9d3fbe1be9 |
SAFETY-90: the peak guard goes on after a P1 meter gap
A meter gap past meter_max_age_s left seconds the quarter average never counted, so the guard was blind for the rest of the quarter (rig case 7b: 3964.8 W against a 3450 W aim). Once readings are back, the missed seconds now count at the higher of the limit and the import seen just before and just after the gap with the batteries at 0 W (peakguard.gap_w/fill_gaps); the gap's first meter_max_age_s is topped up to that too. Seconds before the add-on's first reading count at the aim, and the page says part of the period was not measured (EN/NL). The bill record is unchanged; no option. DECISIONS/SAFETY-90-peak-guard-after-a-gap.md, test_safety90.py. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> |
||
|
|
d0db5b8c39 |
SAFETY-87: peak guard uses every battery that can still give
At N>=2 a battery at or under its own peak reserve is held: it gives nothing for the peak (weight 0 while the site gives) and the guard's need is placed on the live, non-refusing batteries above theirs. The guard is floor-limited, and alarms, only when those cannot hold the limit at full power for ALARM_HOLD_S. The peak alarms no longer read "Not ready" or hold the Home page at 0 W, because control keeps running. N=1 is byte-identical. DECISIONS/SAFETY-87-guard-uses-able-batteries.md. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_019DBUfvndgHwaV339Fvd2gr |
||
|
|
f967073cfe |
SAFETY-81 review: 10 s hold, ERROR line per episode, more scenarios
- The alarm must hold for peakguard.ALARM_HOLD_S (10 s) on the projection's
clock. A load that tops cap + battery for ~5 s every 30 s alarmed at every
quarter start while the quarter landed under the aim (sine4500_fast).
- A cycle with no battery reading leaves the hold alone.
- Notified once per quarter, but the ERROR line is written per episode.
- New sim scenarios (sine4500_fast, twice7000, step6500_gap) with
|
||
|
|
6eb67c0f9c |
SAFETY-81: no false 'Load too high' alarms
The alarm now also needs peakguard.load_too_high(): with the battery at full power, the quarter still ends more than 10 W over the real limit. The battery reading is the lower of this cycle's and the last, so a meter sample from before the battery's last increase is not counted twice. At most one alarm per quarter. Control outputs unchanged. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> |
||
|
|
ce0aea30b6 |
SAFETY-79 review: margin under a banked month peak too; identity harness reaches headroom and maintenance
- quarter_target_w() is now the margin under quarter_ceiling_w(): a peak
banked between cap - margin and the cap was aimed at exactly, so one
overshoot crossed the cap; above the cap the same overshoot raised the bill.
- safety79_identity.py hashes charge_headroom_w() and the shaping suspension,
and adds n1_maint/n2_maint (cheap window, forecast across cap - 50 .. cap).
Digests re-printed on
|
||
|
|
7c4c8f5c66 |
SAFETY-79: peak guard keeps a margin below the limit
New option peak_margin_w (default 50 W, 0-500 W). The peak guard, the
forecast checks and the maintenance charge sizing aim at
peak_cap_w - peak_margin_w; the month peak, the bill, headroom, warnings
and every notice keep the real cap. Owner decision 2026-09-28.
peak_margin_w 0 is byte-identical to
|
||
|
|
e0b578756f |
UX-10 review: the line as logged gets the red-alarm shape, clamp lines at 30 words, plain HA 400
Part 6 checked the quoted reason alone, so title + reason + tails logged as 4+ sentences. It now also checks the whole line (at most 3 sentences, none over 30 words); 25 lines failed and are rewritten (one-sentence wrappers, two-sentence circulation and peak reasons, STALE_READING's fixed limits on a DEBUG line). The clamp lines for one inverter are pinned at 30 words with OUTPUT_CLAMP and the numbers kept. Home Assistant's bare '400: Bad Request' while it loads becomes one plain line; still WARNING, throttled, a failed write. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> |
||
|
|
23a3a3f5b5 |
UX-10: the last plain-language leftovers: log lines, two table rows, 'Why: Other', red at 0 s
- test_messages.py part 6: every dynamic part of a WARNING+ line is classified as data or as a built text, and every built text is produced by the real code and checked. This is the gap the 2d scan had: it counted `%s` as one word, so reasons built by loop_clamp_note() and friends were never seen. - Quoted reasons rewritten to STYLE.md (red-alarm shape, codes kept): OUTPUT_CLAMP, METER_FROZEN, CIRCULATING_POWER, STALE_READING, the peak guard (codes now PEAK_GUARD*), the migration report, price feed, price history and gate reasons. Plurals via messages.times()/count(). - Top table: Price history "96 prices over 24 hours for 26 Sep", Tariff "one every 15 minutes or every hour", "not final yet" dropped. - Levels and noise: per-cycle shadow line DEBUG, shadow on/off INFO, aiohttp access log only at log level debug, settings warnings once per start, one plain line per Home Assistant outage (hass.Outage). - INFO jargon and error texts: no "§8.3", ISO times, "banked", "keys ARE", "NOT_OBSERVED", "did NOT land", "AND". - Display bugs: WHY_WINNER covers every winner and safety reason (main.why_key(), part 7 finds them in the code); the meter row is amber "waiting for the first reading" inside its limit after a start; the missing-reading age is counted when the page asks. - STYLE.md and DECISIONS/UX-08-short-notifications.md (UX-10 section). No change to safety behaviour, alarm levels, notification ids, triggers, cadence or the banner cascade. One row colour changes (meter at start), justified in DECISIONS. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> |
||
|
|
6a95447248 |
UX-08 2d: plain log lines, the rest of the status page, and DOCS
Every WARNING and ERROR line is one plain line of at most 25 words, with no card ids, capitals or semicolons; the reasoning of the ten longest is on a DEBUG line. The ux08 allowlist is empty and its cap is 0 (43 -> 0). The status page: the month-peak and peak-guard rows, the stale-reading row, the top table (Why, Tariff, Arbitrage, Shadow mode, labels), the Stopped banner and the line under the buttons, which now shows the plain hint of each event instead of the raw action log. The Supervisor question at start logs one line with a real reason. Refusals are counted as shown (labels expanded, long cases driven), seven were shortened, the card and parse errors lost their internals, a blank value reads "empty", and the panel no longer files inverters.max_w under the flat max_w. Option names lose "(JSON)", the NL texts are checked too. DOCS gets a glossary (control board, isolator, Developer Tools) and card ids move from headings to a "For installers" line. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01LyR88rXETvwhTgx6yHE39p |
||
|
|
e1b9254626 |
SAFETY-45: a price-driven charge is SIZED by the capacity guard, not switched by it
checks / unit (pull_request) Successful in 7m42s
With arbitrage armed at the shipped defaults, arbitrage and the capacity-tariff guard drove each other in a sustained limit cycle. Re-measured on TEST-23 stage 3's closed rig against |
||
|
|
f9e7fbf86d |
SAFETY-32: bms_soc_floor per pack, rule 8 per unit
`bms_soc_floor` describes A BATTERY, not a site. At two packs of different models the cut-outs differ, and one number for both graded the shallower pack against the deeper one's BMS - so a site with cut-outs of 10 % and 30 % under `peak_soc_floor: 20` STARTED, and the guard would command a forced discharge that pack B's BMS, not the operator's floor, is the thing that stops. That is rule 8's own failure mode, reached through rule 8. Scoped to the card's third bullet, per its PM PROOFREAD: the aggregate anti-windup (DEV-02) and per-instance `achievable_w` (CFG-04) were verified as already shipped and are untouched. * config.yaml: `bms_soc_floor: int(0,50)` REQUIRED per `inverters:` entry. Nothing is inherited; the flat key stays the single-inverter shape's own cut-out. A per-entry DEFAULT was declined - a default is one number for every pack, which is this card's defect - and the decision is recorded. * inverter.py: `Inverter.bms_soc_floor`; an entry that states none gets None, not a borrowed number and not 0.0 (the most permissive value the key has). * peakguard.py: `Pack`, `pack_floor_pct()`, `pack_permissions()`, `binding_soc_floor()`. `discharge_permitted()` is unchanged and is still the one place the question is answered. * validate.py: `unit_bms_floors_indexed()` carries the ROSTER index; rule 8 grades EVERY unit and NAMES the one it refuses. Graded with the offender SECOND and with the same two numbers in the other order. * main.py: `Controller.packs`; `decide(soc_floor=...)` is the per-pack reduction of the same option; the floor-limited notification names the pack that stopped the site. `pack_floor_soc` - the emptiest pack, and its None-on-missing behaviour - is untouched. * tools/supervisor_shape_probe.py: RE-RUN and repaired. The required key broke §C and left §D printing PASS on a refusal about a different key. §D is now an isolated counterfactual over an accepted merged baseline, one key varied, asserting the key name. `all cases passed` on 2026.08.0. Stated rather than hidden: under any config rule 8 accepts the per-pack FLOOR reduces to `peak_soc_floor` for every pack. The reduction is written for `unit_caps_indexed()`'s reason and graded on both sides - 1775 rule-8-valid pairs answer the option, the pair rule 8 refuses answers the cut-out. `peak_soc_floor` is still one number for the site, so the "deeper pack needlessly withheld" half is filed as an open question, not closed. Full 19-file suite green. Twelve source mutations through tools/mutation_run.sh: eleven red, one argued survivor. The battery also found `_flat_bms_floor()` defaulting in two places, each covering for the other. No measurement of inverter B appears anywhere: it does not exist yet. Every second-pack figure is simulated and labelled. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU |
||
|
|
06f95e0a64 |
ARB-03: restore Claim.actuator and make resolve() three-stage
checks / unit (pull_request) Successful in 3m45s
specs.md:467 declares `actuator: str` as the FIRST field of `Claim`.
app/arbiter.py:55 had no such field. The specification designed
per-actuator claims and the implementation dropped it, so every claim was
implicitly about "the one and only actuator", resolve() returned one scalar
Resolution.target_w, and main.py assigned it to one self.target. THERE WAS
NO SEAM AN ALLOCATOR COULD OCCUPY - and ARCH-01 (specs.md §6.2, 2026-09-02)
decided the site grid target is ALLOCATED across several inverters and never
broadcast. This is a regression fix against the written design; creating that
seam is the whole of the change.
WHY IT MATTERS, IN THE UNITS THE SYSTEM IS BILLED IN. The control primitive
is meter emulation: the master reports a fabricated grid reading and the
inverter regulates itself to it, so one number means "the battery moves X W"
to the add-on and "the grid is at X W" to the inverter - an identity that
holds only at N=1. Broadcast one target to two inverters and each supplies it
in full; the loop gain at the meter becomes N times the per-unit gain, which
at the gain config.yaml:374 accepts is a permanent limit cycle with every
watchdog in §11.2 reporting healthy. And a per-inverter reserve filed as a
site `hi` against the peak guard's site `lo` is `lo > hi`, arbiter clause 3,
0 W IN THE BILLED QUARTER - the parked battery SAFETY-25's memo calls fatal.
THE SPLIT, VERIFIED AT EACH CONSTRUCTION SITE RATHER THAN ACCEPTED FROM THE
SURVEY. Four sources are about the GRID CONNECTION and are SITE claims:
`loop` (compute() regulates grid_w, the P1 measurement, and §6.2's whole
architecture is one integrator on P1 whose output is then split), `peak` (the
15-minute average offtake AT the grid connection, which is what the capacity
tariff bills - one quarter-hour peak per site, not one per pack),
`arbitrage` (buys and sells at the grid against a day-ahead price; the price
is a property of the connection and the energy crosses the meter) and
`safety` (both construction sites read: "stopped" is the operator switching
control off for the site, "inputs missing" is the site's own meter gone -
neither is about a pack, and both must stop every inverter).
Four are about a pack, a device or one write and are PER-INVERTER: `device`
(one inverter's own reported min/max - there is no site rating),
`supervised` (max_w caps what may be WRITTEN to one setpoint entity, §11.3,
so it is scoped like `device` for the same reason), `maintenance` (§12's
recalibration is a pack procedure - drain THIS pack, charge THIS pack,
recalibrate THIS pack's counter) and `failsafe`. `failsafe` is the entry that
needed the reading rather than the survey: SAFETY-02's EVIDENCE is site-wide
(it compares P1 against the standing command) but its CONCLUSION is
"the unit I am driving is pushing power the wrong way" and its remedy is to
park that unit. At N>=2 the same evidence cannot be attributed to a sibling
this controller never commanded, so a site-wide stop would park an inverter
this watchdog never graded. The reasoning for all eight is recorded AT THE
LINE, in arbiter.CLAIM_SCOPE and again at each claims.append in main.py.
WHAT WAS BUILT. resolve() is three stages, each a separate function so a test
can construct a case at any one of them:
pre_resolve() - one inverter's own claims -> that unit's interval. Clauses
1 and 2 transposed: the unit's own winning SET gates its
own limits. The SET's value travels BESIDE the interval,
not inside it - folding a -2500 W drain into
[-2500, -2500] would turn "clamped to max_w" into
"contradicts max_w", a different and wrong answer.
site_resolve() - THE SHIPPED ARBITER, UNCHANGED. Same code, new name.
allocate() - THE SEAM, AND DELIBERATELY NOT AN ALLOCATOR. ALLOC-01
builds it. At N<=1 it passes the target through (§6.2's
identity). At N>=2 it DECLINES - no shares,
allocated=False - and main.py refuses to write rather than
broadcast, because the obvious placeholder (hand the target
to each) is the fault ARCH-01 was filed about and no guard
we have can tell it apart from the real thing.
THE CONTRADICTION IS NOT GUARDED AGAINST, IT CANNOT BE WRITTEN DOWN. The
partition is by `actuator` and it is a partition: a unit's `hi` and the site's
`lo` are never both terms of one `lo > hi` test. Constructed and swept - 40
filings (every per-inverter source x unit x bound, including a unit
contradicting ITSELF at lo 900 > hi 100) against a live site floor, and not
one moves the site target or raises a contradiction. A unit's own impossible
pair parks that unit and says so on its own bounds; it does not park the site.
That is SAFETY-25 §0c's table made mechanical.
AT N=1 THIS IS A PURE REFACTOR, AND THAT IS PROVEN RATHER THAN ASSERTED. With
one inverter the fabricated grid reading and the battery setpoint are the same
number, so the grid connection and the only unit ARE one actuator:
actuator_for() routes every source to the site, no claim is filed on a unit,
stage 2 sees the whole list and answers what the shipped arbiter answered.
All 17 suites replay UNEDITED above the ARB-03 sections and are green on the
same numbers; test_arbiter.py additionally runs 13 claim lists through both
resolve() and site_resolve() and compares target, winner, binder,
contradiction flag, the considered list and the operator line.
EVIDENCE, BY BREAKING EACH THING (tools/mutation_run.sh, purged tree):
* Claim's dataclass default emptied -> RED (test_arbiter)
...and it survived until the check was added: the two helpers pass their
own default down, so the FIELD's default never ran. Now checked directly.
* `peak` reclassified SCOPE_UNIT -> RED (arbiter x4, peakguard x2)
* `maintenance` reclassified SCOPE_SITE -> RED (arbiter x4, peakguard)
* the N=1 identity dropped in actuator_for() -> RED (arbiter, peakguard
incl. the maintenance/peak suppression checks, freeze) - which is the
measurement that says splitting at N=1 would be a behaviour change
* resolve() stops partitioning -> RED (arbiter x4)
* allocate() broadcasts at N>=2 -> RED (arbiter x2)
* stage 1 drops clause-2 gating -> RED (arbiter)
* a call site routes `device` through `loop` -> RED (peakguard 10g)
* SAFETY-25 Option B built as a ninth source -> RED (peakguard 10f, both
halves, plus 10g) - the tripwire still bites
SAFETY-24's asymmetry proof is re-run and holds: 0 negative floors over the
shipped sweep, `hi` still +inf on every claim the guard files, and it now also
asserts every one of them is on the SITE actuator - a floor bound to one
inverter's share would leave the site, the thing the capacity tariff meters,
with no floor at all.
test_peakguard.py part 10f is kept, not adapted around. `source` is still
Claim.set()'s first positional argument precisely so its AST scan keeps
reading it, which is why `actuator` is the LAST field of Claim and not the
first - moving `source` off position 0 would silently blind the tripwire that
guards SAFETY-25's deferred option. The one adaptation is `**kw` on its spy,
so main.py's roster passes through unread rather than being silently dropped.
New part 10g pins CLAIM_SCOPE to the same eight-source set and grades a REAL
two-inverter cycle, which is the only place a mis-typed actuator_of(...) at a
call site is observable - at N=1 every source legitimately routes to the site,
so a swap there is invisible by construction.
No config key, no option, no operator surface, no default moved. Inverter B
does not exist yet and nothing here measures it.
Co-Authored-By: Claude Opus 5 (1M context) <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
|
||
|
|
ab6fbe2f9e |
SAFETY-25: record the owner's decision - option a, with alloc-01 as the revisit trigger
checks / unit (pull_request) Successful in 3m43s
The product owner answered SAFETY-25's §1 on 2026-09-02: OPTION A. The BMS cut-out is the DELIBERATE and only backstop for demand-driven discharge on the grid-following loop, and Option B - a loop-side reserve floor - is DEFERRED rather than rejected. Option A is the shipped behaviour, so this is a recording, not a change. `app/` is touched in exactly two places and both are comments that claimed the question was still open (freeze.py's finding, peakguard.py's point 2). No setpoint, no claim, no option, no default moved. The 17-suite run is green on the same numbers as before. WHY DEFERRING IS THE SAFE DIRECTION. Option B's proof - bms_soc_floor < loop_soc_floor <= peak_soc_floor, run through the real arbiter in test_peakguard.py part 10d - has an unstated premise: the reserve predicate and discharge_permitted() read the SAME state of charge. With two packs they read different numbers. The reserve binds on the emptier pack and files hi = 0; the peak guard, reading the other pack or an average, files lo = excess > 0; lo > hi is arbiter clause 3 and the answer is 0 W - the battery parked in the billed quarter, which is the failure the memo itself marks fatal. And no config validator can catch it: it is a runtime divergence between two readings, not a config ordering, so CFG-01's shape of check passes on the exact tree that parks the battery. Option A's cost is energy; Option B's cost built too early is the one quarter of the month that sets the bill. THE REVISIT TRIGGER IS ALLOC-01, recorded in §0c. Under ARCH-01's host-side allocator the two claims stop sharing a list: the loop floor becomes a per-inverter `hi` consumed as an INTERVAL at stage A, while the peak floor stays a site `lo` at stage B. Different claim lists, different stages, structurally unable to cross - a stronger argument than the ordering rule, because it makes the crossing unreachable rather than harmless. That is the shape in which Option B becomes safe to build. WHAT HAS TO BE RE-EARNED AT N=2 is stated plainly in §0d rather than left for someone to discover. SAFETY-27 now names five floors across two packs, so "the SoC" stops being a scalar the config can bound. And part 10f - the pin that made SAFETY-25 mergeable - CANNOT EXPRESS TWO PACKS: its dynamic half is a scalar 0-100 % SoC sweep against a single-series capture, and a two-pack exposure lives in the DIFFERENCE between two readings, which that sweep visits at no resolution. Its static half, the AST scan pinning the eight claim sources, still bites at N=2; the dynamic half goes silent. Merging a two-pack reserve on 10f's current green would be merging on a check that cannot see the failure. The options analysis is kept intact on purpose - §1-§7 stand exactly as written, including §5's "(recommended)" on Option B and §6's recommendation, with a new §0 saying what was decided and §6 marked as answered. A memo that recorded the verdict and deleted the reasoning is the failure this DECISIONS/ directory exists to prevent. Part 10e's check moved with the memo: it used to pin the honest "Status: OPEN" line and now pins that the memo names the option, the date and the trigger AND still carries both options and the recommendation. The tripwire itself stays - a ninth claim source in Controller.cycle() still takes 10f red on the line it is written, and "deferred" is precisely the state in which someone builds Option B by accident. Co-Authored-By: Claude Opus 5 (1M context) <noreply@anthropic.com> |
||
|
|
182102eeaf |
SAFETY-25: say what peak_soc_floor bounds, and measure what it does not
checks / unit (pull_request) Successful in 3m41s
peak_soc_floor reads like a pack-wide reserve and is not one. The
grid-following loop has no SoC guard of any kind, so on a sustained-load
evening it discharges straight past that number and keeps going until the
pack's own BMS cut-out stops it.
The gap has now been written down four times without being filed -
SAFETY-18's finding (freeze.py:18), SAFETY-24's module note, its PR body,
and its honestly-uncaught 13th mutation - and never once measured. It is
measured here, on the committed 2026-08-20 capture, driving the SHIPPED
control.compute(), peakguard.decide(), peakguard.claim() and the real
arbiter.resolve() in main.py's order:
19:00-22:00 UTC, 830 W mean, minimum 701 W, zero export in the window
reference pack (300 Ah x 51.2 V x DoD 90) started at 21 %, one point
above peak_soc_floor
ends at 10.0 % - the bms_soc_floor cut-out
1525 Wh delivered by the LOOP over 587 cycles
549 cycles below peak_soc_floor, 343 of them still discharging
0 cycles on which the peak guard filed any floor at all
AND IT IS A BEHAVIOUR, NOT A CONFIG VALUE. The same evening ends at
9.9715 % at peak_soc_floor = 5, 11, 20 and 60 - the shipped value and both
ends of the schema range - identical to four decimal places. The option an
operator would reach for cannot move the number by any amount at all. On
the same day's high-load block the two states coexist: 49 cycles reporting
PEAK GUARD FLOOR-LIMITED and, on all 49 of them, the arbiter simultaneously
granting the loop up to 2000 W of discharge.
WHY SAFETY-24 COULD NOT CLOSE IT. The peak guard files a `lo` limit - a
LOWER bound on the setpoint. That asymmetry is exactly what makes it
trustworthy: a reviewer proved across 19,800 combinations that it can never
lower a target, cap a discharge or contradict the arbiter. The same property
makes it structurally incapable of stopping a discharge the loop itself
wants. A floor on the guard cannot become a floor on the pack by being
raised, and the sweep above is that sentence measured.
WHAT THIS COMMIT CHANGES IS THE HONESTY, on the four surfaces an operator
actually reads. That half is required whichever way the open question is
answered, and it is the real misstatement on the live system today:
* config.yaml, beside the option itself - it BOUNDS THE PEAK GUARD ONLY
and is NOT A PACK-WIDE RESERVE, with the replayed evening and the sweep;
* DOCS.md, in the options table and in a new section carrying the figures;
* the STATUS-PAGE ROW for a floor-limited guard. This is the one line a
human reads at the moment the guard stops discharging, and read alone it
says "the battery is being held at peak_soc_floor" - which the replay
shows is false in every cycle that row is rendered;
* the PERSISTENT NOTIFICATION, which outlives the page. It now names what
has stopped (the guard buying a lower bill) and what has not (the pack
being spent).
peakguard.py and freeze.py carry the measurement beside the findings they
already recorded, so the next reader does not have to take the caveat on
trust.
THE PRODUCT DECISION IS NOT TAKEN HERE, and must not be. Whether the loop
gets a reserve floor of its own decides whether this house's battery may
discharge to the BMS floor on a heavy evening; that moves real energy and it
is the owner's call. DECISIONS/SAFETY-25-loop-soc-floor.md is the memo AC 1
asks for: the options, what each costs, what each protects, weighed against
MAINT-01 (a pack repeatedly at the BMS floor is the SoC-drift condition the
maintenance cycle exists to correct, and an over-tight reserve fights it from
the other side) and against the fact that this would be the FIFTH SoC key -
OPT-04's arbitrage_soc_floor fired SAFETY-24's "revisit if a third floor
appears" trigger unremarked, so SAFETY-27's naming decision should land
first. It carries a recommendation and says plainly that it is not a
decision.
It also records a trap found while writing it, and now CHECKED through the
real arbiter rather than described: the obvious shape of a loop-side floor
is a `hi` limit at P_LOOP, and filed while the peak guard is asking for a
positive floor that is `lo > hi` - which arbiter.py resolves to a
CONTRADICTION at 0 W, the battery PARKED in the one quarter of the month
that sets the bill. It is the same crossing-limits hazard
shaping_suspended() already exists to avoid. The ordering
`bms_soc_floor < loop_soc_floor <= peak_soc_floor` removes it provably,
because wherever the reserve binds the guard is already floor-limited and
files lo = 0; both halves are run in part 10d.
test_peakguard.py part 10 is a TRIPWIRE, not a guarantee. It records a
defect and goes RED the day somebody builds a loop-side floor, so the
exposure cannot change size under a green suite and closing it has to be
deliberate. Part 11's mutation 13 stays honestly NOT CAUGHT - nothing
prevents the loop discharging past this floor - but it now reports a number
instead of a sentence.
Verified: 16/16 suites green in the CI image. Eight mutations, each against
a tree copied fresh with __pycache__ excluded and mounted :ro, so no .pyc
existed to go stale (MUTATION.md's structural immunity, the same one it
records for CI); byte deltas +61, -8, -465, -430, -1088, -46, file deleted,
and -95; none is +0 B. All eight go red on the named check:
M1 peakguard.claim() also files hi=floor_w -> 7 red, incl. 10c
M2 control.compute() gain forced to 0 -> 6 red, incl. 10a/10b
M3 scope sentence removed from the status row -> 10e red
M4 scope sentence removed from the notification -> 10e red
M5 scope paragraph removed from config.yaml -> 10e red
M6 scope bullet weakened in DOCS.md -> 10e red
M7 the decision memo deleted -> 10e red
M8 arbiter clamps crossing limits instead of
reporting a contradiction -> 5 red, incl. 10d
AC 2 is left explicitly OPEN, pending the owner's answer.
Co-Authored-By: Claude Opus 5 (1M context) <noreply@anthropic.com>
|
||
|
|
e709554857 |
SAFETY-24: an energy floor under the peak guard's forced discharge
checks / unit (pull_request) Successful in 3m29s
SAFETY-07 can command a discharge to hold a billed quarter down, and nothing below it consulted the state of charge. On the 2026-08-20 replay it asks for 878 Wh in a day. Relying on the BMS is not absurd - it is a real floor and it works - but it is the pack's protection rather than the operator's, and a month of aggressive quarters leaves the battery repeatedly at that cut-out with no EMS-side record of why. The first symptom is a pack never available when wanted, which is indistinguishable from the SoC drift MAINT-01 exists to correct. decide() now takes soc and soc_floor, both required and neither defaulted, and discharge_permitted() is the one place the question is answered. Above the floor nothing changes. At or below it the guard files a 0 W floor instead of a sized one - one-directional, so charging stays blocked and no discharge is capped - and reports floor_limited with the reason it bound. It is not a trip: every stop in 11.2's table still outranks the claim, and the floor is never negative, so 9.1's asymmetry survives as a property of the object (0 negative floors over 1296 swept combinations, SoC included). The SoC is graded only after `wanted > 0` is established, so it is never evaluated where it governs nothing. An unreadable SoC is floor-limited, not a full battery - a full battery is exactly the value that would disarm the floor, and this project shipped that defaulting once already. Failing to shave is not silent: one notification per episode (goodwe_peak_soc_floor), distinct from the saturation alarm because the two ask for opposite operator actions, plus its own status row and an action-log line. Verified by replay. The 2026-08-20 capture is driven against a modelled pack sized from the day's own measured appetite, so it genuinely exhausts: without the floor it reaches the BMS cut-out and holds there for 1227 guard cycles; with it the pack stops at 20.0 % and never touches the BMS. The energy withheld equals the energy between the two floors to within one cycle at the rail. The honest half is reported too - the worst quarter goes 4338 W -> 5030 W, because a floor-limited guard shaves less on purpose. Two new options, mirrored once in peakguard.PEAK_OPTION_DEFAULTS (TARIFF-02's pattern), imported by validate.py and main.py rather than typed as literals and pinned to config.yaml by a check that reads the file - so CFG-03 still tracks three places. validate.py rule 8 refuses peak_soc_floor <= bms_soc_floor at startup, in CFG-01/MAINT-04's manner. maintenance_soc_floor is deliberately not reused and not renamed: it is a drain target, not a spend limit, and the rename is recorded as a decision to revisit if a third floor appears. Eleven mutations of the shipped source were run against the checks; all eleven go red and there are no survivors. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_015VXjA3LWccN1rJsk3okyPC |
||
|
|
2d570d84ce |
SAFETY-07 review: defend the three wiring mutations that survived
The reviewer's finding was correct and the shape of it matters: everything the
first cut graded was in peakguard.py, and grading the module is not the same as
grading the guard. Three one-line changes to main.py's CALL SITE left all twelve
suites green while a default install parked at 0 W in the quarter that sets the
month's bill.
B2 was the serious one. My own comment described that defect - "that entity is
optional and empty on a default install, so until now the suspension could not
fire on the site that needed it" - and nothing could regress it. A comment that
documents a fix nobody can test is the same shape as a corrected comment nobody
tests, which this project has already been caught by once.
WHAT CHANGED
The suppression conjunction moved out of main.py and into
peakguard.shaping_suspended(), for the reason watchdog.loop_is_following() and
freeze.looks_frozen() live where they do: the check that grades a safety
predicate must assert on THE SHIPPED EXPRESSION, not on a transcription that can
drift apart from it in silence. Its docstring carries both terms and why neither
is sufficient alone. main.py's call site now says READ THAT FUNCTION FIRST, and
records that a reviewer mutated it back to its historical broken form with every
suite staying green.
test_peakguard.py part 7 gains a section that EXECUTES the three mutations
rather than describing them. Each one is put in place on the shipped module and
the REAL Controller.cycle() is driven with it, on the dangerous fixture: a
default install (no peak_forecast_entity, so peak_fc is None and peak_at_risk is
False forever) with maintenance in its CHARGE phase, so a P_MAINT_SHAPE `hi <= 0`
limit is live, and the guard genuinely engaged on the measurement. That the
mutations are monkeypatched onto the shipped module is itself load-bearing: if
main.py inlined either expression again the patch would do nothing and these
checks would pass vacuously.
SHIPPED suspended=True loop -> 1498 W, limited by peak +1497.8 W
B1 suspended=False CONTRADICTION between limits 0.0 W
B2 suspended=False CONTRADICTION between limits 0.0 W
B2b (forecast term dropped instead) - caught by its own check
B3 is graded three ways, because the single-cycle form is only INFLATED and the
failure is what happens on the next cycle:
* the value main.py actually hands decide() is recorded off the real call, with
the measured battery at 0 W and the command standing at +3000 W;
* the one-cycle difference is asserted to be exactly the standing command - the
whole defect in one line, watts that were asked for and never arrived counted
as if they had;
* both forms are then run forward against the REAL controller's own projection
with an inverter that never follows:
intent-sized floor 4482 5000 5000 5000 ... SATURATED at cycle 2
delivered-power floor 1482 1482 1482 1482 ... stationary
* and the call site is graded on parsed syntax, so a rename cannot quietly
reintroduce it: `decide(batt_w=...)` must unparse to `self.batt`.
SAFETY-24 is now named in peakguard.py, in its own section, with the number that
makes it real - 878 Wh of forced discharge on the 2026-08-20 replay - and the
statement that this must not go to a client install before that ticket lands. A
ticket nobody can find from the code is a ticket nobody reads before shipping.
RED AND GREEN
Fifteen mutations run against the shipped modules, each reverted after: the six
new wiring ones (B1, B2, B2b, B3, B3b, and deleting the SAFETY-24 pointer) and
the eight from the first round, re-run to confirm they still bite. All fifteen
turn test_peakguard.py red. Full suite green, test_price.py and TARIFF-03's
included.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_015VXjA3LWccN1rJsk3okyPC
|
||
|
|
616b62d3e9 |
SAFETY-07: cap the loop before it sets the month's billed capacity peak
checks / unit (pull_request) Successful in 3m7s
TARIFF-01 measured the quarter and said the consumer would be this card. It is
one new module, app/peakguard.py, and one new claim.
THE MECHANISM. Every cycle the guard projects the open 900 s block to its
end-of-interval average - from P1 telegrams only, never from the command - and
compares it to a ceiling. Over the ceiling it files ONE arbiter claim: a lower
bound on the setpoint at P_PEAK. That single shape is both behaviours 10.1 asks
for, a hard clamp on charging and pre-emptive discharge, and it cannot cap
discharge or export, because a floor cannot. 9.1's asymmetry becomes a property
of the object instead of a rule to remember.
excess = 900 x (projected - ceiling) / seconds remaining
floor = MEASURED battery power + excess
The 900/remaining gain is 1.0 at the top of the quarter and grows, so the guard
is gentlest where its projection rests on the least evidence. The floor is sized
from delivered battery power, not the standing command: a floor built on intent
re-adds its own unmet ask every cycle and winds to the rail whenever the inverter
fails to follow, and test_peakguard.py part 1 shows the two diverging.
IT TRIPS, AND THE CAPTURES DECIDED THAT. On the healthy reference day it engages
on zero of 95 quarters. The action is level-triggered, unlatched and re-derived
every cycle, so a false engagement costs one cycle of discharge rather than a
parked battery - the cost SAFETY-18 could not bound and this one can. Replayed on
2026-08-20 the billed quarter goes from 5029.8 W, above the inverter's own 5000 W
rating, to 3485 W, under the soft limit and without saturating. Quarters under
the limit across both committed days: 189/190 -> 190/190. Two days is not thirty
and AC 3 remains TARIFF-01's open item.
BLINDNESS IS CHECKED BEFORE THE PROJECTION IS GRADED, and it is a different
action. A fresh averager projects a confident 0 W, which is under every ceiling
there is; a meter gap longer than meter_max_age_s makes the projection read LOW;
a frozen meter reading export projects 0 W at full coverage. All three become a
floor of 0 W - no importing while the billed quantity is unobservable - which is
one-directional and cannot cost pack energy. That is the backstop SAFETY-18 could
not be: its alarm arrives at 300 s of a 900 s quarter and commands nothing. The
frozen term is freeze.looks_frozen() itself, on this cycle's standing command.
THE CEILING IS peak_cap_w, RAISED ONLY BY AN OBSERVED READING. NO_RECORD and
NOT_OBSERVED both leave it at the cap, so an unreadable peak store makes the
guard stricter and never looser. The gate is the reading's STATE, not whether a
number happens to be attached: today a `peak_w is not None` test behaves
identically, and depending on that coincidence is how a future last-known-peak
field would raise the ceiling off a read that failed. headroom_w() is
deliberately not consumed - cap minus peak turns a zero peak into FULL freedom.
TWO DEFECTS FOUND BUILDING IT, both in the interaction rather than the
arithmetic, and both caught by running the thing rather than by reading it:
* A LIMIT does not out-vote another LIMIT. arbiter.resolve() applies every
limit at or above the winner's priority and takes the most restrictive, so
the peak floor (lo >= 0) and the maintenance charge-only shaping (hi <= 0)
resolved to a CONTRADICTION and 0 W - the battery parked in the exact quarter
it should shave. Fixed by suppression, not priority: main.py drops the
maintenance shaping while the guard is engaged, which is what that branch
already did for the optional peak_forecast_entity - a key empty on a default
install, so until now the suspension could not fire on the site that needed
it.
* Thresholding `excess > 0` released the claim the instant it began working,
producing seventeen engage/release cycles in one 900 s quarter and leaving
that quarter 49 W over the limit it had spent fifteen minutes holding. That
is 10.2's oscillation. The threshold is now the floor itself, which is the
same arithmetic read as a level rather than as a switch.
PeakTracker.project() no longer reads a private name with a default.
getattr(averager, "_last_net", 0.0) failed quiet AND disarming - a rename credits
0 W held, the projection reads low, the money guard does not engage.
QuarterAverager.held_net_w is a documented public property now, read without a
default, and Projection carries it. TEST-13 item 4.
NO NEW OPTION AND NO FOURTH DEFAULTS SITE. The ceiling is peak_cap_w, the
coverage threshold is meter_max_age_s, the freeze predicate is meter_freeze_s,
and the achievable discharge comes from max_w and the device rating. config.yaml
and validate.py are untouched; 14's capacity_peak_limit_kw stays declined. On
meter_source: off there are no telegrams, so the guard does not run at all and
the status page says NOT COVERED - running it there blinded it permanently and
stopped every legacy install from charging, which is what the first cut did until
test_clamp.py's export case caught it.
test_peakguard.py: eight parts, all figures derived from the shipped config.yaml
and the committed captures. Part 8 runs seven one-line defeats of the guard and
reports which check bites; six do, and the seventh is reported as NOT caught,
because max(cap, peak) makes a zero peak the strictest ceiling there is and there
is nothing left to catch.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_015VXjA3LWccN1rJsk3okyPC
|