glenn schrooyenandClaude Opus 5 0a617c5482 TEL-01 review fixes: stop the age sensor tripping installs that have no meter
T-1, and it was a fleet-wide trip to zero. publish() emitted p1_age
unconditionally, and published_age_s counts from P1Ingest.__init__ when no
sample has ever arrived. With meter_source defaulting to off, every existing
install would have published sensor.p1_sample_age_s climbing without bound; the
ESP32 does `has_state() && state >= max_age_s` and forces the layer-1 failsafe,
so each of them would have pinned its inverter at 0 W within 30 s. Exactly the
opposite of the zero-regression the off default was for. The key is now omitted
from the payload AND from MQTT discovery when P1 is off, so the entity does not
exist at all - which is the status quo, and what has_state() is testing for.
The predicate is one function, is_enabled(), because the grid reading, the task
start and the discovery announcement have to agree or this comes back.

T-2, connect no longer manufactures a sample. get_states returns whatever HA
currently holds, which after a Core restart is a RestoreEntity value of unknown
age; stamping it with ingest_ts=now reset the age and reported a fresh meter
that could have been dead for an hour. run()'s own docstring already said a
reconnect must emit nothing - the code disagreed with it, and a test asserted
the violation. The cache is still primed, so the first real state_changed
builds a complete sample; the age just stays honest until one arrives.

T-3, gaps are no longer filled with the last held value. The averager held a
sample forward across any interval, so a meter dying at 5 kW and returning ten
minutes later credited 5 kW x 600 s to the capacity-tariff accumulator - a
fabricated peak on a permanent record. The hold is capped at max_age_s: past
that the stretch is walked so block boundaries still land correctly, but
nothing accumulates and elapsed does not grow, which is what finally makes the
comment about a gap dragging the billed average down true. Same threshold for
control and billing: a reading too old to steer by is too old to bill by.

T-4, the out-of-order/duplicate guard is covered. It was untested, and the
reason is worth recording: the obvious assertion passes without the guard,
because the negative interval is separately refused by the covered > 0 test.
What the guard prevents is the timestamp REWIND, which only shows up one sample
later as a re-integrated window. The test now goes one sample later.

T-6, DOCS was wrong about latency. meter_max_age_s and stale_input_s stack, so
meter death to 0 W is 45 s and not 30. Documented as a table with both clocks.

Also documented the T-5 asymmetry rather than papering over it: the age
measures arrival, not change, so a stuck MQTT bridge republishing its last
telegram still looks fresh. Correct on ha_dsmr, not detectable on mqtt_p1
without a change-detector. Written up as a known limit.

Writing the T-1 test caught a second defect in the test itself: it recorded
only MQTT topics, and object_id lives in the payload, so "the age sensor is not
announced" had been passing for the wrong reason.

test_p1.py: 99 -> 122 checks. 14 mutations run, all 14 red, files restored
byte-identical - including one per fix above.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
2026-08-24 22:16:34 +02:00
glenn schrooyenandClaude Opus 5 2097b7aaf6 TEL-01: P1 ingestion, with the derivation and the age the EMS owns
A Belgian P1 meter publishes two UNSIGNED registers, not one signed figure.
Until now the add-on asked the installer to bridge that gap with a template
sensor, which put the sign convention of the whole control loop in a text box.
This moves it into the EMS: net = import - export, derived once, in one place,
with a test that fails if anyone inverts it.

Two transports behind one contract, chosen by `meter_source`: the HA WebSocket
subscribing to the DSMR integration's entities, and MQTT on a configurable
topic. Everything downstream reads P1Ingest, so switching is a config edit.
`meter_source: off` is the default and keeps the existing meter_entity path,
so no installed system changes until it opts in.

The other half is the timestamp. Every accepted sample is stamped at ingest
with a monotonic clock, `meter_max_age_s` is applied to it, and the age is
published as sensor.p1_sample_age_s for the ESP32's stale-input watchdog. That
entity is recomputed against the clock every second rather than only when a
telegram lands, because HA pushes state only on change: a meter frozen at a
constant reading emits nothing and looks, to anything watching the value,
exactly like a meter that has died. The age tells them apart.

Deliberately absent: any fallback to an inverter-side power figure. The
inverter's own AC power correlates 0.998 with battery power and 0.09 with the
real meter, so failing over to it means regulating against your own output.
A gap stays a gap - a reconnect emits no synthetic sample, and a rejected
telegram never resolves to 0 W or refreshes the timestamp.

Quarter-hour averages are time-weighted over clock-aligned blocks rather than
a mean of samples, so a cadence change cannot bias the capacity-tariff figure,
and only offtake is accumulated so a quarter of pure export averages to 0 kW.
Per-phase import is kept separately: on an unbalanced three-phase load the
phase sum and the connection net are different numbers, and only one of them
is billed.

test_p1.py: 99 checks, runnable with a bare interpreter and no meter. Includes
an end-to-end run of the HA transport against a fake Home Assistant websocket.

Stacked on SAFETY-04; nothing here touches control.py.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
2026-08-24 22:16:34 +02:00
adminandClaude Opus 5 594f8f9fc9 Six silent failures found by installing this on a live system
Migrated the reference site off the YAML packages and onto the add-on. Every
bug below presented identically: the add-on starts, logs "started", serves its
UI, and cannot do its job.

- run.sh needs #!/usr/bin/with-contenv sh. s6-overlay sanitises the environment
  for services, so a plain shebang means SUPERVISOR_TOKEN is absent and every
  Core API call is 401 - while homeassistant_api: true makes permissions look
  granted. Startup now prints the token length and probes the API.
- Supervisor keys the image by config.yaml `version`, so rebuilding without a
  bump reuses the old image. Two fixes appeared not to work because of it.
- Alpine is musl and has no aiohttp wheel on PyPI; deps now come from apk so
  nothing compiles on a client's Pi.
- Alpine ships paho-mqtt 1.x, which has no CallbackAPIVersion. That raised at
  construction and took the control loop down with it - so MQTT setup is now
  wrapped too. Observability must never be able to stop the controller.
- MQTT discovery is published from on_connect: paho silently drops QoS-0
  publishes issued before the CONNACK, so the previous code announced nothing
  while logging "MQTT connected".
- Repeated failures now log once a minute. Six warnings a second rolled the log
  buffer and destroyed the startup diagnostics needed to find the 401.
- auto_start could never fire, because the store's defaults always supplied
  auto: False for the fallback to find.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_016NckgXecasQb2eSsPYNSW6
2026-08-23 02:25:58 +02:00
adminandClaude Opus 5 0a1e61dbc9 Packaged as a Home Assistant add-on, with a field guide
Turns the reference RS485 controller into something a technician can install
at a client site: a typed config form instead of YAML, an ingress UI that
names misconfiguration in words, and persistent state that cannot be broken by
a timezone.

Why an add-on rather than YAML packages or blueprints:

- Blueprints cannot create helpers, and the maintenance cycle is a state
  machine whose phase and completion date must survive restarts.
- YAML packages need filesystem access, a configuration.yaml edit and a
  restart - none of which belong in a client install.
- Add-ons authenticate with SUPERVISOR_TOKEN, so there is no long-lived token
  to generate, store or leak on someone else's machine.
- Requires HA OS/Supervised. Container and Core installs cannot run add-ons at
  all, which is a market decision, not an oversight.

The control law and the maintenance machine are pure functions with no Home
Assistant imports, and both ship with runnable checks (22 and 22 assertions).
Every assertion corresponds to a rule whose absence caused an observed failure
on hardware - the saturation duration term, the clamp-before-slew ordering, the
deadband, the sign convention.

One behaviour deliberately differs from the implementation it replaces: when
its inputs go missing this commands 0 W rather than replaying the last
setpoint. The reference version kept replaying, which the hardware watchdog
cannot catch - from the ESP32's side, Home Assistant is still talking to it.

Includes the ESPHome firmware (now parameterised: node name, inverter rating,
watchdog timeout) and the optional RS485 e-stop. FIELD-GUIDE.md carries the
commissioning gates, all judged on the wire rather than on how Home Assistant
looks, plus the written statement a site without an e-stop needs signed.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_016NckgXecasQb2eSsPYNSW6
2026-08-23 01:15:25 +02:00