AC3 says "verified on the rig". The previous commit drove hwsim in-process
because `riglock status` reported UNKNOWN - which is the tool declining to
observe, not an observation. riglock shells out to the local docker CLI; on a
Windows host without DOCKER_HOST that resolves to a Docker Desktop npipe which
is not running, and the result is indistinguishable from a genuinely absent rig.
The rig was up the whole time. With DOCKER_HOST=ssh://homelab@192.168.2.147 it
reads FREE.
Re-run under sim/riglock.py against the real goodwe-sim compose project, with
the shipped modules staged into goodwe-sim-plant so they poll that container's
own hwsim while plantsim drives it. Both phases passed, lock released cleanly.
The rig produced a result the in-process stub could not, and it strengthens the
design rather than merely confirming it: in the NEGATIVE twin - +8000 W of house
load, healthy meter, correctly railed command - `active_power_w` did not move at
all, sitting at exactly 10130.0 W for 26 consecutive polls. The only thing
keeping `unchanged_s` at 0.0 s was the kWh registers advancing.
So the register terms in measurement_fingerprint() are not belt-and-braces for
this detector, they ARE the negative case: fingerprinted on the power figure
alone it would have raised a false alarm on a healthy meter under a real load,
which is precisely how a safety guard gets switched off. Recorded in freeze.py
so nobody simplifies the fingerprint without meeting that run first.
No behaviour change - documentation and the harness note only.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_015VXjA3LWccN1rJsk3okyPC
A meter that answers 200 OK with a stale document forever is ARRIVING on every
poll, so every freshness mechanism in the stack reads it as healthy while the
loop integrates a constant error and rails: 360/135/75 s at the live install's
max_w: 5000 for a meter frozen at 350/1000/>=3000 W. Fifteen minutes of a 5 kW
unattended import sets the month's billed capaciteitstarief peak.
The detector is a conjunction, not the bare unchanged_s threshold TEL-05
measured and rejected:
unchanged_s >= meter_freeze_s AND |command| within 5 % of max_w
Both terms already existed and were already on the status page, and they fail
for independent reasons: at the converged point the command is nowhere near the
rail, and at the rail against a real load the kWh registers move in seconds. At
the shipped 300 s the relation is structural rather than a margin - the slowest
a healthy 1 Wh register can tick and still look unchanged is 12 W, which is
inside the 15 W deadband, so the command there is parked at 0 W.
Notification only, deliberately: an HA persistent notification with a fixed
notification_id, an ERROR log line, a UI event and a red status row. No claim,
no latch, no 0 W. A false trip parks the battery; a false notification costs an
alert. Only meter_source: homewizard_local is covered - the status page says
NOT COVERED elsewhere rather than pretending the guard is armed.
DOCS.md states the capacity-tariff exposure this does NOT close: peak_cap_w caps
maintenance charging and nothing caps the loop. That cap is SAFETY-07.
test_freeze.py grades both directions and was verified by breaking what it
watches (six mutations, all red): silent over the committed 40-minute converged
capture, silent over an hour of TEL-05's low-power case where the rejected bare
threshold is shown to fire, alarming on a genuinely frozen meter driven over
real HTTP through the real HomeWizardLocalSource (the rig's own hwsim freeze
fault when reachable), silent on the same railed command against a meter that is
still moving, and asserting on the service call that leaves Controller.cycle()
rather than on the watchdog's own flag.