SAFETY-81 review: 10 s hold, ERROR line per episode, more scenarios
- The alarm must hold for peakguard.ALARM_HOLD_S (10 s) on the projection's
clock. A load that tops cap + battery for ~5 s every 30 s alarmed at every
quarter start while the quarter landed under the aim (sine4500_fast).
- A cycle with no battery reading leaves the hold alone.
- Notified once per quarter, but the ERROR line is written per episode.
- New sim scenarios (sine4500_fast, twice7000, step6500_gap) with 5a4cdc2
digests; control still byte-identical. Unit checks for export and the
hold across a missing reading. test_peakguard's saturated fixture moves
the hold start back instead of waiting it out.
- DECISIONS and DOCS updated: costs of the hold, tolerance reasoning, the
double count in control left to a follow-up.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
This commit is contained in:
@@ -1259,6 +1259,13 @@ check(f"the saturating fixture ({NET2:.0f} W) is a load the real ingest "
|
||||
f"accepts, not one it rejects as implausible", NET2 < PLAUSIBLE_MAX_W)
|
||||
print(f" saturated case: {c2.peak_guard.explain()}")
|
||||
check("a load larger than the inverter saturates the guard", c2.peak_guard.saturated)
|
||||
# SAFETY-81 review: the alarm must hold ALARM_HOLD_S first. The fixture runs on
|
||||
# the wall clock, so the start of the hold is moved back instead of waited out.
|
||||
check("...but not on its first cycle: it must hold peakguard.ALARM_HOLD_S "
|
||||
"(SAFETY-81)", hass2.notifications.count("goodwe_peak_saturated") == 0
|
||||
and c2._peak_high_since is not None)
|
||||
c2._peak_high_since -= timedelta(seconds=peakguard.ALARM_HOLD_S)
|
||||
asyncio.get_event_loop_policy().new_event_loop().run_until_complete(c2.cycle())
|
||||
check("...and THAT raises exactly one notification, with its own id - the one "
|
||||
"state where the money will be spent and a human is the only remaining "
|
||||
"actuator", hass2.notifications.count("goodwe_peak_saturated") == 1)
|
||||
|
||||