SAFETY-30: grade each inverter against its own power, and the site's total against the meter
checks / unit (pull_request) Successful in 4m38s
checks / unit (pull_request) Successful in 4m38s
THE DEFECT, in one line. `inv.sign_wd.evaluate(stood, self.grid, ...)` compared
the command THIS controller put on ONE actuator against what the WHOLE SITE is
exchanging with the network. At a roster of one those are two views of the same
thing - specs.md §6.2's identity - and that is what makes the check sound and
what earned it the best record in the safety table (NOTES.md: 93 % agreement
while healthy against 4 % during runaway, four observed episodes, zero false
positives). At two inverters they are not, and it fails in BOTH directions:
FALSE TRIP inverter A commanded -1500 W while the meter reads +1500 W is
evidence of nothing when inverter B is discharging 3000 W exactly
as told. Nothing is faulty and the highest-value check fires.
MISSED the converse, and it is worse. A unit commanded +1500 W and
MEASURED at -1500 W, beside a sibling at +1500 W, leaves P1
exactly where a healthy site leaves it. The summation destroys the
evidence and no threshold recovers it.
DEV-02 had already shipped the per-INSTANCE half - one SignWatchdog per
inverter, namespaced latch, a trip on B no longer latching A. What was left was
the COMPARISON, and it is two questions rather than one:
PER UNIT this unit's standing command against ITS OWN measured power
(`Inverter.batt`, holding register 0x0518, per-instance since
DEV-02). Conclusion: "the actuator I am driving is not doing what I
told it" - a fact about one device, so the remedy stays the per-unit
`failsafe` SET that arbiter.CLAIM_SCOPE has classified SCOPE_UNIT
from the day it was written. That entry read "the evidence is
site-wide and the remedy is not"; the first half is now simply true.
SITE the SUM of the standing commands against the meter, as a new
`sign_site` SET at P_SAFETY on the site actuator, latched under flat
`site_sign_tripped` / `site_sign_reason`. This is the 2026-08-20
fault day and NO per-unit check can see it, because every inverter
may be faithfully executing its share of a number that is itself
wrong. It stops every inverter and the banner names the site.
WHAT IT IS NOT, said here because two guards that overlap without saying so is
how a false-alarm generator gets built. It is not SAFETY-31: circulation.py
compares the units AGAINST EACH OTHER and catches them pushing power THROUGH
each other, which nets to zero at the meter and about which no single command is
evidence. This compares each unit against ITS OWN COMMAND. They overlap in
exactly one scenario - a unit reversing while its sibling pulls the other way -
and test_watchdog.py asserts on that fixture that both fire and what each
concludes. It is also not the saturation freeze, which is a MAGNITUDE test
(|command - measured| > 500 W) that shapes the loop and fires on a merely
saturated unit; this is a DIRECTION test that latches and parks one.
THE FOUR NUMBERS, RE-DERIVED AT TWO INVERTERS - one carried with a justification
and one refused. 1890 closed-loop runs on admin/goodwe's TEST-19 two-master rig
in which NOTHING is faulty, swept over the whole range config.yaml accepts for
`gain` and `slew_w`, across load reversals with write staggers and flapping
loads, and RUN AT BOTH ROSTERS so the N=1 arm is the control:
unit_sign_disagree_w 250 `saturation_w / 2`. The check gates on both sides,
opposed, so the smallest gap it can see is 500 W -
exactly where compute()'s own anti-windup test
already says the inverter is not following. It
cannot fire on a divergence the control law calls
ordinary tracking. Worst legitimate opposition at
250 W: 10.0 s; the curve is nearly flat, because a
unit's own power chases its own command.
unit_sign_disagree_s 85 8.5x that 10.0 s, 2.8x the firmware's own 30 s
link veto (inverter.LINK_STALE_S), under half the
180 s site hold.
site_sign_disagree_w 300 CARRIED. Its argument is the meter's noise floor
and the 15 W deadband; the roster touches neither,
and the campaign agrees - the gate opens in 994 of
1050 runs at two inverters and 955 of 1050 at one.
site_sign_disagree_s 325 NOT CARRIED, and this is the number the card
exists to not assume. The worst legitimate
crossing at 300 W is 110 s with one inverter and
215 s with TWO, because the command must travel a
rail that is the roster sum at a `slew_w` that is
not - reachable at gain 0.05, slew_w 50 and a
2.2 kW load reversal, all schema-legal. 180 s
would have shipped a false trip. 325 s is 1.51x
the measured worst, inside the 900 s billing
quarter and inside every episode of the fault day.
AT ONE INVERTER NOTHING CHANGES, and "nothing" is asserted rather than assumed.
The two questions are the same sentence there, so only the detector that shipped
is armed: same comparison against the meter, same 300 W / 180 s, same reason
string byte for byte, same namespaced latch and flat rollback mirror, same
`failsafe` claim, same banner, same single status row - and the site detector is
NEVER CALLED, counted on the object over twelve cycles.
VERIFIED BY BREAKING IT. Thirteen mutations on fresh per-mutation trees with no
__pycache__, mounted :ro, with the battery refusing to report at all unless the
baseline is green. Twelve red on the first pass. M4 - the site half armed at N=1
as well - SURVIVED, because the check read `disagree_since is None` and the unit
detector trips first, parks the inverter and leaves the site standing at 0 W:
the assertion ran, the sentence was true, and the data could not reach the
failure it named. Replaced with a call counter on the object; M4 is red now.
Recorded as a survivor in DECISIONS/SAFETY-30-per-unit-sign.md §5, with the
first battery's own RED BASELINE - a shared mutation directory read mid-copy -
discarded rather than reported.
RECORDED, NOT FIXED: the site comparison is defeated by a square-wave load whose
half period is about one control cycle, which holds it opposed for ~1000 s. The
N=1 control arm is what makes that interpretable - it is identical at the roster
this add-on ships, so it is a property of comparing a lagged command against a
meter and has nothing to do with the second inverter. It wants an alternation
test rather than a number, and a card of its own.
SAFETY-24's lo-only asymmetry proof re-run unchanged: 1296 combinations, 0
negative floors, `hi` +inf on every claim, every claim on the SITE actuator.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
This commit is contained in:
@@ -74,7 +74,8 @@ NOT READY banner already names the problem, (b) does not apply.
|
||||
was overruled. That firmware file's own comment says a lower bound on this
|
||||
"belongs in CFG-01, not here" - so here it is.
|
||||
|
||||
5. `sign_disagree_w` at or above `max_w`. [(a)]
|
||||
5. `sign_disagree_w` - or SAFETY-30's `unit_sign_disagree_w` - at or above
|
||||
`max_w`. [(a)]
|
||||
The arbiter's `supervised` limit bounds every command to +-max_w, and
|
||||
SAFETY-02's predicate needs `abs(command) > sign_disagree_w`. Set the
|
||||
threshold at or above the ceiling and the command side of the comparison
|
||||
@@ -207,6 +208,7 @@ from .p1 import is_enabled, validate_meter_options
|
||||
from .peakguard import PEAK_OPTION_DEFAULTS
|
||||
from .price import PRICE_OPTION_DEFAULTS, PROVIDERS
|
||||
from .static_tariff import ProfileInvalid, parse_static_profile
|
||||
from .watchdog import SIGN_OPTION_DEFAULTS
|
||||
|
||||
_LOG = logging.getLogger("goodwe.config")
|
||||
|
||||
@@ -458,6 +460,38 @@ def validate_startup_config(opts: dict, dev_min=None, dev_max=None) -> list[str]
|
||||
f"sign_disagree_w below {max_w:.0f} W (300 W is the measured "
|
||||
"default), or raise max_w.")
|
||||
|
||||
# ⚠️ AND THE SAME RULE FOR SAFETY-30's PER-UNIT THRESHOLD, WHICH IS A
|
||||
# SEPARATE COMPARISON AND THEREFORE A SEPARATE WAY TO DISARM. It grades a
|
||||
# unit's own SHARE against that unit's own measured power, and a share is
|
||||
# bounded by the same `supervised` claim at +-max_w - so a threshold at or
|
||||
# above the ceiling makes the command side unsatisfiable by construction,
|
||||
# exactly as above. Written as its own branch rather than folded into the
|
||||
# one above because the two produce different sentences and an operator
|
||||
# needs to be told WHICH watchdog they have disarmed.
|
||||
#
|
||||
# ⚠️ REFUSED EVEN AT A ROSTER OF ONE, WHERE THIS CHECK IS NOT ARMED. A
|
||||
# config that cannot work is refused when it is WRITTEN, not on the day a
|
||||
# second inverter is added - which is the day nobody is watching the startup
|
||||
# log. This is `meter_max_age_s`'s rule read the same way: the failure it
|
||||
# prevents is silent.
|
||||
unit_sign_w = _number(opts, "unit_sign_disagree_w",
|
||||
float(SIGN_OPTION_DEFAULTS["unit_sign_disagree_w"]))
|
||||
if unit_sign_w is None:
|
||||
problems.append(f"unit_sign_disagree_w "
|
||||
f"{opts.get('unit_sign_disagree_w')!r} is not a number")
|
||||
elif max_w is not None and max_w > 0 and unit_sign_w >= max_w:
|
||||
problems.append(
|
||||
f"unit_sign_disagree_w is {unit_sign_w:.0f} W but max_w is "
|
||||
f"{max_w:.0f} W, so the SAFETY-30 per-inverter sign-disagreement "
|
||||
"watchdog can never fire: no inverter is ever commanded past max_w, "
|
||||
f"and the watchdog needs a command over {unit_sign_w:.0f} W. At two "
|
||||
"inverters that is the guard which catches a unit doing the "
|
||||
"OPPOSITE of what it was told while its sibling covers for it at "
|
||||
"the meter - the case the site-level watchdog is structurally "
|
||||
f"blind to. Lower unit_sign_disagree_w below {max_w:.0f} W "
|
||||
f"({SIGN_OPTION_DEFAULTS['unit_sign_disagree_w']:.0f} W is the "
|
||||
"measured default), or raise max_w.")
|
||||
|
||||
# --- 6. a maintenance charge the ceiling can actually accommodate --------
|
||||
# ⚠️ Strictly `>`, matching the arbiter exactly. The shaping is
|
||||
# `Claim.limit(hi=-charge_w)` against `supervised`'s `lo=-max_w`, so
|
||||
|
||||