPUT_CLAMP and the numbers kept. Home
Assistant's bare '400: Bad Request' while it loads becomes one plain
line; still WARNING, throttled, a failed write.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-27 12:08:38 +02:00
glenn schrooyenandClaude Opus 5.5 23a3a3f5b5 UX-10: the last plain-language leftovers: log lines, two table rows, 'Why: Other', red at 0 s
checks / unit (pull_request) Successful in 9m3s
infra-pin / fresh (pull_request) Successful in 2s
- test_messages.py part 6: every dynamic part of a WARNING+ line is classified
  as data or as a built text, and every built text is produced by the real
  code and checked. This is the gap the 2d scan had: it counted `%s` as one
  word, so reasons built by loop_clamp_note() and friends were never seen.
- Quoted reasons rewritten to STYLE.md (red-alarm shape, codes kept):
  OUTPUT_CLAMP, METER_FROZEN, CIRCULATING_POWER, STALE_READING, the peak
  guard (codes now PEAK_GUARD*), the migration report, price feed, price
  history and gate reasons. Plurals via messages.times()/count().
- Top table: Price history "96 prices over 24 hours for 26 Sep", Tariff
  "one every 15 minutes or every hour", "not final yet" dropped.
- Levels and noise: per-cycle shadow line DEBUG, shadow on/off INFO,
  aiohttp access log only at log level debug, settings warnings once per
  start, one plain line per Home Assistant outage (hass.Outage).
- INFO jargon and error texts: no "§8.3", ISO times, "banked", "keys ARE",
  "NOT_OBSERVED", "did NOT land", "AND".
- Display bugs: WHY_WINNER covers every winner and safety reason
  (main.why_key(), part 7 finds them in the code); the meter row is amber
  "waiting for the first reading" inside its limit after a start; the
  missing-reading age is counted when the page asks.
- STYLE.md and DECISIONS/UX-08-short-notifications.md (UX-10 section).

No change to safety behaviour, alarm levels, notification ids, triggers,
cadence or the banner cascade. One row colour changes (meter at start),
justified in DECISIONS.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-27 10:58:43 +02:00
adminandClaude Opus 5.5 d017fc67bf UX-08 phase 2b: short, plain status rows and page banners
checks / unit (pull_request) Successful in 8m47s
infra-pin / fresh (pull_request) Failing after 1s
Every Commissioning row and every page banner is now worded in
app/messages.py (row_*, banner_*): one sentence of at most 15 words, a red
row up to three sentences so a latch still says how it clears, banners at
most 12 words. No row names a Home Assistant entity: sensors by their
setting, solar sources by their place in the list. Reason codes and limits
stay on the log line and event list; rows keep the numbers a reader acts on.

UX-07 item 1: ClampWatchdog counts over-rating and integrator-bound
engagements separately, and after an episode each count shows under its own
alarm's title instead of both under "output clamp".

No row colour, visibility or banner order changed. Rows carry an "id" so the
tests pin meaning rather than wording. The row and banner kinds leave the
allowlist (200 -> 168, cap equal). DOCS.md gains "Status page"; choices are in
DECISIONS/UX-08-short-notifications.md.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01LyR88rXETvwhTgx6yHE39p
2026-09-27 02:12:10 +02:00
glenn schrooyenandClaude Opus 5.5 50ccea3dd7 UX-08 phase 2a: short, plain notifications, and a ratchet for the rest
checks / unit (pull_request) Successful in 8m54s
infra-pin / fresh (pull_request) Successful in 1s
Every HA notification the add-on raises now has a title of at most 5
everyday words and a one-sentence body; a red alarm may use three so no
action is lost. The texts live in app/messages.py, the rule in STYLE.md,
and the detail that moved out in DOCS.md "Notifications", which each body
links to. No notification_id, trigger or cadence changed.

test_messages.py enforces the rule on every notification, fails any
notification worded outside app/messages.py, and ratchets the kinds not yet
rewritten (rows, banners, refusals, logs, options) through a shrinking
allowlist of 200. Six tests re-pinned from prose to meaning.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01LyR88rXETvwhTgx6yHE39p
2026-09-27 01:00:54 +02:00
glenn schrooyenandClaude Opus 5.5 fd14569a71 SAFETY-40: the integrator bound is not a BUG SIGNAL; numbers from the clamp tick
checks / unit (pull_request) Successful in 8m47s
infra-pin / fresh (pull_request) Successful in 1s
The clamp alarm gave `i_clamped` (normal anti-windup) the over-rating BUG
SIGNAL text, printed `Decision.i_w` as "the loop asked for", and printed
`self.target` (after slew/freeze) as "was clamped to".

- clamp.loop_clamp_note(): i_clamped says "the loop's integrator reached its
  N W anti-windup bound" with this tick's command; clamped keeps BUG SIGNAL
  with the requested command and the clamp's own result.
- Decision carries i_bound_w / requested_w / clamped_w, set at the clamp.
- i_clamped still counts and notifies (same id, cadence, SAFETY-41
  escalation) but as a WARNING, amber row, plain title. A bug has its own
  notification budget and its text is not overwritten within an episode.
- test_clamp.py part 9: red on the old code per defect; 5 mutations killed.
- DOCS.md alarm section (and its stale 30 s cadence), DECISIONS/SAFETY-40.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01LyR88rXETvwhTgx6yHE39p
2026-09-26 22:37:01 +02:00
glenn schrooyenandClaude Opus 5 3527c8a04c SAFETY-41: escalate a sustained engagement, so a runaway is never held
checks / unit (pull_request) Successful in 4m59s
Review found the case I asked it to construct, and it is not a corner
case. The rate limit alone DELAYS A RUNAWAY: a benign one-cycle clamp
that spends the budget, then a continuous §10.3-shaped runaway, held the
runaway's first notification for up to 140 s - one REASSERT_S minus a
cycle. On the live install, where ordinary railing spends the budget
essentially all the time, a runaway arriving during normal operation
would be delayed with near-certainty. That is the "benign noise
suppresses the bug signal" shape this module's docstring is written
against, and the family the first attempt at this card died of.

THE ESCALATION. An episode that has not yet spoken because an EARLIER,
unrelated episode spent the budget speaks anyway once it has engaged
SUSTAINED_CYCLES = 3 times in a row. The discriminator is run length and
the two populations genuinely differ: the live flood was runs of length
ONE (engage, de-assert, engage), while a runaway engages every cycle.

Measured, and it costs nothing it was protecting:
  live scatter flood (305 cycles, 1-in-6)   11 -> 11 notifications
  chatter 1-engaged/3-clean over 8000 s     50 -> 50 notifications
  pinned 900 s quarter (floor is 5)          6 ->  6 alarms
  runaway delay after a benign episode     140 s -> 10 s

⚠️ MY COUNTERFACTUAL CHECK COULD NOT FAIL FOR THE DEFECT IT NAMED, and
review caught that too. It read `ClampWatchdog().note(True, ...) is True`
- a FRESH object, which only exercises the `last_alarm is None` branch,
the trivially-true one. A fresh watchdog has no earlier episode to be
held back BY. It now SPENDS THE BUDGET FIRST: benign clamp, gap past
CLEAR_CYCLES, then a continuous runaway, and asserts the delay is well
under REASSERT_S. That is the third instance in this file of the family
recorded at line 216 and at the 224 s sweep, and it was guarding the most
safety-critical property in the change.

Also pinned: `last_alarm` SURVIVING the de-assert. Review built the
mutation - if the de-assert also refreshed it, chatter collapses from 50
notifications to 1 and the alarm never fires again, with the suite green.
That is the "alarm that never fires" class, a different bug from one that
fires later. Now caught.

Both new checks verified against the mutations they name: removing the
escalation -> 1 FAILED; refreshing last_alarm on de-assert -> 1 FAILED.

Full suite: 21 passed, 0 failed.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
2026-09-05 18:13:09 +02:00
glenn schrooyenandClaude Opus 5 8790c4d38f SAFETY-41: rate-limit the RISING EDGE, which is where the flood came from
checks / unit (pull_request) Successful in 5m9s
Review falsified the first version of this change, and the correction is
the substance of it.

Raising REASSERT_S 30 -> 150 removed NONE of the owner's notifications.
The re-assert interval governs only the still-engaged path; the rising
edge fired unconditionally. At the measured ~5 s cycle the live pattern -
48 engagements in ~25 minutes, about one cycle in six - leaves ~25 s of
clean cycles between engagements, past CLEAR_CYCLES x 5 s = 15 s. So the
alarm DE-ASSERTED between almost every engagement and each one returned
as a fresh rising edge. Measured on the shipped class over that window:
48 episodes, 48 notifications at REASSERT_S = 30, and still 48 at 150.

The interval now bounds the NOTIFICATION RATE rather than the repeat rate
within one episode: `last_alarm` survives a de-assert, and a new episode
speaks only if the interval has elapsed. Same window afterwards: 51
episodes, 51 engagements, 11 notifications.

⚠️ NOTHING IS DROPPED, AND THE TWO PROPERTIES THAT MATTER ARE PINNED:
  - a PINNED loop still speaks 6 times in the 900 s billing quarter,
    against a floor of 5 (part 2, unchanged);
  - a rising edge from a COLD watchdog still fires IMMEDIATELY, so a
    runaway beginning from quiet is never held back by a budget spent on
    an earlier, unrelated episode. That check is the counterfactual and it
    is the half that would go red if the limit ignored elapsed silence.
Every engagement is still counted, every episode still increments, and
the action-log row is still written on every engaged cycle. The budget is
on notifications, never on evidence.

The new pin is written in wall-clock seconds and in the shape the field
produced, so it does not move when the constant does. Verified by
reverting the rising edge to unconditional: 2 checks go RED naming it.

Full suite: 21 passed, 0 failed.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
2026-09-05 17:06:29 +02:00
glenn schrooyenandClaude Opus 5 1d393ced22 SAFETY-41: correct the comment, and fix the check it cites
Review found two false statements in the comment and one weak check. All
three are fixed here; the constant itself is unchanged at 150 s and was
never in question.

1. "That caps this constant at 900/5 = 180 s" was FALSE ABOUT THE CHECK IT
   CITED. test_clamp.py part 2 sweeps i = 0..899 and the rising edge at
   i=0 is free, so it measured `1 + floor(899/R)` - one alarm more than a
   real quarter earns. Measured: 224 s was GREEN across the whole suite.
   Anyone raising this to 200 s would have had a green board and a
   requirement quietly unmet - the same defect recorded at
   test_clamp.py:216, one notch weaker.

   The check now grades floor(QUARTER_S / REASSERT_S) directly, so it
   enforces the ceiling the comment claims for it. Verified: 150 PASS,
   180 PASS, 181 FAIL, 224 FAIL. 180 is also the true requirement edge -
   on the worst sliding 900 s window 180 earns 5 alarms and 181 earns 4.

2. The "60 cycles of the §10.3 runaway" note was attributed to this module
   and truncated. It is main.py:2479 and reads "60 cycles of the §10.3
   runaway produce 0 write-path engagements and 2 loop-side ones". Quoted
   in full, attributed correctly.

3. "48 engagements in 25 minutes" was left implying a pinned rail. It is
   roughly one cycle in six - real, and far above the 2-in-60 the guard
   was sized for, but not continuous. Restated, and labelled as a live-log
   reading rather than a measurement in this repo.

Also recorded: the 1500 W tuning derivation is in the OTHER repo
(admin/goodwe NOTES.md, "Simulated 2 kW load step (gain 0.6, clamp
1500)"), so this repo cannot corroborate it and a reader should not go
looking here; and MIN_PER_QUARTER = 5 is a test-local integer, not a spec
figure - the 900 s quarter is system-wide but the 5 is not, so the 180 s
ceiling rests on one number a test author chose.

Full suite: 20 passed, 0 failed.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
2026-09-05 16:53:46 +02:00
glenn schrooyenandClaude Opus 5 3516947b5e SAFETY-41: raise the clamp alarm's re-assert 30 s -> 150 s
The owner reported the OUTPUT_CLAMP notification as a persistent
annoyance on the live install. It re-asserted every 30 s, all day.

⚠️ THIS IS A REGIME CHANGE, NOT A CHANGE OF MIND ABOUT THE ALARM. 30 s
was chosen when a loop-side engagement was rare - clamp.py's own note
records "60 cycles of the §10.3 runaway produce 2 loop-side engagements".
The live install produced 48 IN 25 MINUTES of ordinary operation, because
`max_w` is 5000 W where the loop's tuning was derived at a 1500 W clamp
(SAFETY-39). The integrator therefore reaches its bound constantly and
the alarm narrated it every 30 s. An alarm that speaks that often about
the normal case is how an operator learns to ignore the one that matters,
which is the exact failure clamp.py's docstring is written against.

⚠️ 150 s IS THE REQUIREMENT'S OWN EDGE WITH ONE STEP OF MARGIN, not a
comfort choice. test_clamp.py part 2 pins the cadence in WALL-CLOCK terms
rather than against this constant: a loop pinned on the rail must speak
at least MIN_PER_QUARTER = 5 times inside the 900 s quarter that bills
the capacity tariff. That caps the constant at 900/5 = 180 s. Measured:
  180 s -> 5 alarms per quarter (exactly the required 5, no margin)
  150 s -> 6 alarms per quarter
  300 s -> 3, and the floor check goes RED
180 s would sit on the boundary, so any later change to the firing logic
would tip it red for a reason unrelated to that change. The FLOOR is the
thing that must not move, and it does not.

⚠️ WHAT THIS DOES NOT DO. It changes how often the alarm repeats. It does
NOT make the alarm correct: the message still calls the integrator bound
a BUG SIGNAL and still pairs a request from one moment with a `self.target`
read at another. That is SAFETY-40. And it does not stop the loop railing
in the first place; that is SAFETY-39. This is a stop-gap and says so at
the line.

Nothing was suppressed: every engagement is still counted, the action-log
row is unchanged, and the §10.3 runaway still raises the alarm - an
earlier attempt at this that split the alarm so only `clamped` notified
was REVERTED because test_clamp.py:398 proved it would have disabled
runaway detection entirely (a runaway presents as `i_clamped`, and
control.py:78-81 says `clamped` is unreachable on a default install).

Full suite: 20 passed, 0 failed.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
2026-09-05 16:53:46 +02:00
adminandClaude Opus 5 83911ed637 SAFETY-20: measure the freeze rail against the reachable ceiling, not max_w
checks / unit (pull_request) Successful in 3m37s
SAFETY-18's conjunction needs `abs(commanded_w) >= 0.95 * max_w`, but the
emitted command is clipped to the setpoint device's own [dev_min, dev_max]
range as well as to max_w - in clamp_to_rating()'s second stage and again as
the arbiter's `device` P_SAFETY limit claim. Measured on the shipped predicate
at the ticket's numbers, max_w 5000 on a +-4700 W inverter:

    looks_frozen(unchanged_s=3600, commanded_w=4700, max_w=5000)  ->  False

The command is pinned at the hardware's rail, the meter has been frozen for an
hour, and term 2 is unsatisfiable by construction because 4700 < 4750. Any
device rating at or below 0.95 * max_w disarms the conjunction outright, and
the status page then printed `armed (... command is over 4750 W)` - a guard
that cannot fire, advertising that it can, which is the failure SAFETY-15,
SAFETY-19 and validate.py rule 5 all exist to prevent.

The rail is now measured against min(max_w, |dev_min|, |dev_max|), through a
new `rail_ceiling_w()` threaded into looks_frozen(), FreezeWatchdog.evaluate()
and both call sites in main.py. An unread rating leaves the old behaviour
exactly, and correctly: hass.limits() returns None whenever ESPHome is not up,
and on that path no device clamp is applied either, so max_w really is the
ceiling. A rating larger than max_w cannot raise the rail - this is a min(),
not a swap.

THE DELIBERATE CHOICE, since SAFETY-03 has landed. The arithmetic was kept
rather than substituting Decision.i_clamped / Decision.clamped. i_clamped is
the integrator bound (control.py:208, `bounded != i_w`), not "the command is
at the device rating", and `clamped` is the max_w output bound, unreachable on
a default install - neither is the device rail. More decisively, both answer
"did the LOOP ask for more than a bound", while the rail term asks "is the
command standing at the ceiling", and those coincide only when the loop is the
claimer that won. A maintenance SET or a peak-guard floor reaches the ceiling
through arbiter LIMIT claims with no clamp engaging at all, so a boolean rail
would go False exactly during a maintenance phase running against a frozen
meter - which freeze.py's own docstring names as the same fault with a worse
actuator behind it. The predicate is also public with two call sites that pass
DIFFERENT command values (self.target, and `standing` = last_write); a
per-cycle boolean cannot be passed per call site, so substituting it would
have silently decided the pre-clamp-versus-wire question that PM recorded as
still open. AC 1 governs, and it is satisfied literally.

The smaller of the two device bounds, not a per-sign pair. A per-sign rail is
tighter and is not wrong, but it is two rails needing two coverage verdicts on
a status row that carries one number, and the only configuration that
distinguishes them is refused at startup anyway. The symmetric ceiling can only
lower the rail, which widens term 2 rather than disarming it; term 1 carries
the whole no-false-positive argument and is untouched.

A ceiling of 0 W is NOT COVERED, not "armed at 0 W". A device that can command
nothing in one direction would make `abs(command) >= 0` true of every command
including a parked one - term 2 degenerately TRUE, collapsing the conjunction
into the bare unchanged_s > N threshold TEL-05 refused for false-tripping at
this controller's own operating point. rail_unreachable() returns the reason,
looks_frozen() stays silent, and the page uses the NOT COVERED row the
unsupported-transport case already has - a second reason to use that surface,
not a new mechanism.

AC 4, decided rather than assumed: NO NEW validate.py RULE. The configuration
is max_w above the device rating, which rule 2 (CFG-01) already refuses on the
identical predicate, re-run by run_control() once the real rating is known:

    validate_startup_config({... max_w: 5000}, -4700, 4700)
      -> ['max_w is 5000 W but number.sp accepts at most 4700 W - THE DEVICE
          WINS ...']

A rail-specific rule would fire on a strict subset of that (0.95 * max_w >
dev_max implies max_w > dev_max) and could never be the rule that stopped a
start. The residue is the state where hass.limits() answered (None, None) -
ESPHome not up at boot, range checks skipped rather than guessed at, rating
never re-read - and there is nothing to refuse there by construction, which is
why the answer is a runtime row. Recorded in validate.py's "deliberately not
refused" list and pinned by four checks in test_validate.py, so the decision's
premise goes red if rule 2 is ever softened back to a warning.

HOW REACHABLE THIS IS, stated rather than glossed. Because rule 2 refuses the
configuration whenever the rating is known, min(max_w, dev_max) IS max_w on
every install that reaches the control loop with a rating it could read, and
this change is arithmetically dead there. That is clamp.py's argument for its
own second stage word for word: the case where it bites is the case where the
startup gate did not run or no longer holds, and a guard that quietly assumes
the gate ran is a guard that reports armed in exactly the state it cannot fire
in.

Verified by breaking it, per this project's rule. Reverting rail_w() to bare
max_w fails nine checks; deleting the NOT COVERED handling fails five. The one
that mattered: shipping the corrected predicate while NOT passing the rating
from check_meter_frozen() left the entire suite green, because nothing graded
the caller - so test_freeze.py part 5b now drives the real cycle() on a +-4700 W
device and asserts on the notification that leaves the process, and the
unwiring mutation fails three checks there. The peak-guard call site's wiring
is still ungraded (behind p1_enabled, needs a fed averager for `frozen` to have
any observable consequence) and that gap is named in the file rather than
implied.

Full suite: 15/15 in goodwe-addon-ci.

Co-Authored-By: Claude Opus 5 (1M context) <noreply@anthropic.com>
2026-09-01 02:14:07 +02:00
glenn schrooyenandClaude Opus 5 4e66583a52 SAFETY-03 review fixes: both clamp stages always run, and two checks that could not fail
1. BEHAVIOURAL, and a regression this PR introduced. clamp_to_rating() returned
early from the max_w stage, so the device bound was applied only when the rating
bound had NOT fired - the bigger the overshoot, the less the guard did. At max_w
5000 against a +-4000 device, +9999 emitted +5000 W, outside the device range,
while +4500 was correctly held to +4000. It undid the pre-PR guarantee "never
send a value the device will reject outright" and undercut this module's own
case for max_w-not-min(), which rests on that stage catching a validation that
did not run. Both stages now always run; the result names both bounds when both
bite (max_w+device). Asserted over a 492-point sweep, because the defect was
invisible to any single-value check sitting inside one stage.

2. The hysteresis check issued range(CLEAR_CYCLES - 1) clean cycles, which at
CLEAR_CYCLES = 1 issues zero, passes, and prints "0 clean cycles do NOT clear
it" - green for the chatter setting the constant exists to prevent. Now: ONE
clean cycle must not clear the alarm, a literal that does not move with the
constant, and the de-assert count is measured by looping until it clears.

3. The re-assert check stimulated at REASSERT_S + 9, green for any value
including 3600 - the hour of silence the module promises not to produce. Now
stated in wall-clock terms: a loop pinned across the 900 s capacity-tariff
quarter must speak at least 5 times and on no more than 20% of cycles. Pinned in
both directions.

Red confirmed for each: the restored early return (3 checks), CLEAR_CYCLES = 1
(1), REASSERT_S = 3600 (1) and REASSERT_S = 0 (3).

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_015VXjA3LWccN1rJsk3okyPC
2026-08-30 15:52:09 +02:00
glenn schrooyenandClaude Opus 5 c040aac4b8 SAFETY-03: alarm when a computed setpoint exceeds the rating, do not just clip it
The clamp was never the missing half. specs.md 10.3 records an unclamped
integrator climbing ~130 W per 4 s past 10 kW and reporting 14 768 W pinned at
the 5 kW rail; clipped silently that is a flat, legal-looking 5000 W hold and
nothing says the loop asked for three times it.

write_setpoint() - the one path every write takes - now clamps to the VALIDATED
max_w and reports whether the raw value differed; check_output_clamp() raises
OUTPUT_CLAMP as a notification, an ERROR, an event row and a red status banner.
Not a trip: the clamped value is written and the loop keeps running.

The rating is max_w and nothing is min()ed at runtime - CFG-01 already refuses a
max_w outside the device range at startup. The device range is applied second as
defence in depth; it cannot bite after a successful validation, so if it ever
does it alarms too and names the bound. No new config key.

Decision grew i_clamped / clamped booleans, and that is the load-bearing part:
`reason` is one string that slew-limiting and the saturation freeze overwrite,
so an alarm keyed on it is silent on exactly the cycles a winding loop produces.
Mutating main.py back onto the string drops the 10.3 replay from 2 engagements
to 0.

Distinct from saturation by construction - no shared reason code, notification
id, status row or counter - and checked in the negative, after first asserting
the saturation freeze really did engage.

Two things found by running it rather than by reading it: a row per engagement
flushed the 40-row event log and evicted SAFETY-18's own METER FROZEN? row (now
coalesced per episode with an exact count), and a naive clamp turns a nan into a
command at the full rating because every comparison against nan is False.

test_clamp.py is new: assert-based, no framework. Six author mutations
reproduced red, including "clamp kept, alarm deleted". Two of the check's own
hypotheses about the freeze/clamp interaction were refused by its sweep and
rewritten to what it measured.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>