F1: every password option is shown as ******** (set) or empty in /config/model
(options, running, ui) and in a stale refusal; the classic page draws it as a
password field; a save or validate that sends ******** or nothing keeps the
stored value. F2: a static_profile beside price_service is said once at start
(notification and log), not refused. F3 (owner, 2026-10-14): the no-price row,
Home line and notification only while maintenance_enabled is on. F4: tests for
the reviewer's R01 and R10. F5: price_service_token must be 16+ characters.
Co-Authored-By: Claude <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Bdqr7PiaHcBnzPituu2yTC
- DOCS: the migration note said markup and taxes do not matter; with the
provider they are added to the wholesale price. Step 4 and 5 now say what
they set and what static_profile does while no source has a price.
- The gap tests run the notification through cycle(), where the check is
called, so a check that is never called goes red.
- test header: the real-transport checks are section 11.
Co-Authored-By: Claude <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Bdqr7PiaHcBnzPituu2yTC
A new price source, `price_provider: price_service`: the owner's price server,
one fixed HTTPS host, a bearer token (new password option
`price_service_token`), wholesale energy only so markup and taxes are added as
for generic_dayahead.
The chain is server, then energy-charts, then the prices the history store
kept. A step counts only if it has a price for now. Each step down and back up
is one log line. With every source down a site plans from what it saved.
No price for now: one status row, one Home plan line and one notification, in
English and Dutch, cleared when a price returns. With this provider the
maintenance charge gate reads the provider's prices and keeps the Home
Assistant rule: the current 15-minute price is at or below today's average.
The token is hidden on the settings page, refused when missing, and taken out
of any error text. Other providers, `off` and the Home Assistant pair take the
road they always took (scripted-day probe against 0ce7d35: one line differs,
the refusal that lists the known providers). See
DECISIONS/PRICE-01-own-price-server.md.
Co-Authored-By: Claude <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Bdqr7PiaHcBnzPituu2yTC
maint_start and maint_abort take an optional unit. With two or more batteries
each Batteries card has Start cycle and Stop cycle buttons. One slot per site
stays: a start while a battery cycles is refused and names it (no queue). A
battery that is switched off, an unknown unit, and a stop on a battery that is
not cycling are refused with a plain message. A request with no unit is the
old call. The scheduler and the phase machine are unchanged.
Co-Authored-By: Claude <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Bdqr7PiaHcBnzPituu2yTC
Conflicts (5 files, 9 hunks) resolved keeping both sides:
- p1.py: held_t (OPT-15) beside held_since (SAFETY-90).
- modetrade.py: chargers() takes targets (P4) and probe (OPT-15); decide()
clears the chargers, a probing refuser included, while a battery drains
(SAFETY-78); the docstring lists both rules.
- main.py: the roll goes into the SAFETY-90/91 projection chain
(`_peak_proj`); the SAFETY-95 drain-tail grid_w keeps the run-edge hold on
its other branch; the P4 forecast state and the hold state both stay.
- DOCS.md, DECISIONS: both lines kept, OPT-15 item refreshed.
Adaptations the merge needs:
- SAFETY-81 x F1: a rolled projection is not graded by the saturation alarm
until the quarter's first sample, as the old edge tick was not, so a
standing overload is still notified once per quarter.
- test_safety81, test_modes_p4: modes-on pins re-pinned (with a note), modes
off pinned to e3e4ba6; test_price_run_fixes: identity pins on e3e4ba6,
F1 reproduced at one inverter (SAFETY-91 already holds two), tests for the
drain and the day plan against the probe.
Co-Authored-By: Claude <noreply@anthropic.com>
The Supervisor proxy answers 502 to every add-on read, write and websocket
until Core is RUNNING (proxy.py api()/websocket() -> check_api_state()), so
the add-on cannot control while a slow integration holds HA's start, even
with its entities live. Measured on a safety112 repro stack with the
2026.08.0 proxy code: first write 1.0-4.4 s after RUNNING, 238-300 s after
live readings. Not routed around (DECISIONS/SAFETY-112-...).
While the API does not answer, the first status row is red and is the
banner ("Waiting for Home Assistant to finish starting"), Home shows a
"waiting" state in EN/NL instead of "Needs you now", and the log adds a
"still waiting" line every 5 minutes and the wait's length at the end.
A safety stop, a stalled loop or shadow mode keeps its own headline.
Control, writes, heartbeat and the stand-down are unchanged.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
New list options pv_forecast_entities and pv_forecast_tomorrow_entities
(same shape as pv_entities); the single-entity keys are unchanged.
- Each member is read in its own unit (Wh/kWh/MWh) in one gather and the
day is summed. Hourly splits are merged when every member has one, else
the total goes on the bell.
- A member missing, unavailable, stale, non-energy or bad makes that
day's forecast unusable (no partial sum). A caution row names it by
position; the action log names the entity once per change.
- Single key and list both set for one day: refused at start.
- A one-member list behaves exactly like the single key (test_opt17.py);
the single-key path is byte-identical to e36565f over 24 scenarios.
- Supervisor shape measured: tools/supervisor_shape_probe.py section J.
DECISIONS/OPT-17-several-forecast-entities.md has the rules.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Bdqr7PiaHcBnzPituu2yTC
At one inverter SAFETY-52's "another writer" end tested target != loop_w.
A held refusal makes the loop ask 0 W, so any binding claim (maintenance
charge, peak guard, trade) ended it every cycle, and compute() learned it
again in the same cycle: "BATTERY REFUSES" / "ENDED: another writer" each
second on the rig. Now the held refusal is judged afresh against the
writer's ask (compute() gets the same inputs as before); it ends only if
compute() no longer finds it. Commands unchanged: 300-seed differential
trace against release/1.0, N=1 and N=2, every command and refusal state
identical. DECISIONS/SAFETY-107.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Bdqr7PiaHcBnzPituu2yTC
A charge is complete at SoC >= target, or at >= target - 3 once the SoC has
made no new high for 60 min of allowed charging, or when the charging time
runs out at >= target - 3. The 36 h timeout counts only the minutes the price
gate let the pack charge (plus a 7 day wall-clock backstop). A cycle that
fails (stuck drain, charge below target - 3) backs off 7 days, tells the
operator once (EN + NL), and no cycle starts on that pack in that time unless
the operator forces one. State survives a restart; old state files load.
No option added. DECISIONS/MAINT-13-full-pack-is-complete.md.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
While a battery settles from its ended drain (SAFETY-95), the house point
was grid + every battery's reading. A register can be 10 s older than the
meter, so B swung 860 -> 1650 -> 870 W on A's old reading (rig check 5).
Now the house point is held and moved only as far as the meter proves:
each battery is between its last changed reading and its commands since
(a reading that changed this cycle, or a refused side, as it reads).
N=1 and 1 s registers are byte-identical to release/1.0.
DECISIONS/SAFETY-103-old-readings-after-a-drain.md, test_safety103.py.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
test_safety95.py: the N=1 byte-identity now covers all six drain ends
(Off and stale link were missing); end_at()/measure() read through a
default, so test_named_absence.py passes (it failed on bdec66e); a check
that a dropped battery's start is 0 W even under a pinned charge (it
kills a mutation that survived).
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
When a battery's drain ended (done, Off, timeout, abort, stale link,
refusal), its drain floor stayed in the site target and landed on the
others: B 0 -> +1600 W in one cycle at a 1200 W house, exporting; under a
solar surplus B gave into the export.
Now, on that cycle, the loop starts from what the others stood at plus the
battery's new command, raised to the house's own point when the house needs
more (never above last cycle's start). While the battery settles, the loop
counts the batteries at its start instead of chasing the drain's tail on
the meter. Then one slew step a cycle. N=1 is unchanged.
test_safety95.py; DECISIONS/SAFETY-95-drain-end.md; one DOCS line.
test_modes.py: opt11 n2_maint re-pinned on purpose (its drain ends by a
refusal at 1655 s; B now stays at the house's 1420 W instead of 2500 W).
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
At N>=2 a battery out of the split (stale link), with refused writes, or
settling after a step the loop did not make (a charge end, a rejoin) now
counts in the freeze test at its command, not its reading. Its real power
still reaches the loop through the meter. At a drop its share leaves the
loop's start point (the others take over one slew step a cycle); at a
rejoin it enters at its reading. No refusal is learned while a battery's
writes are refused. N=1 and the 46 identity digests are byte-identical.
test_safety78 part 2: the dropped-drain case now rests at B 1510 W (grid at
its -10 W aim) instead of 1500 W; the drop no longer sends B to 2500 W.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
HA can take minutes to start (2026-10-05, 502 from the proxy). Then TZ holds,
which the Supervisor sets from HA's zone, so the hour stays right; only a TZ
of UTC there now logs a WARNING asking for a restart. A test pins the 3 s
budget on the zone request (a mutant without it survived).
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
test_maint10.py part 10: at two inverters both packs get the site zone, the
real Controller is identical for 11 UTC and 13 Brussels, and two due packs
across 24/25 Oct 2026 and 27/28 Mar 2027 start at the local hour on
successive days; a pack freed in the repeated hour does not start there.
Part 3 adds 28 Mar 2027. DOCS: an existing install keeps its saved hour, now
read as local time; an hour set to make up for UTC goes back to 19.
DECISIONS: the SAFETY-83 gate is met; section on two inverters.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
While the add-on is down the batteries are at 0 W (it sets 0 W when it
stops; the ESP32 watchdog after 30 s), so the import before its first
reading was the house, not the aim. Those seconds now count at
gap_w(limit, the import seen first), and after a restart the restored
reading's held 30 s is topped up the same way. Status row: "counted as
high use". Tests take the pre-start import as the house (batteries at
0 W) and add restarts of 10/60/150 s with a restored averager.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
A meter gap past meter_max_age_s left seconds the quarter average never
counted, so the guard was blind for the rest of the quarter (rig case 7b:
3964.8 W against a 3450 W aim). Once readings are back, the missed seconds
now count at the higher of the limit and the import seen just before and
just after the gap with the batteries at 0 W (peakguard.gap_w/fill_gaps);
the gap's first meter_max_age_s is topped up to that too. Seconds before
the add-on's first reading count at the aim, and the page says part of the
period was not measured (EN/NL). The bill record is unchanged; no option.
DECISIONS/SAFETY-90-peak-guard-after-a-gap.md, test_safety90.py.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
B's power reading shows -95 to -118 W at idle (standby draw), so the
|reading| < 100 W refusal band never held a refusing B: never at N=2,
and since SAFETY-94's shared rule not at N=1 either (review F1).
Each unit now learns its idle reading (app/idle.py): only while control
runs, the unit is not refused/stale/tripped and its command has stayed
within 50 W for 120 s; first value a 120 s mean, then a 30 min follow;
samples beyond 250 W dropped, value clamped to 250 W; saved per unit and
restored. The shared refusal evidence, compute()'s N=1 engage and end,
the unit refusal ends, the stale-path refusal and SAFETY-42's "parked"
test are centred on it. Until learned it is 0 W, the rule as it was.
Refusing B caught at N=1 28/28/65 s and N=2 24/24/60 s (1/2/5 s
meters), before never; refusing A unchanged. Healthy B with its offset,
SAFETY-94's scenarios, 96 runs: 0 stale, 0 refused. Live replay: 0.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_019DBUfvndgHwaV339Fvd2gr
The stale-reading gate counted its 35 s from the register's last change, so
after a rest the first read after a new command tripped it (SAFETY-58; live
2026-10-03, four trips 1 s after the command). It now counts only the time
the command asked the register to move.
At N=1 the refusal engaged after 12 frozen cycles if the reading was under
100 W at that moment, which a battery reversing through its lag passes at a
1 s meter. The refusal now needs the N>1 evidence at every roster size: under
100 W, one way, for 12 cycles spanning 22 s, restarting when the reading
moves 50 W towards the ask.
DECISIONS/SAFETY-94-lagging-battery.md; test_safety94.py.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
At N>=2, when a battery's maintenance charge ended, its watts stayed in the
loop's start point and landed on the other battery (B 0 -> -1600 W in one
cycle, charging from the grid at a 6000 W house). On the cycle a charge
ends, the loop now starts from what the others stood at plus that
battery's new command. N=1 and all identity digests unchanged.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
At N>=2 a battery at or under its own peak reserve now weighs 0 whenever
the site gives (not only for the peak), a draining battery's pin becomes
a floor at its drain rate so it rises before the held one gives, and a
quarter's edge is graded on the next quarter when its first telegram is
late. SAFETY-25 option A stays: the held battery is still drawn once the
others are full. N=1 unchanged.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Rule 2 graded each battery against last cycle's command and graded charges
too. On plantsim's battery (10 s lag) at the 2 s meter it warned at every
drain or charge start and 15 times an hour under the peak guard at N=2; a
charge tapering near full warned 11 times in 50 min (SAFETY-42 section 7).
Now a discharge is graded against the least it stood at over SHORT_CYCLES /
SHORT_SPAN_S. DOCS lists `mode-bound` under Loop reason. test_safety85 part 7:
peak guard with a dead battery, lagging plant, taper; part 3: the bound ends
with maintenance.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
The loop's integrator bound counts only on a cycle the loop decided. A battery
another owner set (maintenance, the peak guard, a safety limit) alarms only
when it gives more than saturation_w less than told for saturation_cycles
cycles. At N>=2 the loop is bounded while maintenance holds a battery, so it
does not wind and control comes back one slew step a cycle. The status row
counts episodes, not cycles. Digests re-pinned where behaviour changed on
purpose; DECISIONS/SAFETY-85-no-false-not-keeping-up.md has the list.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_019DBUfvndgHwaV339Fvd2gr
At N>=2 a battery at or under its own peak reserve is held: it gives
nothing for the peak (weight 0 while the site gives) and the guard's need
is placed on the live, non-refusing batteries above theirs. The guard is
floor-limited, and alarms, only when those cannot hold the limit at full
power for ALARM_HOLD_S. The peak alarms no longer read "Not ready" or hold
the Home page at 0 W, because control keeps running. N=1 is byte-identical.
DECISIONS/SAFETY-87-guard-uses-able-batteries.md.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_019DBUfvndgHwaV339Fvd2gr
During a HOLD the holding battery gives what keeps the quarter at the peak
aim. N=1: the peak floor is refiled at P_MAINTENANCE, as for a drain
(SAFETY-83). N>=2: the hold's pin is raised to the floor minus what the
other live batteries may place, so they give first. A site stop still
decides alone. The hold ends on its clock even if the level dipped.
Below the aim nothing changes (rows identical).
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
At N>=2 a cheap-window maintenance charge files a site `hi` (`charge`,
P_MAINT_SHAPE) equal to what the charging pack's own `hi` places, so the
other pack never has to give against it. The charge is sized to the
quarter's headroom under the peak aim so it yields to the peak guard, and
to 0 W under a site safety stop. N=1 byte-identical (safety84_identity).
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
The start hour was compared with the UTC hour, so the shipped 10 started at
12:00 in a Belgian summer. It is now read in Home Assistant's time zone
(fallback: the container's TZ, then UTC, one log line says which), and the
default moves to 19. DST: a missing hour starts at the first hour after the
jump; a repeated hour starts only in its first pass. Stored options are not
rewritten: a saved 10 now means 10:00 local (DOCS, CHANGELOG).
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
At N=1 the drain is the site SET at P_MAINTENANCE (60), so the peak floor
(P_PEAK, 50) was not applied and the house imported what the drain left.
Where the floor asks for more than the drain rate, main.py now refiles the
peak claim at P_MAINTENANCE, so it wins; safety SETs still park everything.
Nothing else changes: safety78_identity --diff against 35cdffe changes only
cycles where the guard wanted more than the drain; N=2 is byte-identical.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Conflicts: modetrade.decide() takes both the day plan (targets) and
SAFETY-78's draining flag; the Why line keeps SAFETY-78's other_cycle
ahead of the plan's word (test added).
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
- DECISIONS: the Cheap hours change and why; the no-sun replay (the gain is
Leftover solar buying the evening's shortfall; the forecast added 0.14
EUR); the reconstruction bias stated plainly.
- DOCS: Cheap hours ignores the forecast; a reading from before midnight
is stale.
- The forecast line: "Solar still to come today: ..." (it is what is
left, and it stays within the 12-word limit).
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
- Cheap hours only fills to the ceiling with or without a forecast, as the
design (section 1) says. Skipping the sun's share cost 0.31 EUR on real
2026 prices (29.72 against P3's 29.41) and saved nothing on the P3 set.
- A forecast reading from before local midnight is stale: until the
integration refreshes, "left today" is still yesterday's 0 and
"tomorrow" is really today.
- Forecast entity ids must be sensor.[a-z0-9_]+ (they go into the
/api/states/<id> path).
- House profile: a stored day that is not a date, or is after today, is
dropped instead of kept forever.
- Text: the forecast line says "for the rest of today"; the learning line
no longer promises "tomorrow" (a plan needs one full day).
- Tests for four surviving review mutants (hour sample floor, the dear run
after the cheap run, share by room, daytime use) and the fixes above.
- Replay tool: `--fc zero` (a forecast of no sun).
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
- The alarm must hold for peakguard.ALARM_HOLD_S (10 s) on the projection's
clock. A load that tops cap + battery for ~5 s every 30 s alarmed at every
quarter start while the quarter landed under the aim (sine4500_fast).
- A cycle with no battery reading leaves the hold alone.
- Notified once per quarter, but the ERROR line is written per episode.
- New sim scenarios (sine4500_fast, twice7000, step6500_gap) with 5a4cdc2
digests; control still byte-identical. Unit checks for export and the
hold across a missing reading. test_peakguard's saturated fixture moves
the hold start back instead of waiting it out.
- DECISIONS and DOCS updated: costs of the hold, tolerance reasoning, the
double count in control left to a follow-up.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
F1: with battery modes on, the peak guard projects the quarter `now` is in
even before its first P1 sample (PeakTracker.project(roll=True)), and only
a measured stop latches the period. The edge tick no longer reads "no
seconds left", so a charge is not stopped and latched at a quarter edge.
F2: after a run edge the loop is held at E until the meter shows the step
(EDGE_HOLD_S, longer while the battery still moves). The replay gained a
lag model (dead time, reading age, P1 debounce, 1 s cycles) that shows
TEST-23's overshoot without the hold.
F3: a charge refuser's SAFETY-73 probe inside a cheap run is a charger
pinned at PROBE_W, the others rest, so the probe actually runs.
Modes off stays byte-identical to 5a4cdc2 (new late-P1 identity scenarios).
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
The alarm now also needs peakguard.load_too_high(): with the battery at
full power, the quarter still ends more than 10 W over the real limit.
The battery reading is the lower of this cycle's and the last, so a meter
sample from before the battery's last increase is not counted twice.
At most one alarm per quarter. Control outputs unchanged.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
At two inverters the drain pins its pack and the site target is split
around the pin. Below the pin the other pack had to charge, the allocator
refused the opposite directions, and the site sat at 0 W with an ARBITER
line every cycle (house below or above the drain rate, or a grid charge).
main.py now files a site limit `drain` (lo = what the pin places, at
P_MAINTENANCE) at N>=2 while a pack drains, so the other pack only adds
power in the same direction. A drain that cannot give power waits with
one log line. With battery modes on, no grid charge while a pack drains,
and the other battery's card says why. N=1 is byte-identical.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
A Home Assistant solar forecast (Forecast.Solar, Solcast or Open-Meteo
shapes) and the add-on's own hourly house use decide, before each cheap
run, whether the sun will fill each battery before the expensive hours.
Leftover solar then buys from the grid only the shortfall; Cheap hours only
skips the part the sun covers; Solar first never grid-charges. No, stale or
failed forecast: P3 option A exactly (12 digests pinned from 5a4cdc2).
Replay (16 recorded days, forecast errors from Elia's day-ahead BE solar):
year-earlier prices P4 19.15 vs P2 19.33 / option A 19.44 / old trade 18.14;
real 2026 prices P4 29.19 vs 32.26 / 32.01 / 31.40 EUR net.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Owner decision 2026-09-29. Selling is off until it can be judged on the price
the grid pays: packmode.SELLING_ENABLED = False makes read() answer
sell=False whatever the store holds, pack_sell is refused ("Selling is off
for now."), and the page has no selling switch; the sell code stays. Until
the P4 forecast, only Cheap hours only charges from the grid
(packmode.GRID_CHARGE_MODES); Leftover solar holds and gives in the
expensive runs. Help, Today and plan lines, DOCS and DECISIONS follow.
Replay, 16 days: Solar first + Leftover solar 19.44 EUR net (P2 19.33).
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
- A sale block on the plan no longer says "Worth up to" at the import
price: a sale earns the lower injection price.
- The selling switch help (EN/NL) and DOCS say the grid pays less than
power costs; DECISIONS records why P3 loses on the replay.
- test_modes_p3 part 11: modes on ignore the site trade switch (R13), a
battery in maintenance takes no part (R10), a headroom stop latches for
the period (R8). All three mutants survived before and are red now.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Cheap and expensive hours as runs of consecutive firm price slots
(priceruns.py); each battery's role per tick from its mode (modetrade.py):
grid charging for Leftover solar / Cheap hours only, never Solar first;
holding for the expensive runs; selling per battery (pack_sell) above the
spread and the floor. The site trade is sized inside the modes (loop bound)
and the peak guard's headroom; a run edge reseeds the loop. Cheap hours only
and selling are enabled on the Batteries screen and in the HA select
(appended). The site Why row no longer says "held back" when the peak limit
pushes power up (F2). Modes off: byte-identical to 7a00f12 on the trade path.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
- quarter_target_w() is now the margin under quarter_ceiling_w(): a peak
banked between cap - margin and the cap was aimed at exactly, so one
overshoot crossed the cap; above the cap the same overshoot raised the bill.
- safety79_identity.py hashes charge_headroom_w() and the shaping suspension,
and adds n1_maint/n2_maint (cheap window, forecast across cap - 50 .. cap).
Digests re-printed on ed739d4 and pinned; margin 0 still identical.
- test_margin_under_banked_peak; DECISIONS and DOCS updated.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
- A refusal past the log-once set or the 32 cap is counted in the log at
1, 10, 100 and so on, so a repeated attack stays visible.
- The logged topic is printable only (no forged log lines).
- mode_announcement(): the start-up store logic, now tested with a real
Store. A removed config topic stays stored, so a start with no broker
cannot forget it (rename case tested).
- A test ties each HA mode option to the page's English name.
- packmode.enabled() is tested for "true", 1 and "false".
- Retained-command text, DOCS and DECISIONS updated to match.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>