SAFETY-32: bms_soc_floor per pack, rule 8 per unit
`bms_soc_floor` describes A BATTERY, not a site. At two packs of different models the cut-outs differ, and one number for both graded the shallower pack against the deeper one's BMS - so a site with cut-outs of 10 % and 30 % under `peak_soc_floor: 20` STARTED, and the guard would command a forced discharge that pack B's BMS, not the operator's floor, is the thing that stops. That is rule 8's own failure mode, reached through rule 8. Scoped to the card's third bullet, per its PM PROOFREAD: the aggregate anti-windup (DEV-02) and per-instance `achievable_w` (CFG-04) were verified as already shipped and are untouched. * config.yaml: `bms_soc_floor: int(0,50)` REQUIRED per `inverters:` entry. Nothing is inherited; the flat key stays the single-inverter shape's own cut-out. A per-entry DEFAULT was declined - a default is one number for every pack, which is this card's defect - and the decision is recorded. * inverter.py: `Inverter.bms_soc_floor`; an entry that states none gets None, not a borrowed number and not 0.0 (the most permissive value the key has). * peakguard.py: `Pack`, `pack_floor_pct()`, `pack_permissions()`, `binding_soc_floor()`. `discharge_permitted()` is unchanged and is still the one place the question is answered. * validate.py: `unit_bms_floors_indexed()` carries the ROSTER index; rule 8 grades EVERY unit and NAMES the one it refuses. Graded with the offender SECOND and with the same two numbers in the other order. * main.py: `Controller.packs`; `decide(soc_floor=...)` is the per-pack reduction of the same option; the floor-limited notification names the pack that stopped the site. `pack_floor_soc` - the emptiest pack, and its None-on-missing behaviour - is untouched. * tools/supervisor_shape_probe.py: RE-RUN and repaired. The required key broke §C and left §D printing PASS on a refusal about a different key. §D is now an isolated counterfactual over an accepted merged baseline, one key varied, asserting the key name. `all cases passed` on 2026.08.0. Stated rather than hidden: under any config rule 8 accepts the per-pack FLOOR reduces to `peak_soc_floor` for every pack. The reduction is written for `unit_caps_indexed()`'s reason and graded on both sides - 1775 rule-8-valid pairs answer the option, the pair rule 8 refuses answers the cut-out. `peak_soc_floor` is still one number for the site, so the "deeper pack needlessly withheld" half is filed as an open question, not closed. Full 19-file suite green. Twelve source mutations through tools/mutation_run.sh: eleven red, one argued survivor. The battery also found `_flat_bms_floor()` defaulting in two places, each covering for the other. No measurement of inverter B appears anywhere: it does not exist yet. Every second-pack figure is simulated and labelled. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
This commit is contained in:
committed by
glenn schrooyen
co-authored by
Claude Opus 5
parent
67e649ad6b
commit
f9e7fbf86d
@@ -15,6 +15,11 @@ The scalars, and what each one was silently asserting:
|
||||
SAFETY-24's pack floor and arbitrage's bounds. An
|
||||
average lets the emptier pack be driven below its own
|
||||
floor; a maximum parks the fuller one.
|
||||
`bms_soc_floor` SAFETY-32. ONE cut-out percent for every pack, and it
|
||||
describes A BATTERY. Two packs of different models
|
||||
have different cut-outs, so the flat key graded the
|
||||
shallower pack against the deeper one's BMS - wrong
|
||||
in the direction that empties a pack.
|
||||
`batt` ONE battery power into the anti-windup saturation
|
||||
detector - see the SITE/UNIT note at the bottom of
|
||||
this docstring, because this one goes the OTHER WAY.
|
||||
@@ -117,6 +122,12 @@ import math
|
||||
from datetime import datetime
|
||||
|
||||
from .clamp import ClampResult
|
||||
# CFG-03's ONE in-code mirror of config.yaml's SAFETY-24 defaults. Imported
|
||||
# rather than retyped: the flat-keys path below needs `bms_soc_floor`'s
|
||||
# shipped default and a literal here would be the fourth defaults site that
|
||||
# ticket exists to prevent. peakguard imports arbiter/control/tariff and none
|
||||
# of those imports this module, so the direction is one-way.
|
||||
from .peakguard import PEAK_OPTION_DEFAULTS
|
||||
from .store import unit_key
|
||||
from .watchdog import SignWatchdog, SignWatchdogConfig
|
||||
|
||||
@@ -170,7 +181,7 @@ class Inverter:
|
||||
|
||||
def __init__(self, name, *, setpoint_entity="", soc_entity="",
|
||||
batt_entity="", batt_invert=False, max_w=2000.0,
|
||||
store=None, sign_cfg=None):
|
||||
bms_soc_floor=None, store=None, sign_cfg=None):
|
||||
self.name = str(name)
|
||||
self.setpoint_entity = str(setpoint_entity or "")
|
||||
self.soc_entity = str(soc_entity or "")
|
||||
@@ -179,6 +190,19 @@ class Inverter:
|
||||
# The supervised cap on what may be written to THIS setpoint entity.
|
||||
# See the module docstring on why this is a number and not a `Tuning`.
|
||||
self.max_w = float(max_w)
|
||||
# SAFETY-32. THIS PACK'S OWN BMS CUT-OUT, in percent, or None when the
|
||||
# roster entry did not state one.
|
||||
#
|
||||
# ⚠️ NOT DEFAULTED HERE, AND None RATHER THAN A NUMBER. A cut-out is a
|
||||
# property of the battery in the cupboard; inventing one for a pack that
|
||||
# did not state it is precisely this card's defect - a pack graded
|
||||
# against a floor that belongs to a different battery - rebuilt in the
|
||||
# constructor. `peakguard.pack_floor_pct()` treats None as an unknown
|
||||
# floor and `discharge_permitted()` treats an unknown floor as NO
|
||||
# permission, so the absence costs a shave; validate.py rule 8 refuses
|
||||
# the config by name long before that, at startup.
|
||||
self.bms_soc_floor = (None if bms_soc_floor is None
|
||||
else float(bms_soc_floor))
|
||||
|
||||
# --- the device's own reported range, read from its own entity -------
|
||||
# None until `hass.limits()` has answered. NOT guessed at: ESPHome is
|
||||
@@ -339,8 +363,9 @@ def build_roster(opts: dict, store, sign_cfg=None) -> list:
|
||||
TWO SHAPES, AND WHICH ONE IS IN FORCE IS DECIDED BY ONE TEST: is
|
||||
`inverters:` empty?
|
||||
|
||||
EMPTY the five flat keys - `setpoint_entity`, `soc_entity`,
|
||||
`batt_entity`, `batt_invert`, `max_w` - describe the ONE inverter,
|
||||
EMPTY the six flat keys - `setpoint_entity`, `soc_entity`,
|
||||
`batt_entity`, `batt_invert`, `max_w`, `bms_soc_floor` (SAFETY-32)
|
||||
- describe the ONE inverter,
|
||||
exactly as the shipped scalars did. This is what every install
|
||||
that upgrades into this version reads, without an operator
|
||||
touching anything, and it is byte-identical to what DEV-02
|
||||
@@ -353,8 +378,8 @@ def build_roster(opts: dict, store, sign_cfg=None) -> list:
|
||||
`soc_entity` has no SoC sensor; it does NOT borrow the flat one,
|
||||
because "this unit's number came from somewhere else" is the
|
||||
defect DEV-02 spent a card removing and a fallback here would
|
||||
rebuild it in three lines. `name`, `setpoint_entity` and `max_w`
|
||||
are required of every entry - the schema enforces it on the
|
||||
rebuild it in three lines. `name`, `setpoint_entity`, `max_w` and
|
||||
`bms_soc_floor` (SAFETY-32) are required of every entry - the schema enforces it on the
|
||||
Supervisor path, `validate.py` rule 9 enforces it for sim/inject.py
|
||||
and the checks, which reach this function with any dict at all.
|
||||
|
||||
@@ -380,6 +405,12 @@ def build_roster(opts: dict, store, sign_cfg=None) -> list:
|
||||
batt_entity=opts.get("batt_entity", ""),
|
||||
batt_invert=bool(opts.get("batt_invert")),
|
||||
max_w=float(opts.get("max_w", 2000)),
|
||||
# SAFETY-32. THE FLAT KEY, because this IS the single-inverter shape
|
||||
# - the one pack the flat options describe is the one pack whose
|
||||
# cut-out `bms_soc_floor` states. Defaulted from CFG-03's single
|
||||
# mirror exactly as validate.py rule 8 defaults it, so an install
|
||||
# that never set the key reads the same 10 % in both places.
|
||||
bms_soc_floor=_flat_bms_floor(opts),
|
||||
store=store, sign_cfg=sign_cfg)]
|
||||
|
||||
roster = []
|
||||
@@ -401,10 +432,54 @@ def build_roster(opts: dict, store, sign_cfg=None) -> list:
|
||||
# ⚠️ NOT `opts["max_w"]`. See the docstring: a rating an entry did
|
||||
# not state is not the flat one, it is a rating rule 9 refuses.
|
||||
max_w=_entry_max_w(entry),
|
||||
# ⚠️ NOT `opts["bms_soc_floor"]`, FOR `max_w`'S REASON AND THIS
|
||||
# CARD'S. An entry that omits its cut-out has NOT got the flat one;
|
||||
# it has none, and rule 8 refuses it by name. Borrowing here would be
|
||||
# SAFETY-32's own defect written in three lines - the shallower pack
|
||||
# graded against the deeper pack's BMS.
|
||||
bms_soc_floor=_entry_bms_floor(entry),
|
||||
store=store, sign_cfg=sign_cfg))
|
||||
return roster
|
||||
|
||||
|
||||
def _flat_bms_floor(opts: dict):
|
||||
"""The single-inverter shape's own cut-out, or None if it is unparseable.
|
||||
|
||||
Defaulted from `PEAK_OPTION_DEFAULTS` when the key is absent or blank, which
|
||||
is `validate._number()`'s behaviour on the same key - the two have to agree
|
||||
or the validator would grade a number the roster does not build.
|
||||
"""
|
||||
# ⚠️ ONE defaulting line, not two. The first cut wrote the fallback into the
|
||||
# `.get()` AND into the blank test below it, and a mutation that deleted
|
||||
# either one survived - each was covering for the other, which is
|
||||
# MUTATION.md's masking section in three lines of configuration reading.
|
||||
raw = opts.get("bms_soc_floor")
|
||||
if raw is None or raw == "":
|
||||
return float(PEAK_OPTION_DEFAULTS["bms_soc_floor"])
|
||||
try:
|
||||
return float(raw)
|
||||
except (TypeError, ValueError):
|
||||
return None
|
||||
|
||||
|
||||
def _entry_bms_floor(entry: dict):
|
||||
"""One entry's OWN cut-out, or None when it did not state a usable one.
|
||||
|
||||
None rather than a borrowed number and rather than 0.0 - `_entry_max_w()`
|
||||
can answer 0.0 because a zero rating commands nothing, but a zero FLOOR is
|
||||
the most permissive value the key has and would read as "this pack may be
|
||||
emptied". Rule 8 refuses the missing key by name; until it does, None
|
||||
withholds.
|
||||
"""
|
||||
raw = entry.get("bms_soc_floor")
|
||||
if raw is None or raw == "":
|
||||
return None
|
||||
try:
|
||||
return float(raw)
|
||||
except (TypeError, ValueError):
|
||||
return None
|
||||
|
||||
|
||||
def _entry_max_w(entry: dict) -> float:
|
||||
"""One entry's supervised cap, or 0.0 when it did not state a usable one.
|
||||
|
||||
|
||||
@@ -1065,6 +1065,26 @@ class Controller:
|
||||
return None
|
||||
return float(min(float(v) for v in vals))
|
||||
|
||||
@property
|
||||
def packs(self) -> list:
|
||||
"""SAFETY-32. Each pack as its own THREE numbers, in roster order.
|
||||
|
||||
`pack_floor_soc` above is the site's ONE verdict and stays exactly what
|
||||
DEV-02 made it - the emptiest measured pack. This is the thing that
|
||||
reduction cannot produce: by the time `min()` has answered, WHICH pack
|
||||
the number came from and how far that pack was from ITS OWN cut-out have
|
||||
both been thrown away, and two packs at 15 % against cut-outs of 10 % and
|
||||
20 % have opposite answers that are indistinguishable afterwards.
|
||||
|
||||
⚠️ EVERY unit, live or not. Same reason as `inputs_ok`: a pack whose SoC
|
||||
did not answer is a pack nothing can grade, and dropping it from this
|
||||
list would let the site spend the packs that DID answer while one sat
|
||||
unmeasured. `peakguard.discharge_permitted()` treats a None SoC as no
|
||||
permission, which is where that must be decided.
|
||||
"""
|
||||
return [peakguard.Pack(inv.name, inv.soc, inv.bms_soc_floor)
|
||||
for inv in self.inverters]
|
||||
|
||||
@property
|
||||
def inputs_ok(self) -> bool:
|
||||
"""The site meter, and EVERY pack's own two readings.
|
||||
@@ -1881,9 +1901,21 @@ class Controller:
|
||||
# protect. None stays None: `decide()` treats it as floor-limited,
|
||||
# which costs a shave rather than a pack.
|
||||
soc=self.pack_floor_soc,
|
||||
soc_floor=float(self.o.get(
|
||||
# ⚠️ SAFETY-32. THE SAME OPTION, REDUCED OVER THE PACKS' OWN
|
||||
# CUT-OUTS. `peak_soc_floor` is still one site-wide EMS floor and is
|
||||
# still read from that one key with CFG-03's one mirror behind it;
|
||||
# what `binding_soc_floor()` adds is the conjunction with each pack's
|
||||
# OWN `bms_soc_floor`, so the floor this site is graded against can
|
||||
# never be below the deepest cut-out on the roster. MAXIMUM here
|
||||
# pairs with the MINIMUM in `pack_floor_soc`: both reductions move
|
||||
# the verdict towards refusing a shave and away from spending a pack.
|
||||
# Under any config rule 8 accepts it IS the option, for every pack -
|
||||
# asserted over the whole schema range in test_peakguard.py part 12
|
||||
# rather than assumed, because "another rule refuses that" is a claim
|
||||
# about rule ordering and sim/inject.py does not run rule 8 at all.
|
||||
soc_floor=peakguard.binding_soc_floor(self.packs, float(self.o.get(
|
||||
"peak_soc_floor",
|
||||
peakguard.PEAK_OPTION_DEFAULTS["peak_soc_floor"])),
|
||||
peakguard.PEAK_OPTION_DEFAULTS["peak_soc_floor"]))),
|
||||
max_hold_s=self.p1.averager.max_hold_s,
|
||||
# ⚠️ SAFETY-20. The device range goes in TOO, and this call site is
|
||||
# the one that needed it most: `standing` is `last_write`, i.e. the
|
||||
@@ -2596,6 +2628,22 @@ class Controller:
|
||||
# notification that matters into a traceback.
|
||||
_at_floor = ("at the floor" if g.soc_floor is None
|
||||
else f"at {float(g.soc_floor):.0f} %")
|
||||
# ⚠️ SAFETY-32. WHICH PACK STOPPED THE SITE. `g.soc_floor` is the floor
|
||||
# the decision was actually taken with, so this re-grades nothing and
|
||||
# cannot disagree with the alarm it is printed inside. At a roster of one
|
||||
# the sentence is omitted entirely and this notification is byte-for-byte
|
||||
# what SAFETY-25 shipped - there is exactly one pack and naming it would
|
||||
# be noise on every existing install.
|
||||
_blocked = [name for name, why
|
||||
in peakguard.pack_permissions(self.packs, g.soc_floor)
|
||||
if why is not None]
|
||||
_which = ("" if len(self.inverters) < 2 else
|
||||
f"\n\nSAFETY-32 - WHICH PACK: this is graded per pack against "
|
||||
f"that pack's own BMS cut-out (bms_soc_floor), and the "
|
||||
f"pack(s) at or below their own floor right now are "
|
||||
f"{', '.join(_blocked) if _blocked else '(none - see the reason above)'}"
|
||||
f". The other packs on the roster are not the reason the guard "
|
||||
f"stopped and raising their cut-out will not change this.")
|
||||
await self.hass.call("persistent_notification", "create", {
|
||||
"notification_id": "goodwe_peak_soc_floor",
|
||||
"title": "GoodWe: the capacity-peak guard has run out of battery",
|
||||
@@ -2615,7 +2663,7 @@ class Controller:
|
||||
f"{_at_floor} - ordinary self-consumption has no SoC "
|
||||
f"floor at all and will go on discharging past it, down to the "
|
||||
f"pack's own BMS cut-out. What has stopped is the guard buying "
|
||||
f"you a lower bill, not the pack being spent."),
|
||||
f"you a lower bill, not the pack being spent." + _which),
|
||||
})
|
||||
|
||||
async def check_circulating(self) -> None:
|
||||
|
||||
@@ -360,6 +360,29 @@ distinction in DOCS.md and in this comment. Revisit if a THIRD floor appears -
|
||||
a loop-side guard would be the third - at which point the migration buys enough
|
||||
to be worth its cost.
|
||||
|
||||
------------------------------------------------------------------------------
|
||||
SAFETY-32: ONE `bms_soc_floor` FOR TWO PACKS GRADES ONE AGAINST THE OTHER'S BMS
|
||||
|
||||
`bms_soc_floor` above describes A PACK, not a site, and it was a flat option
|
||||
because there was one pack. At two, two batteries of different models have
|
||||
different cut-outs, and one number for both is wrong in the direction that
|
||||
empties a battery: the SHALLOWER pack (the higher cut-out) is protected by a
|
||||
floor that belongs to the DEEPER one. So it became a roster key - `Pack` carries
|
||||
each unit's own value, `pack_floor_pct()` conjoins it with the site's EMS floor,
|
||||
and validate.py rule 8 grades EVERY unit and NAMES the one it refuses.
|
||||
|
||||
⚠️ `peak_soc_floor` DID NOT MOVE, AND THE RESIDUAL IS RECORDED RATHER THAN
|
||||
HIDDEN. It is one number for the site, so with cut-outs of 10 % and 18 % the
|
||||
operator must set it above 18 and the deeper pack is then withheld above its own
|
||||
need. That half - a per-pack EMS floor - is NOT this card and must not be
|
||||
smuggled in with it; DECISIONS/SAFETY-32-per-pack-bms-floor.md states it as the
|
||||
open question it is.
|
||||
|
||||
⚠️ AND THE MIN() OVER MEASURED SoC IS STILL RIGHT. `Controller.pack_floor_soc`
|
||||
reduces to the emptiest pack and this card does not touch it. What changed is
|
||||
the FLOOR it is graded against, and the addition of a per-pack answer beside the
|
||||
site's one verdict - see `pack_permissions()`.
|
||||
|
||||
------------------------------------------------------------------------------
|
||||
AND IT READS NO PER-PHASE QUANTITY, ON PURPOSE
|
||||
|
||||
@@ -572,6 +595,110 @@ def discharge_permitted(soc, soc_floor) -> str | None:
|
||||
return None
|
||||
|
||||
|
||||
@dataclass(frozen=True)
|
||||
class Pack:
|
||||
"""SAFETY-32. ONE pack's three numbers for the floor question, NAMED.
|
||||
|
||||
`name` the roster name, because a refusal that does not say WHICH pack
|
||||
stopped the site sends an operator to the wrong device - the
|
||||
same defect CFG-04's `unit_caps_indexed()` was written for.
|
||||
`soc` THIS pack's measured state of charge. None when its sensor did
|
||||
not answer, and None is not a full battery.
|
||||
`bms_floor` THIS pack's OWN cut-out percent (`bms_soc_floor`), which is a
|
||||
property of the hardware in the cupboard and NOT of the site.
|
||||
None when the roster entry did not state one - see
|
||||
`pack_floor_pct()` for why that is withheld and not 0 %.
|
||||
|
||||
⚠️ IT CARRIES THE CUT-OUT, NOT THE EMS FLOOR. `peak_soc_floor` is one number
|
||||
for the whole site (the depth a money-saving discharge may never reach) and
|
||||
stays a flat option; `bms_soc_floor` describes a battery and became a roster
|
||||
key here, because two packs of different models have different cut-outs and
|
||||
grading both against one of them is wrong in the direction that empties the
|
||||
shallower one.
|
||||
"""
|
||||
|
||||
name: str
|
||||
soc: float | None
|
||||
bms_floor: float | None
|
||||
|
||||
|
||||
def pack_floor_pct(pack, soc_floor):
|
||||
"""The percent THIS pack may not be spent below, or None if that is unknown.
|
||||
|
||||
`max(the site's EMS floor, this pack's own cut-out)` - the CONJUNCTION, and
|
||||
the direction matters: the EMS floor is what the operator asked for and the
|
||||
cut-out is what the hardware will do anyway, so a pack is protected by
|
||||
whichever is higher. Taking the site floor alone is the shipped defect this
|
||||
card removes (the shallower pack graded against the deeper one's cut-out);
|
||||
taking the cut-out alone would throw SAFETY-24's margin away.
|
||||
|
||||
⚠️ AN UNSTATED CUT-OUT IS None, NOT ZERO, AND NOT THE FLAT OPTION. 0 % would
|
||||
be a floor that permits everything - the most permissive value there is,
|
||||
invented from an absence - and borrowing the flat `bms_soc_floor` is CFG-04's
|
||||
"nothing is inherited" broken in one line, which is this card's whole subject
|
||||
restated. `discharge_permitted()` already treats a None floor as NO
|
||||
permission, so an entry that forgot the key costs a shave rather than a pack.
|
||||
|
||||
⚠️ AND UNDER A rule-8-VALID CONFIG THIS IS `soc_floor`, FOR EVERY PACK.
|
||||
validate.py rule 8 refuses `peak_soc_floor <= bms_soc_floor` on EVERY unit,
|
||||
so `max()` selects the EMS floor everywhere the add-on will actually start -
|
||||
which is exactly why the reduction is written here rather than assumed at the
|
||||
call site. "Another rule refuses that config" is a claim about today's rule
|
||||
ordering, not a property of this function, and `validate_startup_config()` is
|
||||
also `sim/inject.py`'s entry point. `unit_caps_indexed()`'s docstring records
|
||||
the same argument, and CFG-04's index desynchronisation is what happened the
|
||||
last time it was left implicit.
|
||||
"""
|
||||
if soc_floor is None or pack.bms_floor is None:
|
||||
return None
|
||||
return max(float(soc_floor), float(pack.bms_floor))
|
||||
|
||||
|
||||
def pack_permissions(packs, soc_floor) -> list[tuple[str, str | None]]:
|
||||
"""SAFETY-32. Per pack: None if it may be spent, else the reason it may not.
|
||||
|
||||
ONE `(name, reason)` pair per pack, in roster order, from the SAME
|
||||
`discharge_permitted()` the site verdict uses - a second transcription of
|
||||
"may this pack be spent" is a second answer to it, which is the argument
|
||||
that made that predicate public in the first place.
|
||||
|
||||
⚠️ THIS IS THE OBSERVABLE THE MIN() CANNOT PRODUCE. `Controller.pack_floor_soc`
|
||||
reduces the measured SoC to the emptiest pack BEFORE anything is graded, and
|
||||
that reduction is right for the site's one verdict - but it has thrown away
|
||||
which pack it came from and how far that pack was from ITS OWN floor by the
|
||||
time the answer exists. Two packs at 15 % against floors of 10 % and 20 %
|
||||
have opposite answers and are indistinguishable after the `min()`.
|
||||
"""
|
||||
return [(p.name, discharge_permitted(p.soc, pack_floor_pct(p, soc_floor)))
|
||||
for p in packs]
|
||||
|
||||
|
||||
def binding_soc_floor(packs, soc_floor):
|
||||
"""The ONE floor `decide()` may grade `pack_floor_soc` against, at a roster.
|
||||
|
||||
MAXIMUM over the packs' own floors, and it is the conservative reduction that
|
||||
pairs with the MINIMUM `pack_floor_soc` reduction: `min(soc) <= max(floor)`
|
||||
is implied by "some pack is at or below its own floor", so this verdict is
|
||||
never more permissive than grading each pack separately would be. The other
|
||||
direction is not true and is not claimed - a site can be refused here while
|
||||
every pack individually has headroom, which costs a shave and never a pack.
|
||||
|
||||
None when ANY pack's floor is unknown, for `Controller.site_dev_bound()`'s
|
||||
reason and in the same direction: `discharge_permitted()` treats a None floor
|
||||
as no permission, so an unknown floor withholds rather than defaults.
|
||||
|
||||
⚠️ AT N=1 THIS IS `soc_floor` ITSELF under any config rule 8 accepts, and
|
||||
test_peakguard.py part 12 asserts that over the whole schema range rather
|
||||
than assuming it.
|
||||
"""
|
||||
if not packs:
|
||||
return None if soc_floor is None else float(soc_floor)
|
||||
floors = [pack_floor_pct(p, soc_floor) for p in packs]
|
||||
if any(f is None for f in floors):
|
||||
return None
|
||||
return max(floors)
|
||||
|
||||
|
||||
def decide(projection, *, batt_w, cap_w, reading, achievable_w, soc, soc_floor,
|
||||
max_hold_s=None, frozen: bool = False) -> PeakDecision:
|
||||
"""The whole guard. Pure: no clock, no I/O, no state carried between calls.
|
||||
|
||||
@@ -132,7 +132,7 @@ NOT READY banner already names the problem, (b) does not apply.
|
||||
installed base is on a fixed or static tariff. Refusing to start without a
|
||||
price feed would lock those sites out of the add-on entirely.
|
||||
|
||||
8. `peak_soc_floor` at or below `bms_soc_floor`. [(a)]
|
||||
8. `peak_soc_floor` at or below `bms_soc_floor`, ON ANY UNIT. [(a)]
|
||||
SAFETY-24, and the same shape as 1, 4, 5 and 6. The peak guard can COMMAND
|
||||
a discharge to hold a billed quarter down (SAFETY-07), and `peak_soc_floor`
|
||||
is the EMS-side bound on how far down it may take the pack. The BMS has its
|
||||
@@ -142,6 +142,12 @@ NOT READY banner already names the problem, (b) does not apply.
|
||||
of binding while its status page reports one - rule 5's "a disarmed guard
|
||||
that advertises itself as armed", on the guard whose failure mode is a pack
|
||||
that is quietly never available when it is wanted.
|
||||
⚠️ SAFETY-32: `bms_soc_floor` DESCRIBES A BATTERY, so at a roster it is a
|
||||
per-entry key and this rule grades EVERY unit and NAMES the one it refuses.
|
||||
One number for two packs of different models refuses the wrong config and
|
||||
accepts the wrong one - cut-outs of 10 % and 30 % under `peak_soc_floor: 20`
|
||||
used to start. A missing per-entry cut-out is refused here rather than
|
||||
defaulted: a cut-out invented for a pack IS this defect.
|
||||
|
||||
⚠️ `<=`, NOT `<`, and the equality case is the interesting one. At exactly
|
||||
equal, the EMS floor and the pack's cut-out act at the same percent, so the
|
||||
@@ -386,6 +392,49 @@ def unit_caps_indexed(opts: dict) -> list[tuple[int, float]]:
|
||||
return caps
|
||||
|
||||
|
||||
def unit_bms_floors_indexed(opts: dict) -> list[tuple[int, object, object]]:
|
||||
"""SAFETY-32. Each pack's OWN `bms_soc_floor`, carrying its ROSTER INDEX.
|
||||
|
||||
`(roster index, the raw value as configured, the parsed float or None)`, one
|
||||
triple per unit. The raw value travels too because the refusal quotes what
|
||||
the operator actually wrote, and `!r` of a re-read `opts` key is the wrong
|
||||
string the moment the value came off a roster entry.
|
||||
|
||||
⚠️ THE INDEX IS THE ROSTER'S, NOT THIS LIST'S, AND THAT IS CFG-04'S BUG
|
||||
WRITTEN DOWN. Rules 5 and 6 fed a CAPS-list index into `_unit_label()`,
|
||||
which indexes the ROSTER, so on a roster whose first entry was malformed the
|
||||
refusal named the WRONG INVERTER - an operator sent to the wrong device by
|
||||
the very message that exists to stop that. `unit_caps_indexed()` exists
|
||||
because of it. This function goes one step further and SKIPS NOTHING: every
|
||||
entry produces a triple, including the ones with no usable floor, because a
|
||||
missing cut-out is itself what rule 8 has to refuse BY NAME. There is
|
||||
therefore no second list for an index to desynchronise from.
|
||||
|
||||
⚠️ AND NOTHING IS INHERITED. At a declared roster the FLAT `bms_soc_floor` is
|
||||
not read at all - CFG-04's rule, and this card's subject: a pack that borrows
|
||||
a sibling's cut-out is graded against a battery it is not. At the flat shape
|
||||
the flat key IS this one pack's cut-out, defaulted from CFG-03's single
|
||||
mirror exactly as `inverter._flat_bms_floor()` defaults it.
|
||||
"""
|
||||
entries = roster_entries(opts)
|
||||
if not entries:
|
||||
return [(0, opts.get("bms_soc_floor"),
|
||||
_number(opts, "bms_soc_floor",
|
||||
PEAK_OPTION_DEFAULTS["bms_soc_floor"]))]
|
||||
out: list[tuple[int, object, object]] = []
|
||||
for index, entry in enumerate(entries):
|
||||
if not isinstance(entry, dict):
|
||||
# Rule 9(a)/(b) already refuses a non-dict entry by index, and it
|
||||
# runs FIRST. Naming it twice would hand the operator two sentences
|
||||
# about one line of YAML.
|
||||
continue
|
||||
raw = entry.get("bms_soc_floor")
|
||||
out.append((index, raw,
|
||||
None if raw is None or raw == ""
|
||||
else _number(entry, "bms_soc_floor", None)))
|
||||
return out
|
||||
|
||||
|
||||
def _unit_label(opts: dict, index: int) -> str:
|
||||
""""" at a single-inverter config, " (inverter-b)" at a roster.
|
||||
|
||||
@@ -871,28 +920,39 @@ def validate_startup_config(opts: dict, dev_min=None, dev_max=None) -> list[str]
|
||||
# in-code mirror, pinned to config.yaml by test_peakguard.py, and main.py
|
||||
# reads the same one - exactly as maintenance.MAINT_OPTION_DEFAULTS now is
|
||||
# for the `maintenance_*` family.
|
||||
#
|
||||
# ⚠️ SAFETY-32 - GRADED ONCE PER UNIT, AND THE REFUSAL NAMES THE UNIT. One
|
||||
# `bms_soc_floor` for two packs compares the EMS floor against whichever
|
||||
# battery happened to be written into the flat key: a site with cut-outs of
|
||||
# 10 % and 30 % and `peak_soc_floor: 20` STARTED, and the guard would then
|
||||
# command a forced discharge that the second pack's BMS - not the operator's
|
||||
# floor - is the thing that stops. That is the disarmed-backstop state this
|
||||
# rule exists to refuse, reached through the rule itself. So the loop is over
|
||||
# units, and `_unit_label()` is fed the ROSTER index the value came off (see
|
||||
# `unit_bms_floors_indexed()`), because CFG-04 has just fixed the version of
|
||||
# this that named the wrong inverter.
|
||||
soc_floor = _number(opts, "peak_soc_floor",
|
||||
PEAK_OPTION_DEFAULTS["peak_soc_floor"])
|
||||
bms_floor = _number(opts, "bms_soc_floor",
|
||||
PEAK_OPTION_DEFAULTS["bms_soc_floor"])
|
||||
if soc_floor is None or bms_floor is None:
|
||||
problems.append(
|
||||
"peak_soc_floor and bms_soc_floor must both be numbers (got "
|
||||
f"{opts.get('peak_soc_floor')!r} / {opts.get('bms_soc_floor')!r})")
|
||||
elif soc_floor <= bms_floor:
|
||||
problems.append(
|
||||
f"peak_soc_floor is {soc_floor:.0f} % but the pack's own cut-out "
|
||||
f"(bms_soc_floor) is {bms_floor:.0f} %, so SAFETY-07's forced "
|
||||
"discharge has no EMS-side bound at all - THE BMS WINS, and it is "
|
||||
"the pack's protection rather than yours. The guard would report a "
|
||||
"SoC floor on its status page while being incapable of ever being "
|
||||
"the thing that stops the discharge, and the symptom of that is a "
|
||||
"battery repeatedly sitting at the BMS limit with no record of why "
|
||||
f"- which looks exactly like the SoC drift the maintenance cycle "
|
||||
f"exists to correct. Raise peak_soc_floor above {bms_floor:.0f} % "
|
||||
f"(the shipped default is "
|
||||
f"{PEAK_OPTION_DEFAULTS['peak_soc_floor']:.0f} %), or correct "
|
||||
"bms_soc_floor if it does not match this pack.")
|
||||
for _ix, _raw, bms_floor in unit_bms_floors_indexed(opts):
|
||||
where = _unit_label(opts, _ix)
|
||||
if soc_floor is None or bms_floor is None:
|
||||
problems.append(
|
||||
f"peak_soc_floor and bms_soc_floor{where} must both be numbers "
|
||||
f"(got {opts.get('peak_soc_floor')!r} / {_raw!r})")
|
||||
elif soc_floor <= bms_floor:
|
||||
problems.append(
|
||||
f"peak_soc_floor is {soc_floor:.0f} % but the pack's own cut-out "
|
||||
f"(bms_soc_floor{where}) is {bms_floor:.0f} %, so SAFETY-07's forced "
|
||||
"discharge has no EMS-side bound at all - THE BMS WINS, and it is "
|
||||
"the pack's protection rather than yours. The guard would report a "
|
||||
"SoC floor on its status page while being incapable of ever being "
|
||||
"the thing that stops the discharge, and the symptom of that is a "
|
||||
"battery repeatedly sitting at the BMS limit with no record of why "
|
||||
f"- which looks exactly like the SoC drift the maintenance cycle "
|
||||
f"exists to correct. Raise peak_soc_floor above {bms_floor:.0f} % "
|
||||
f"(the shipped default is "
|
||||
f"{PEAK_OPTION_DEFAULTS['peak_soc_floor']:.0f} %), or correct "
|
||||
f"bms_soc_floor{where} if it does not match this pack.")
|
||||
|
||||