Solar as a second writer next to Manual (carmode.SolarPlan, SolarWriter on
ManualWriter's one write site, safe phase sequence and other-writer watch):
signed spare, Batteries first on the batteries' ratings, the margin, whole
amps rounded down, the 30 s / 1 A rule, start and pause dwells, auto phases,
a one-phase car. Every way out ends at 0 A, retried by EV-04's rule; at
shutdown before the inverters, three tries inside 15 s (D3); start-up and a
returning charger or HA write 0 A first (D2); never over another writer's
hold. The peak guard treats a Solar car as a Manual car (D1 wording). Solar
kWh sensor and card line; select.goodwe_car_sun_first; ev_margin_w,
ev_start_min, ev_pause_min with config, validator, translations, DOCS,
DECISIONS and CHANGELOG.
Checks: test_ev20.py, test_ev20_exits.py, test_ev20_writers.py,
test_ev20_guard.py, test_ev20_long.py, test_ev20_long_car.py,
test_ev20_fuzz.py (harness tools/ev20_sun.py, ev20_kit.py, ev20_day.py);
test_ev03/test_ev04 no longer use Solar as the refused example.
Co-Authored-By: Claude <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01VSY9UpTaUYnjJF5oVtbM1w
Stage zero counted mode3 B as quiet whatever the power and selected at the
20 s timeout under load. A power reading now decides (under 100 W); mode3
(not C, not D) only without one. Still drawing at 20 s: no select, the
current comes back at once, one failed try, next try PHASE_GAP_S later.
Co-Authored-By: Claude <noreply@anthropic.com>
N1 the undo gives the old current back (clamped) in shadow mode; DECISIONS records it as the one write shadow mode allows.
N2 the corroboration looks back to a stretch with at least 40 Wh expected (60 s at 2.4 kW and up, 104 s at 1.38 kW).
L4 the current comes back 10 s after the phase select returned, also when it was refused.
Co-Authored-By: Claude <noreply@anthropic.com>
M1 the writer ignores a reading taken before its latest confirmed write.
M2 a refused phase select gives the current back and stops after 3 tries (amber row).
M3 Off, shadow mode or a control/safety stop before the select undoes the change.
M4 the restore on shutdown (and the undo) is clamped.
M5 the car's power reaches the alarm path only while the charger's energy meter agrees with it.
L1 fuzz other-writer branch reachable and shown to run. L2 one wording. L3 Batteries-help-off text.
Co-Authored-By: Claude <noreply@anthropic.com>
Off and Manual (runtime state, Home and Home Assistant): the current (6 A to
the clamp) and the phases (1 or 3) are written once per user change through
the safe phase sequence, read back within 10 s, clamped to
min(ev_max_a, station limit, entity range). Shadow mode gates the writes.
The car's fresh power goes to the peak guard's alarm path: no false "Load too
high" or "Battery stopped limiting the peak", one grey notice per session.
ev_batt_cover and ev_mode_start options, peak line "set by the car", HA
entities, sim writes, DOCS, CHANGELOG, test_ev04.py.
Co-Authored-By: Claude <noreply@anthropic.com>