adminandClaude Opus 5.5 3c0f2b9669 SAFETY-52 review: a refusal is under 100 W, and any delivery ends it
checks / unit (pull_request) Successful in 9m22s
infra-pin / fresh (pull_request) Successful in 1s
- Engage (and seed from a stale stop) below REFUSED_BELOW_W, the probe's
  own 100 W answer, not below saturation_w: a battery derated to 100-499 W
  was held at 0 W ~93 % of the time.
- A reading of 100 W or more in the held direction ends the refusal, probe
  or not: at a 1 s meter SETTLE_CYCLES is 12 s, shorter than a healthy
  reading's lag, and that held a healthy step at 0 W until the next probe.
- test_refusal part 5b and a seed test; DOCS states the N>1 limit; the
  DECISIONS record carries the traced cause of the replay's extra trips.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-27 18:11:42 +02:00
glenn schrooyenandClaude Opus 5.5 1f97c7652f SAFETY-52: a battery that refuses is asked for 0 W, with a 200 W probe every 15 min
infra-pin / fresh (pull_request) Successful in 1s
checks / unit (pull_request) Failing after 9m32s
At the BMS cut-out the saturation freeze held the last request for hours
(+5000 W for 11.87 h on 09-06, +1940 W for 3 h 55 m on 09-19) until the grid
error changed sign. compute() now carries a refused direction: after
SETTLE_CYCLES of a ~0 W reading against a larger ask it holds that direction
at 0 W, probes 200 W (below the gate's 250 W) every 15 minutes, and lets go
on charge, an answered probe, stop/start or another writer. A stale-reading
trip on a frozen ~0 W reading seeds the same hold, which ends SAFETY-59's
~70 s cycle. One inverter only; no SoC in the loop (SAFETY-25 Option A).

test_refusal.py drives the real Controller and gate; tools/replay_refusal.py
replays the 16-day capture. test_clamp.py and test_delivery.py re-baselined
where they asserted the old hold. DECISIONS/SAFETY-52 has the record and what
SAFETY-58/59 must take into account.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-27 16:43:27 +02:00