SAFETY-81 review: 10 s hold, ERROR line per episode, more scenarios
- The alarm must hold for peakguard.ALARM_HOLD_S (10 s) on the projection's
clock. A load that tops cap + battery for ~5 s every 30 s alarmed at every
quarter start while the quarter landed under the aim (sine4500_fast).
- A cycle with no battery reading leaves the hold alone.
- Notified once per quarter, but the ERROR line is written per episode.
- New sim scenarios (sine4500_fast, twice7000, step6500_gap) with 5a4cdc2
digests; control still byte-identical. Unit checks for export and the
hold across a missing reading. test_peakguard's saturated fixture moves
the hold start back instead of waiting it out.
- DECISIONS and DOCS updated: costs of the hold, tolerance reasoning, the
double count in control left to a follow-up.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
This commit is contained in:
@@ -3212,9 +3212,10 @@ reason code `OUTPUT_CLAMP`.
|
||||
**Load too high for battery.** The capacity-peak guard (SAFETY-07) asks for
|
||||
everything the inverter can discharge and the running 15-minute average is
|
||||
still projected over the peak limit, so the month's billed peak
|
||||
(capaciteitstarief) goes up. It fires only when, with the battery at full
|
||||
power, the period will still end more than 10 W over the real limit (not the
|
||||
margin's aim), and at most once per period (SAFETY-81). In shadow mode the
|
||||
(capaciteitstarief) goes up. It fires only when, for 10 s, the period would
|
||||
still end more than 10 W over the real limit (not the margin's aim) with the
|
||||
battery at full power. It notifies at most once per period; later overloads
|
||||
in the same period go to the log (SAFETY-81). In shadow mode the
|
||||
guard's projection is made on a plant that did not respond (SAFETY-47), and
|
||||
the text says so. See *The capacity-peak guard*.
|
||||
|
||||
|
||||