SAFETY-40: the integrator bound is not a BUG SIGNAL; numbers from the clamp tick
The clamp alarm gave `i_clamped` (normal anti-windup) the over-rating BUG SIGNAL text, printed `Decision.i_w` as "the loop asked for", and printed `self.target` (after slew/freeze) as "was clamped to". - clamp.loop_clamp_note(): i_clamped says "the loop's integrator reached its N W anti-windup bound" with this tick's command; clamped keeps BUG SIGNAL with the requested command and the clamp's own result. - Decision carries i_bound_w / requested_w / clamped_w, set at the clamp. - i_clamped still counts and notifies (same id, cadence, SAFETY-41 escalation) but as a WARNING, amber row, plain title. A bug has its own notification budget and its text is not overwritten within an episode. - test_clamp.py part 9: red on the old code per defect; 5 mutations killed. - DOCS.md alarm section (and its stale 30 s cadence), DECISIONS/SAFETY-40. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01LyR88rXETvwhTgx6yHE39p
This commit is contained in:
co-authored by
Claude Opus 5.5
parent
59415ea83f
commit
fd14569a71
@@ -1630,7 +1630,9 @@ share no reason code, no notification id, no status row and no counter.
|
||||
running - this is not the sign-disagreement failsafe, which commands 0 W. You
|
||||
get a persistent notification (`goodwe_output_clamp`, replaced rather than
|
||||
stacked), an `ERROR` in the log with the reason code `OUTPUT_CLAMP`, a row in
|
||||
the event list, and a red status banner while it is engaged. Once it clears, a
|
||||
the event list, and a red status banner while it is engaged. The message quotes
|
||||
the command the loop computed and the value it was clamped to, both from the
|
||||
cycle that clamped. Once it clears, a
|
||||
warning row keeps the engagement count so the evidence does not vanish with the
|
||||
condition. Consecutive engagements share one event row carrying the exact count,
|
||||
because the event list keeps only 40 rows and a row per cycle would flush every
|
||||
@@ -1639,9 +1641,11 @@ other guard's entries out of it.
|
||||
**There is nothing to configure**, deliberately. The bound is `max_w`, which you
|
||||
already set; giving the guard a limit of its own would be a second number that
|
||||
can disagree with the first, which is exactly the failure the startup validation
|
||||
exists to prevent. The alarm's cadence - first engagement, then re-asserted every
|
||||
30 s while it persists, cleared after 3 clean cycles - is fixed for the same
|
||||
reason `RAIL_FRAC` is: it describes the notification bus, not the plant.
|
||||
exists to prevent. The alarm's cadence - at most one notification per 150 s
|
||||
(an episode that has not yet notified does so once it has engaged 3 cycles in
|
||||
a row), cleared after 3 clean
|
||||
cycles - is fixed for the same reason `RAIL_FRAC` is: it describes the
|
||||
notification bus, not the plant.
|
||||
|
||||
WARNING: **on a default install the engagement you will see is the integrator's,
|
||||
not the output's.** The control law bounds the integrator to `max_w` and *then*
|
||||
@@ -1650,6 +1654,15 @@ rating unless `integrator_max_w` has been deliberately raised above `max_w`.
|
||||
Both are watched. A guard that watched only the emitted value would be silent on
|
||||
every standard configuration.
|
||||
|
||||
**The integrator bound is not a bug, and it is reported as what it is.** It
|
||||
reads *"the loop's integrator reached its +5000 W anti-windup bound; the loop's
|
||||
command this cycle was +2000 W"*, titled *"the control loop is at its integrator
|
||||
bound"*, logged as a `WARNING`, with an amber (not red) status row. Brief
|
||||
engagements after a large load or solar step are normal. If it stays engaged,
|
||||
check that the battery is following its commands. Only a command over the rating
|
||||
carries the BUG SIGNAL text, and it never waits behind integrator-bound notices.
|
||||
Why: [`DECISIONS/SAFETY-40-the-integrator-bound-is-not-a-bug.md`](DECISIONS/SAFETY-40-the-integrator-bound-is-not-a-bug.md).
|
||||
|
||||
### The frozen-meter alarm
|
||||
|
||||
A meter that has died is easy — it stops answering, the sample age climbs past
|
||||
|
||||