The loop was in velocity form: the accumulator WAS the commanded power, so
"clamp the integrator" and "clamp the output" were the same line of code and
could not be set apart. This makes the accumulator an explicit carried value
(`i_w`), bounds it with its own `integrator_max_w`, and keeps the output clamp
where it was. Killing either mechanism now still leaves the other holding -
which is the point of the ticket, and what the new regression test asserts.
Freeze semantics: while saturated the integrator may unwind but not wind
further. A strict freeze would strand the command at whatever it reached,
because the condition that releases it is the inverter tracking again, and not
tracking is exactly what saturation means.
The integrator is re-seeded from the arbiter's actual output whenever the loop
did not get what it asked for, so entering any failsafe (all of which resolve
to 0 W) zeroes it, and the first cycle after release does not dump the stale
period as power.
test_control.py: 24 -> 33 checks, all passing.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
The deadband is a one-way ratchet: any resting point inside it holds
indefinitely. Import and export are separate registers on the meter, so a
loop resting at +14 W bills 0.34 kWh/day while behaving perfectly.
target_grid_w (default -10 W) moves that residue onto the export register.
Worst billed rest point drops from 15 W to under 5 W. Behaviour is unchanged
at target_grid_w: 0.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Turns the reference RS485 controller into something a technician can install
at a client site: a typed config form instead of YAML, an ingress UI that
names misconfiguration in words, and persistent state that cannot be broken by
a timezone.
Why an add-on rather than YAML packages or blueprints:
- Blueprints cannot create helpers, and the maintenance cycle is a state
machine whose phase and completion date must survive restarts.
- YAML packages need filesystem access, a configuration.yaml edit and a
restart - none of which belong in a client install.
- Add-ons authenticate with SUPERVISOR_TOKEN, so there is no long-lived token
to generate, store or leak on someone else's machine.
- Requires HA OS/Supervised. Container and Core installs cannot run add-ons at
all, which is a market decision, not an oversight.
The control law and the maintenance machine are pure functions with no Home
Assistant imports, and both ship with runnable checks (22 and 22 assertions).
Every assertion corresponds to a rule whose absence caused an observed failure
on hardware - the saturation duration term, the clamp-before-slew ordering, the
deadband, the sign convention.
One behaviour deliberately differs from the implementation it replaces: when
its inputs go missing this commands 0 W rather than replaying the last
setpoint. The reference version kept replaying, which the hardware watchdog
cannot catch - from the ESP32's side, Home Assistant is still talking to it.
Includes the ESPHome firmware (now parameterised: node name, inverter rating,
watchdog timeout) and the optional RS485 e-stop. FIELD-GUIDE.md carries the
commissioning gates, all judged on the wire rather than on how Home Assistant
looks, plus the written statement a site without an e-stop needs signed.