SAFETY-30: grade each inverter against its own power, and the site's total against the meter
checks / unit (pull_request) Successful in 4m38s
checks / unit (pull_request) Successful in 4m38s
THE DEFECT, in one line. `inv.sign_wd.evaluate(stood, self.grid, ...)` compared
the command THIS controller put on ONE actuator against what the WHOLE SITE is
exchanging with the network. At a roster of one those are two views of the same
thing - specs.md §6.2's identity - and that is what makes the check sound and
what earned it the best record in the safety table (NOTES.md: 93 % agreement
while healthy against 4 % during runaway, four observed episodes, zero false
positives). At two inverters they are not, and it fails in BOTH directions:
FALSE TRIP inverter A commanded -1500 W while the meter reads +1500 W is
evidence of nothing when inverter B is discharging 3000 W exactly
as told. Nothing is faulty and the highest-value check fires.
MISSED the converse, and it is worse. A unit commanded +1500 W and
MEASURED at -1500 W, beside a sibling at +1500 W, leaves P1
exactly where a healthy site leaves it. The summation destroys the
evidence and no threshold recovers it.
DEV-02 had already shipped the per-INSTANCE half - one SignWatchdog per
inverter, namespaced latch, a trip on B no longer latching A. What was left was
the COMPARISON, and it is two questions rather than one:
PER UNIT this unit's standing command against ITS OWN measured power
(`Inverter.batt`, holding register 0x0518, per-instance since
DEV-02). Conclusion: "the actuator I am driving is not doing what I
told it" - a fact about one device, so the remedy stays the per-unit
`failsafe` SET that arbiter.CLAIM_SCOPE has classified SCOPE_UNIT
from the day it was written. That entry read "the evidence is
site-wide and the remedy is not"; the first half is now simply true.
SITE the SUM of the standing commands against the meter, as a new
`sign_site` SET at P_SAFETY on the site actuator, latched under flat
`site_sign_tripped` / `site_sign_reason`. This is the 2026-08-20
fault day and NO per-unit check can see it, because every inverter
may be faithfully executing its share of a number that is itself
wrong. It stops every inverter and the banner names the site.
WHAT IT IS NOT, said here because two guards that overlap without saying so is
how a false-alarm generator gets built. It is not SAFETY-31: circulation.py
compares the units AGAINST EACH OTHER and catches them pushing power THROUGH
each other, which nets to zero at the meter and about which no single command is
evidence. This compares each unit against ITS OWN COMMAND. They overlap in
exactly one scenario - a unit reversing while its sibling pulls the other way -
and test_watchdog.py asserts on that fixture that both fire and what each
concludes. It is also not the saturation freeze, which is a MAGNITUDE test
(|command - measured| > 500 W) that shapes the loop and fires on a merely
saturated unit; this is a DIRECTION test that latches and parks one.
THE FOUR NUMBERS, RE-DERIVED AT TWO INVERTERS - one carried with a justification
and one refused. 1890 closed-loop runs on admin/goodwe's TEST-19 two-master rig
in which NOTHING is faulty, swept over the whole range config.yaml accepts for
`gain` and `slew_w`, across load reversals with write staggers and flapping
loads, and RUN AT BOTH ROSTERS so the N=1 arm is the control:
unit_sign_disagree_w 250 `saturation_w / 2`. The check gates on both sides,
opposed, so the smallest gap it can see is 500 W -
exactly where compute()'s own anti-windup test
already says the inverter is not following. It
cannot fire on a divergence the control law calls
ordinary tracking. Worst legitimate opposition at
250 W: 10.0 s; the curve is nearly flat, because a
unit's own power chases its own command.
unit_sign_disagree_s 85 8.5x that 10.0 s, 2.8x the firmware's own 30 s
link veto (inverter.LINK_STALE_S), under half the
180 s site hold.
site_sign_disagree_w 300 CARRIED. Its argument is the meter's noise floor
and the 15 W deadband; the roster touches neither,
and the campaign agrees - the gate opens in 994 of
1050 runs at two inverters and 955 of 1050 at one.
site_sign_disagree_s 325 NOT CARRIED, and this is the number the card
exists to not assume. The worst legitimate
crossing at 300 W is 110 s with one inverter and
215 s with TWO, because the command must travel a
rail that is the roster sum at a `slew_w` that is
not - reachable at gain 0.05, slew_w 50 and a
2.2 kW load reversal, all schema-legal. 180 s
would have shipped a false trip. 325 s is 1.51x
the measured worst, inside the 900 s billing
quarter and inside every episode of the fault day.
AT ONE INVERTER NOTHING CHANGES, and "nothing" is asserted rather than assumed.
The two questions are the same sentence there, so only the detector that shipped
is armed: same comparison against the meter, same 300 W / 180 s, same reason
string byte for byte, same namespaced latch and flat rollback mirror, same
`failsafe` claim, same banner, same single status row - and the site detector is
NEVER CALLED, counted on the object over twelve cycles.
VERIFIED BY BREAKING IT. Thirteen mutations on fresh per-mutation trees with no
__pycache__, mounted :ro, with the battery refusing to report at all unless the
baseline is green. Twelve red on the first pass. M4 - the site half armed at N=1
as well - SURVIVED, because the check read `disagree_since is None` and the unit
detector trips first, parks the inverter and leaves the site standing at 0 W:
the assertion ran, the sentence was true, and the data could not reach the
failure it named. Replaced with a call counter on the object; M4 is red now.
Recorded as a survivor in DECISIONS/SAFETY-30-per-unit-sign.md §5, with the
first battery's own RED BASELINE - a shared mutation directory read mid-copy -
discarded rather than reported.
RECORDED, NOT FIXED: the site comparison is defeated by a square-wave load whose
half period is about one control cycle, which holds it opposed for ~1000 s. The
N=1 control arm is what makes that interpretable - it is identical at the roster
this add-on ships, so it is a property of comparing a lagged command against a
meter and has nothing to do with the second inverter. It wants an alternation
test rather than a number, and a card of its own.
SAFETY-24's lo-only asymmetry proof re-run unchanged: 1296 combinations, 0
negative floors, `hi` +inf on every claim, every claim on the SITE actuator.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
This commit is contained in:
@@ -151,6 +151,30 @@ CLAIM_SCOPE = {
|
||||
# other went on feeding the loop. The evidence is site-level and so is the
|
||||
# remedy: stop commanding, everywhere, and say why.
|
||||
"circulation": SCOPE_SITE,
|
||||
# main.py: `Claim.set("sign_site", P_SAFETY, 0.0, "site sign disagreement")`.
|
||||
# SAFETY-30, and it is the twin of `failsafe` below rather than a duplicate
|
||||
# of it - the two exist BECAUSE the same words describe two different
|
||||
# measurements once there is more than one inverter.
|
||||
#
|
||||
# `failsafe` grades ONE unit's standing command against THAT UNIT'S OWN
|
||||
# measured power (register 0x0518). Its conclusion is "the actuator I am
|
||||
# driving is not doing what I told it", which is a fact about one device,
|
||||
# so it parks one device.
|
||||
#
|
||||
# This one grades the SUM of the standing commands against P1. Its
|
||||
# conclusion is "the site as a whole is driving the wrong way" - an inverted
|
||||
# gain, an integrator wound past the rail, a strategy on the wrong side of
|
||||
# the meter - and there is nothing per-unit about it: the quantity is a sum
|
||||
# over the roster and the offending number is the site target, which no
|
||||
# single inverter owns. Parking one unit on that evidence would leave the
|
||||
# rest of the site pushing the same way with the guard satisfied.
|
||||
#
|
||||
# ⚠️ AT N=1 IT IS NEVER FILED, and that is the identity rather than a
|
||||
# special case: with one inverter the sum of the commands IS that unit's
|
||||
# command and `failsafe` already carries exactly this trip, under the keys,
|
||||
# the banner and the claim an install has had since SAFETY-02 shipped.
|
||||
# `Controller.cycle()` does not even arm the site detector there.
|
||||
"sign_site": SCOPE_SITE,
|
||||
|
||||
# --- UNIT: about one pack, one inverter, one device -------------------
|
||||
# main.py: `Claim.limit("device", P_SAFETY, self.dev_min, self.dev_max,
|
||||
@@ -164,13 +188,22 @@ CLAIM_SCOPE = {
|
||||
# same reason, so it is scoped like `device`.
|
||||
"supervised": SCOPE_UNIT,
|
||||
# main.py: `Claim.set("failsafe", P_SAFETY, 0.0, "sign disagreement")`.
|
||||
# ⚠️ THE EVIDENCE IS SITE-WIDE AND THE REMEDY IS NOT, and that is why this
|
||||
# entry needs its reasoning written down. SAFETY-02 compares P1 - a site
|
||||
# measurement - against `standing`, THE COMMAND THIS CONTROLLER PUT ON THIS
|
||||
# ACTUATOR. What it concludes is "the unit I am driving is pushing power the
|
||||
# wrong way", and what it does is park that unit. At N>=2 the same evidence
|
||||
# cannot be attributed to a sibling nobody here commands, so a site-wide
|
||||
# remedy would be this watchdog stopping an inverter it never graded.
|
||||
# ⚠️ THE EVIDENCE IS PER-UNIT AND SO IS THE REMEDY - AND SINCE SAFETY-30 THE
|
||||
# FIRST HALF OF THAT SENTENCE IS TRUE. It used to read "the evidence is
|
||||
# site-wide and the remedy is not", because the watchdog compared THIS
|
||||
# unit's standing command against P1: a site measurement, attributed to one
|
||||
# actuator on the strength of §6.2's N=1 identity. That identity does not
|
||||
# survive a second inverter - at N>=2 the meter answers for a sibling this
|
||||
# unit's command says nothing about, in both directions (a false trip when
|
||||
# the sibling covers the meter, and a missed one when the sibling MASKS a
|
||||
# unit that really is reversed).
|
||||
#
|
||||
# So at N>=2 the comparison behind this claim is THIS unit's command against
|
||||
# THIS unit's own measured power - register 0x0518, per-instance since
|
||||
# DEV-02 - and the scope that was already right for the wrong reason is now
|
||||
# right for the right one. The site-wide half moved to `sign_site` above.
|
||||
# At N=1 the two are the same comparison and this claim is the one filed,
|
||||
# exactly as it shipped.
|
||||
"failsafe": SCOPE_UNIT,
|
||||
# main.py: `Claim.set("maintenance", P_MAINTENANCE, ...)` when the cycle owns
|
||||
# the setpoint, and `Claim.limit("maintenance", P_MAINT_SHAPE, hi=...)` when
|
||||
|
||||
+317
-14
@@ -62,7 +62,10 @@ from .static_tariff import resolve_tariff, static_status
|
||||
from .tariff import PeakStore, PeakTracker
|
||||
from .store import migrate_unit_keys
|
||||
from .validate import ConfigRefused, refuse, validate_startup_config
|
||||
from .watchdog import SignWatchdogConfig, loop_is_following
|
||||
from .watchdog import (
|
||||
AGAINST_METER, AGAINST_OWN_POWER, SIGN_OPTION_DEFAULTS,
|
||||
SignWatchdog, SignWatchdogConfig, loop_is_following,
|
||||
)
|
||||
from . import web
|
||||
|
||||
OPTIONS_PATH = "/data/options.json"
|
||||
@@ -171,10 +174,42 @@ class Controller:
|
||||
# first or every existing tripped install comes up ARMED, into the
|
||||
# fault, with a green banner - which is the exact failure the latch was
|
||||
# persisted to prevent, rebuilt by a key rename.
|
||||
sign_cfg = SignWatchdogConfig(
|
||||
# SAFETY-02's pair, and since SAFETY-30 it is THE SITE COMPARISON's
|
||||
# pair - which at the shipped roster of one is the same thing under a
|
||||
# more careful name. It is what `Inverter.sign_wd` is armed with at N=1,
|
||||
# byte for byte, and what the site detector is armed with at N>=2.
|
||||
self.sign_cfg = sign_cfg = SignWatchdogConfig(
|
||||
min_w=float(opts.get("sign_disagree_w", 300)),
|
||||
hold_s=float(opts.get("sign_disagree_s", 180)),
|
||||
)
|
||||
# SAFETY-30. THE PER-UNIT COMPARISON'S OWN PAIR, RE-DERIVED AT TWO
|
||||
# INVERTERS AND NOT CARRIED ACROSS. `sign_disagree_w` / `sign_disagree_s`
|
||||
# were measured on two SINGLE-INVERTER bus captures against a command
|
||||
# opposed to THE METER; this comparison is a command against ONE UNIT'S
|
||||
# OWN POWER, where the magnitudes, the transient and the worst
|
||||
# legitimate episode are all different quantities. watchdog.py's
|
||||
# SIGN_OPTION_DEFAULTS carries the campaign that produced these, and
|
||||
# DECISIONS/SAFETY-30-per-unit-sign.md carries the tables.
|
||||
self.unit_sign_cfg = SignWatchdogConfig(
|
||||
min_w=float(opts.get("unit_sign_disagree_w",
|
||||
SIGN_OPTION_DEFAULTS["unit_sign_disagree_w"])),
|
||||
hold_s=float(opts.get("unit_sign_disagree_s",
|
||||
SIGN_OPTION_DEFAULTS["unit_sign_disagree_s"])),
|
||||
)
|
||||
# SAFETY-30. THE SITE COMPARISON'S OWN PAIR, USED ONLY AT N>=2. The
|
||||
# threshold is the shipped 300 W - carried, because the argument behind
|
||||
# it is about the meter's noise floor and the deadband, neither of which
|
||||
# the roster touches - and the WINDOW is not, because the transient it
|
||||
# rejects is the loop crossing zero at `slew_w` per cycle across a rail
|
||||
# that IS the roster sum. Measured at both rosters on the same stimuli:
|
||||
# 110 s at one inverter, 215 s at two, against a 180 s hold. See
|
||||
# watchdog.SIGN_OPTION_DEFAULTS.
|
||||
self.site_sign_cfg = SignWatchdogConfig(
|
||||
min_w=float(opts.get("site_sign_disagree_w",
|
||||
SIGN_OPTION_DEFAULTS["site_sign_disagree_w"])),
|
||||
hold_s=float(opts.get("site_sign_disagree_s",
|
||||
SIGN_OPTION_DEFAULTS["site_sign_disagree_s"])),
|
||||
)
|
||||
self.store_migration = migrate_unit_keys(store, UNIT_A)
|
||||
self.inverters = build_roster(opts, store, sign_cfg)
|
||||
|
||||
@@ -241,6 +276,45 @@ class Controller:
|
||||
"opposed the meter.", inv.name,
|
||||
inv.sign_wd.reason or "(reason not recorded)")
|
||||
|
||||
# --- SAFETY-30: THE SITE HALF OF THE SIGN CHECK ----------------------
|
||||
# ⚠️ ONE PER SITE, BESIDE THE ONE PER INVERTER, AND ARMED ONLY AT N>=2.
|
||||
# The per-unit watchdogs above ask "is THIS actuator doing what I told
|
||||
# it", graded on that unit's own measured power. This one asks "is the
|
||||
# SITE driving the wrong way", graded on the SUM of the standing
|
||||
# commands against P1 - the comparison SAFETY-02 shipped, re-scoped to
|
||||
# the quantity it was always actually about.
|
||||
#
|
||||
# ⚠️ AT A ROSTER OF ONE IT IS CONSTRUCTED AND NEVER EVALUATED, and that
|
||||
# is the whole compatibility promise of this card rather than an
|
||||
# oversight. With one inverter the sum of the commands IS that
|
||||
# inverter's command, so arming this would be arming a duplicate of
|
||||
# `inverters[0].sign_wd`: two latches for one fault, two banners, and a
|
||||
# false-positive record measured on ONE comparison being spent twice.
|
||||
# `cycle()` is where that is enforced and says so at the line.
|
||||
#
|
||||
# Restored from the store like SAFETY-02's and SAFETY-31's latches, for
|
||||
# the reason store.py gives: "restart the add-on" is the first thing an
|
||||
# operator looking at a FAILSAFE banner tries, and a latch held only in
|
||||
# memory brings the controller back armed, into the fault, unattended.
|
||||
# FLAT keys, not namespaced - store.py carries that argument too.
|
||||
self.site_sign_wd = SignWatchdog(
|
||||
self.site_sign_cfg,
|
||||
tripped=bool(store.data.get("site_sign_tripped", False)),
|
||||
reason=str(store.data.get("site_sign_reason", "") or ""))
|
||||
if self.site_sign_wd.tripped:
|
||||
_LOG.error(
|
||||
"SAFETY-30 (site) was TRIPPED before this restart and stays "
|
||||
"tripped: %s. Every inverter is held at 0 W. Restarting does "
|
||||
"not clear this - start control from the UI once you know why "
|
||||
"the site's total command opposed the meter.",
|
||||
self.site_sign_wd.reason or "(reason not recorded)")
|
||||
# And the per-unit detectors are told which question they are asking,
|
||||
# here as well as in `cycle()`. `checks()` and the status page read
|
||||
# `inv.sign_wd.cfg` and can be called before the first cycle has run, so
|
||||
# a roster of two would otherwise advertise the site thresholds on a
|
||||
# detector that is about to be graded against a unit's own power.
|
||||
self._arm_sign_watchdogs()
|
||||
|
||||
# SAFETY-18. The frozen-but-fresh meter detector - see freeze.py for why
|
||||
# it is a conjunction and not an `unchanged_s` threshold, and for the
|
||||
# measurements behind the default.
|
||||
@@ -692,6 +766,45 @@ class Controller:
|
||||
def sign_wd(self):
|
||||
return self._only().sign_wd
|
||||
|
||||
# -- SAFETY-30: which comparison each sign detector is making -------------
|
||||
def _arm_sign_watchdogs(self) -> None:
|
||||
"""Tell every sign detector which of SAFETY-30's two questions it asks.
|
||||
|
||||
⚠️ A PURE FUNCTION OF `len(self.inverters)`, AND THE ONLY PLACE THE
|
||||
ROSTER DECIDES ANYTHING ABOUT THIS CHECK. Written as one method rather
|
||||
than as a conditional at the two call sites for `loop_is_following()`'s
|
||||
reason: the arrangement that does not keep two things in step is the one
|
||||
where they are written down twice.
|
||||
|
||||
AT ONE INVERTER - §6.2's identity, and the whole of AC 8. The single
|
||||
unit's detector is armed against THE METER with the shipped
|
||||
`sign_disagree_w` / `sign_disagree_s`, which is what it has always been
|
||||
armed against, and the site detector is not armed at all. A one-inverter
|
||||
install therefore makes the same comparison, at the same thresholds,
|
||||
writes the same reason string, latches under the same keys and files the
|
||||
same `failsafe` claim as it did before this card.
|
||||
|
||||
AT TWO OR MORE - the identity is gone and the meter stops being a view
|
||||
of any one actuator. Each unit's detector is armed against ITS OWN
|
||||
MEASURED POWER (`Inverter.batt`, register 0x0518) under the re-derived
|
||||
per-unit pair, and the site detector is armed against the meter under
|
||||
the site pair. Two questions, two remedies, two latches.
|
||||
|
||||
⚠️ CALLED AGAIN AT THE TOP OF EVERY `cycle()`, not only from
|
||||
`__init__`. The roster is re-read every cycle for liveness and for the
|
||||
allocation, and this repository's two-inverter fixtures append an
|
||||
`Inverter` AFTER the Controller is constructed - a detector frozen at
|
||||
construction would then be graded against the meter at a roster of two,
|
||||
which is the defect this card exists to remove, wearing a fixture's
|
||||
name. `arm()` touches no timer and no latch, so calling it every cycle
|
||||
cannot disturb an episode in progress.
|
||||
"""
|
||||
one = len(self.inverters) <= 1
|
||||
for inv in self.inverters:
|
||||
inv.sign_wd.arm(self.sign_cfg if one else self.unit_sign_cfg,
|
||||
AGAINST_METER if one else AGAINST_OWN_POWER)
|
||||
self.site_sign_wd.arm(self.site_sign_cfg, AGAINST_METER)
|
||||
|
||||
# -- the site aggregates, each one named for the question it answers ------
|
||||
# ⚠️ THESE ARE NOT "THE SCALARS WITH A SUM IN FRONT". Each one picks a
|
||||
# DIFFERENT reduction, because the questions are different, and getting the
|
||||
@@ -1219,17 +1332,44 @@ class Controller:
|
||||
# case where the last write was REJECTED - the inverter is then still
|
||||
# latched on `last_write`, which is exactly what `last_write` holds).
|
||||
# ⚠️ ONE WATCHDOG PER INVERTER, EVALUATED ON THAT INVERTER'S OWN
|
||||
# STANDING COMMAND. The meter is site-wide - there is one P1 - but what
|
||||
# the watchdog concludes is "THE UNIT I AM DRIVING is pushing power the
|
||||
# wrong way", and that evidence cannot be pinned on a sibling this
|
||||
# controller commanded differently. `inv.target` is that unit's share
|
||||
# from the last resolution, which at N=1 is the site target itself.
|
||||
# STANDING COMMAND. What the watchdog concludes is "THE UNIT I AM
|
||||
# DRIVING is pushing power the wrong way", and that evidence cannot be
|
||||
# pinned on a sibling this controller commanded differently.
|
||||
# `inv.target` is that unit's share from the last resolution, which at
|
||||
# N=1 is the site target itself.
|
||||
#
|
||||
# ⚠️ SAFETY-30: AND WHAT IT IS COMPARED AGAINST IS DECIDED BY THE ROSTER.
|
||||
# This block used to hand every unit's detector `self.grid`. There is
|
||||
# ONE P1, so at N>=2 that compares a number this controller put on ONE
|
||||
# actuator against a measurement that answers for ALL of them, and it is
|
||||
# wrong in both directions:
|
||||
#
|
||||
# FALSE TRIP inverter A commanded -1500 W while the meter reads
|
||||
# +1500 W is evidence of nothing when inverter B is
|
||||
# discharging 3000 W exactly as instructed. Nothing is
|
||||
# faulty and the highest-value check in the safety table
|
||||
# fires - on a record of zero false positives.
|
||||
# MISSED the converse, and it is worse. A unit commanded +1500 W
|
||||
# and MEASURED at -1500 W, beside a sibling at +1500 W,
|
||||
# leaves P1 exactly where a healthy site leaves it. The
|
||||
# sum destroys the evidence; no threshold recovers it.
|
||||
#
|
||||
# So at N>=2 each unit is graded against ITS OWN measured power -
|
||||
# `inv.batt`, register 0x0518, per-instance since DEV-02 - which is the
|
||||
# only instrument that can answer "is THIS actuator doing what I told
|
||||
# it". At N=1 §6.2's identity holds, the meter IS the view of that one
|
||||
# unit, and the comparison stays the meter, byte for byte. The site's
|
||||
# own question has not gone away; it is asked below, once, of the sum.
|
||||
# `_arm_sign_watchdogs()` states the choice and its docstring argues it.
|
||||
self._arm_sign_watchdogs()
|
||||
n_units = len(self.inverters)
|
||||
standing = {}
|
||||
for inv in self.inverters:
|
||||
was_tripped = inv.sign_wd.tripped
|
||||
stood = inv.last_write if inv.last_write is not None else inv.target
|
||||
standing[inv.name] = stood
|
||||
if inv.sign_wd.evaluate(stood, self.grid, self.following, now) \
|
||||
against = self.grid if n_units <= 1 else inv.batt
|
||||
if inv.sign_wd.evaluate(stood, against, self.following, now) \
|
||||
and not was_tripped:
|
||||
# ⚠️ REASON FIRST, FLAG SECOND, and each `set` writes the file.
|
||||
# The ordering is the whole atomicity story: a crash between the
|
||||
@@ -1270,6 +1410,50 @@ class Controller:
|
||||
# share of it. At the shipped roster of one the two are the same number.
|
||||
site_standing = float(sum(standing.values()))
|
||||
|
||||
# --- SAFETY-30: THE SITE HALF OF THE SIGN CHECK ----------------------
|
||||
# The comparison SAFETY-02 shipped, asked of the quantity it was always
|
||||
# about: the TOTAL this controller has standing on the wire, against the
|
||||
# meter that total is answerable for. What it catches is a fault no
|
||||
# per-unit check can see, because every unit is faithfully executing its
|
||||
# share of a site target that is itself pointing the wrong way - an
|
||||
# inverted gain, an integrator wound past the rail, a strategy on the
|
||||
# wrong side of the meter. That is the 2026-08-20 fault day, and it is
|
||||
# the reason the site question survives rather than being replaced.
|
||||
#
|
||||
# ⚠️ ONLY AT N>=2, AND THIS BRANCH IS AC 8. At one inverter the sum of
|
||||
# the commands IS that inverter's command and the loop above has already
|
||||
# made exactly this comparison, at exactly these thresholds, on the
|
||||
# detector whose latch, store keys, claim and banner an install has had
|
||||
# since SAFETY-02 shipped. Arming this as well would be two latches for
|
||||
# one fault, two banners, and the same false-positive record spent
|
||||
# twice. A shipped install does not reach this block at all.
|
||||
if n_units > 1:
|
||||
was_site = self.site_sign_wd.tripped
|
||||
if self.site_sign_wd.evaluate(site_standing, self.grid,
|
||||
self.following, now) and not was_site:
|
||||
# REASON FIRST, FLAG SECOND - the same atomicity ordering the
|
||||
# per-unit trip uses above and SAFETY-31 uses below: a crash
|
||||
# between the two must not persist a latch with no explanation
|
||||
# for the operator who has to decide about clearing it.
|
||||
#
|
||||
# ⚠️ AND THE KEYS ARE FLAT, NOT NAMESPACED, AND NOT THE
|
||||
# PRE-DEV-02 PAIR EITHER. `sign_tripped` / `sign_reason` are the
|
||||
# ROLLBACK VIEW of a UNIT latch (store.py rule 2) and mirroring
|
||||
# a site trip onto them would hand a downgraded add-on - which
|
||||
# drives exactly one actuator - a latch taken on evidence about
|
||||
# a roster it cannot have. `site_sign_*` is its own pair, for
|
||||
# the same reason `circ_*` is.
|
||||
self.store.set("site_sign_reason", self.site_sign_wd.reason)
|
||||
self.store.set("site_sign_tripped", True)
|
||||
self.log_event("FAILSAFE site: " + self.site_sign_wd.reason)
|
||||
_LOG.error("SAFETY-30 TRIPPED at the SITE - %s. That is the "
|
||||
"SUM of every standing command opposing the meter, "
|
||||
"which no single inverter is answerable for. "
|
||||
"Commanding 0 W on every inverter and holding it "
|
||||
"until control is started again. This survives an "
|
||||
"add-on restart; restarting will not clear it.",
|
||||
self.site_sign_wd.reason)
|
||||
|
||||
# --- SAFETY-31, AND IT RUNS BESIDE SAFETY-02 FOR THE SAME REASON -----
|
||||
# Evaluated EVERY cycle, unconditionally, above the "inputs missing but
|
||||
# not yet stale" hold below. A run of held cycles would otherwise leave
|
||||
@@ -1309,8 +1493,14 @@ class Controller:
|
||||
# list below, because its `failsafe` SET is what parks it. One tripped
|
||||
# unit therefore takes the whole roster past the hold, which is the
|
||||
# conservative direction: every other unit's claims are re-filed too.
|
||||
# ⚠️ AND SAFETY-30's SITE LATCH TAKES THE ROSTER PAST THE HOLD TOO, for
|
||||
# the same reason: its `sign_site` SET is what parks every inverter, and
|
||||
# a latched site that returned early here would leave each unit's last
|
||||
# share standing for the heartbeat to re-emit - i.e. the trip would stop
|
||||
# acting the moment a poll was missed.
|
||||
if not self.inputs_ok and not any(i.sign_wd.tripped
|
||||
for i in self.inverters):
|
||||
for i in self.inverters) \
|
||||
and not (n_units > 1 and self.site_sign_wd.tripped):
|
||||
bad_for = (now - self.inputs_bad_since).total_seconds() if self.inputs_bad_since else 0.0
|
||||
if bad_for < stale_after:
|
||||
# A single missed poll is not a fault. Hold, keep the heartbeat
|
||||
@@ -1364,6 +1554,30 @@ class Controller:
|
||||
"sign disagreement",
|
||||
actuator=self.actuator_of("failsafe", inv)))
|
||||
|
||||
# --- SAFETY-30: THE SITE SIGN TRIP, AND IT IS A SITE SET ------------
|
||||
# ⚠️ THE TWIN OF THE LOOP ABOVE, NOT A DUPLICATE OF IT. That loop files
|
||||
# one `failsafe` per unit on the evidence of THAT unit's own measured
|
||||
# power, and parks that unit. This files ONE claim on the SITE, because
|
||||
# what tripped is the SUM of every standing command against the meter -
|
||||
# a fact about the grid connection, whose offending number is the site
|
||||
# target and which no single inverter owns. Parking one unit on it would
|
||||
# leave the rest of the roster pushing the same way with the guard
|
||||
# satisfied. See arbiter.CLAIM_SCOPE, which classifies `sign_site` and
|
||||
# `failsafe` side by side and says why they differ.
|
||||
#
|
||||
# ⚠️ AND THE `n_units > 1` GUARD IS NOT REDUNDANT, EVEN THOUGH `cycle()`
|
||||
# never arms this detector at a roster of one. The latch is RESTORED
|
||||
# FROM THE STORE, so an install that ran with two inverters, tripped,
|
||||
# and was then reconfigured back to one would come up with
|
||||
# `site_sign_tripped: true` and would otherwise file a claim on evidence
|
||||
# about a roster it no longer has. Guarded, that install comes up
|
||||
# driving - which is right: the fault it latched on is not a statement
|
||||
# about the site it is now.
|
||||
if n_units > 1 and self.site_sign_wd.tripped:
|
||||
claims.append(Claim.set("sign_site", P_SAFETY, 0.0,
|
||||
"site sign disagreement",
|
||||
actuator=self.actuator_of("sign_site")))
|
||||
|
||||
# --- SAFETY-31: WHAT "ACTED ON" MEANS, AND WHAT IT HONESTLY CANNOT --
|
||||
# ⚠️ A SITE SET AT P_SAFETY: STOP COMMANDING, EVERYWHERE. Read the next
|
||||
# paragraph before changing it, because the obvious objection is right
|
||||
@@ -2578,8 +2792,15 @@ class Controller:
|
||||
# here would be a surface to migrate later. This sensor is already
|
||||
# discovered, already on every dashboard, and "failsafe" is
|
||||
# additive to its vocabulary rather than a change to it.
|
||||
# SAFETY-30 adds the site sign latch to the same vocabulary, for
|
||||
# the reason the note above gives: "failsafe" is additive to a
|
||||
# sensor that already exists and is already on every dashboard, and
|
||||
# a P_SAFETY stop that did not reach it would be a site at 0 W
|
||||
# reporting "running".
|
||||
"status": ("failsafe" if any(i.sign_wd.tripped
|
||||
for i in self.inverters)
|
||||
or (self.site_sign_wd.tripped
|
||||
and len(self.inverters) > 1)
|
||||
or self.circ_wd.tripped
|
||||
else "running" if self.auto else "stopped"),
|
||||
# SAFETY-31. ⚠️ MEASURED, not the allocation record - see
|
||||
@@ -2906,24 +3127,70 @@ class Controller:
|
||||
# and a trip on B leaves A commanding. A single row would have to pick
|
||||
# one of them to describe, and the honest answer at a roster of two is
|
||||
# both. At a roster of one the wording is unchanged.
|
||||
# ⚠️ AND SINCE SAFETY-30 THE ROW SAYS WHAT THE UNIT WAS COMPARED
|
||||
# AGAINST, because at a roster of two that is no longer the meter and a
|
||||
# row that still said "the command opposed the meter" would send an
|
||||
# operator to look at P1 for a fault that is visible only on one
|
||||
# inverter's own power sensor. `sign_wd.against` is the same string the
|
||||
# trip sentence uses, so the two cannot drift apart.
|
||||
for inv in self.inverters:
|
||||
tag = "" if len(self.inverters) == 1 else f" [{inv.name}]"
|
||||
# ⚠️ ADDED ONLY WHEN THERE IS SOMETHING TO DISAMBIGUATE. At the
|
||||
# shipped roster of one the two sentences below are the ones that
|
||||
# have always been on the page, word for word - AC 8 is about what
|
||||
# an operator sees as much as about what the detector computes, and
|
||||
# "opposed a meter reading" would be a gratuitous change to a line
|
||||
# somebody has learned to recognise. At N>=2 the noun is load-
|
||||
# bearing: the row would otherwise send them to look at P1 for a
|
||||
# fault that is visible only on one inverter's own power sensor.
|
||||
vs = ("" if len(self.inverters) == 1
|
||||
else f" against {inv.sign_wd.against}")
|
||||
if inv.sign_wd.tripped:
|
||||
what = ("the meter" if len(self.inverters) == 1
|
||||
else inv.sign_wd.against)
|
||||
out.append({"ok": False, "warn": False,
|
||||
"text": f"SIGN-DISAGREEMENT FAILSAFE{tag} - "
|
||||
+ inv.sign_wd.reason
|
||||
+ ". The inverter is held at 0 W. Find out why the "
|
||||
"command opposed the meter before starting control "
|
||||
+ f". The inverter is held at 0 W. Find out why the "
|
||||
f"command opposed {what} before starting control "
|
||||
"again; starting clears this. Restarting the "
|
||||
"add-on does NOT clear it."})
|
||||
else:
|
||||
held = inv.sign_wd.held_s(datetime.now(timezone.utc))
|
||||
out.append({"ok": True, "warn": False,
|
||||
"text": f"sign watchdog{tag}: armed (trips after "
|
||||
"text": f"sign watchdog{tag}: armed{vs} (trips after "
|
||||
f"{inv.sign_wd.cfg.hold_s:.0f} s opposed, both over "
|
||||
f"{inv.sign_wd.cfg.min_w:.0f} W)"
|
||||
+ (f" - opposed for {held:.0f} s now" if held else "")})
|
||||
|
||||
# --- SAFETY-30: the SITE row -----------------------------------------
|
||||
# ⚠️ ONLY AT N>=2, and the absence at N=1 is the honest report rather
|
||||
# than a missing row. With one inverter the site comparison and the row
|
||||
# above are the same sentence about the same actuator; printing it twice
|
||||
# would advertise two guards where there is one, which is how an
|
||||
# operator learns to skim the list.
|
||||
if len(self.inverters) > 1:
|
||||
if self.site_sign_wd.tripped:
|
||||
out.append({"ok": False, "warn": False,
|
||||
"text": "SITE SIGN-DISAGREEMENT FAILSAFE - "
|
||||
+ self.site_sign_wd.reason
|
||||
+ ". EVERY inverter is held at 0 W. This is the "
|
||||
"SUM of the commands against the meter, so it is "
|
||||
"not one inverter's fault to find - look at the "
|
||||
"loop, the integrator and whatever won the "
|
||||
"arbitration. Starting control clears this; "
|
||||
"restarting the add-on does NOT."})
|
||||
else:
|
||||
_sheld = self.site_sign_wd.held_s(datetime.now(timezone.utc))
|
||||
out.append({"ok": True, "warn": False,
|
||||
"text": f"site sign watchdog: armed against the sum of "
|
||||
f"the commands (trips after "
|
||||
f"{self.site_sign_wd.cfg.hold_s:.0f} s opposed, "
|
||||
f"both over "
|
||||
f"{self.site_sign_wd.cfg.min_w:.0f} W)"
|
||||
+ (f" - opposed for {_sheld:.0f} s now"
|
||||
if _sheld else "")})
|
||||
|
||||
# --- SAFETY-31 -----------------------------------------------------
|
||||
# ⚠️ SITE-LEVEL, WHERE THE ROWS ABOVE ARE PER-INVERTER, and the row says
|
||||
# so. There is one circulating figure for the site; naming an inverter
|
||||
@@ -2980,10 +3247,28 @@ class Controller:
|
||||
level, banner = "bad", ("CIRCULATING POWER — the inverters were "
|
||||
"pushing against each other. Site held at "
|
||||
"0 W.")
|
||||
elif self.site_sign_wd.tripped and len(self.inverters) > 1:
|
||||
# SAFETY-30's site half, ABOVE the per-unit rows below and below
|
||||
# circulating power above, and the ordering is the same argument
|
||||
# both times: the banner carries one sentence, so it carries the one
|
||||
# that says the widest true thing. A site sign trip means EVERY
|
||||
# inverter is parked and the fault is in what the site was asking
|
||||
# for, not in one device - naming a unit here would send an operator
|
||||
# to swap the wrong box.
|
||||
level, banner = "bad", ("FAILSAFE — the site's total command "
|
||||
"opposed the meter. Every inverter held at "
|
||||
"0 W.")
|
||||
elif any(i.sign_wd.tripped for i in self.inverters):
|
||||
# Outranks "NOT READY": nothing is missing, something went wrong.
|
||||
level, banner = "bad", ("FAILSAFE — the command opposed the meter. "
|
||||
"Inverter held at 0 W.")
|
||||
# ⚠️ THE SENTENCE IS UNCHANGED AT A ROSTER OF ONE, where "the meter"
|
||||
# is what the unit was graded against. At N>=2 it is that unit's own
|
||||
# power, so the banner says so - see checks() on why the noun is
|
||||
# load-bearing rather than cosmetic.
|
||||
level, banner = "bad", (
|
||||
"FAILSAFE — the command opposed the meter. "
|
||||
"Inverter held at 0 W." if len(self.inverters) == 1 else
|
||||
"FAILSAFE — an inverter's command opposed its own measured "
|
||||
"power. That inverter held at 0 W.")
|
||||
elif bad:
|
||||
# ⚠️ `banner` IF THE ROW OFFERS ONE, `text` OTHERWISE. A row may
|
||||
# need to say more to an operator reading the checks list than fits
|
||||
@@ -3088,6 +3373,24 @@ class Controller:
|
||||
# unit in particular.
|
||||
self.store.set("sign_tripped", False)
|
||||
self.store.set("sign_reason", "")
|
||||
# SAFETY-30's SITE latch, cleared by the SAME press and for the
|
||||
# same reason the per-unit ones are: the condition always goes
|
||||
# away on its own, because the trip commands 0 W everywhere and
|
||||
# a site commanding zero cannot oppose anything. Only a human
|
||||
# who has read the banner can say the site is clear.
|
||||
#
|
||||
# ⚠️ UNCONDITIONAL, LIKE THE FLAT PAIR ABOVE, AND NOT GUARDED ON
|
||||
# THE ROSTER. An install that ran with two inverters, tripped,
|
||||
# and was then reconfigured back to one would otherwise carry
|
||||
# `site_sign_tripped: true` in its file forever, with no roster
|
||||
# that can reach the code which clears it - and would re-arm the
|
||||
# moment a second inverter was configured again.
|
||||
if self.site_sign_wd.tripped:
|
||||
self.log_event("site sign-disagreement failsafe cleared "
|
||||
"by operator")
|
||||
self.site_sign_wd.reset()
|
||||
self.store.set("site_sign_tripped", False)
|
||||
self.store.set("site_sign_reason", "")
|
||||
# SAFETY-31, cleared by the SAME press and for the same reason:
|
||||
# the condition always goes away on its own, because the trip
|
||||
# commands 0 W everywhere and two inverters at zero cannot
|
||||
|
||||
@@ -71,6 +71,24 @@ _LOG = logging.getLogger("goodwe.store")
|
||||
# the card is gone while the fault runs on - exactly how the 2026-09-02 outage
|
||||
# went unseen for 6 h 25 m with the detector correct throughout. main.py
|
||||
# re-raises the notification from this key on every start.
|
||||
#
|
||||
# ⚠️ AND SAFETY-30's PAIR IS FLAT FOR THE SAME REASON SAFETY-31's IS, WHICH IS
|
||||
# NOT THE SAME REASON THE ONES ABOVE ARE NAMESPACED. `site_sign_tripped` /
|
||||
# `site_sign_reason` hold the SITE sign-disagreement latch: the SUM of every
|
||||
# standing command opposed the meter, continuously. That is a statement about
|
||||
# the grid connection - the offending number is the site target, which no single
|
||||
# inverter owns - so there is no unit to hang it on, and hanging it on one would
|
||||
# let an operator clear "inverter B's half" of a fault that has no halves.
|
||||
# `unit/<name>/sign_tripped` above stays what it always was and now means what
|
||||
# it says: THAT unit's own command against THAT unit's own measured power.
|
||||
#
|
||||
# ⚠️ AND THEY ARE NOT IN `LEGACY_UNIT_KEYS`, MUST NEVER BE, AND ARE NOT WRITTEN
|
||||
# AT A ROSTER OF ONE AT ALL. At N=1 the site comparison and the unit comparison
|
||||
# are the same sentence and `Controller.cycle()` arms only the per-unit
|
||||
# detector, so a one-inverter install's state file is byte-identical to what it
|
||||
# was before this card - these two keys sit at their defaults and nothing reads
|
||||
# them. A rollback therefore finds exactly the flat `sign_tripped` mirror it
|
||||
# always found.
|
||||
DEFAULTS = {
|
||||
"phase": "idle",
|
||||
"phase_started": None,
|
||||
@@ -80,6 +98,8 @@ DEFAULTS = {
|
||||
"sign_reason": "",
|
||||
"circ_tripped": False,
|
||||
"circ_reason": "",
|
||||
"site_sign_tripped": False,
|
||||
"site_sign_reason": "",
|
||||
}
|
||||
|
||||
# --------------------------------------------------------------------------- #
|
||||
|
||||
@@ -74,7 +74,8 @@ NOT READY banner already names the problem, (b) does not apply.
|
||||
was overruled. That firmware file's own comment says a lower bound on this
|
||||
"belongs in CFG-01, not here" - so here it is.
|
||||
|
||||
5. `sign_disagree_w` at or above `max_w`. [(a)]
|
||||
5. `sign_disagree_w` - or SAFETY-30's `unit_sign_disagree_w` - at or above
|
||||
`max_w`. [(a)]
|
||||
The arbiter's `supervised` limit bounds every command to +-max_w, and
|
||||
SAFETY-02's predicate needs `abs(command) > sign_disagree_w`. Set the
|
||||
threshold at or above the ceiling and the command side of the comparison
|
||||
@@ -207,6 +208,7 @@ from .p1 import is_enabled, validate_meter_options
|
||||
from .peakguard import PEAK_OPTION_DEFAULTS
|
||||
from .price import PRICE_OPTION_DEFAULTS, PROVIDERS
|
||||
from .static_tariff import ProfileInvalid, parse_static_profile
|
||||
from .watchdog import SIGN_OPTION_DEFAULTS
|
||||
|
||||
_LOG = logging.getLogger("goodwe.config")
|
||||
|
||||
@@ -458,6 +460,38 @@ def validate_startup_config(opts: dict, dev_min=None, dev_max=None) -> list[str]
|
||||
f"sign_disagree_w below {max_w:.0f} W (300 W is the measured "
|
||||
"default), or raise max_w.")
|
||||
|
||||
# ⚠️ AND THE SAME RULE FOR SAFETY-30's PER-UNIT THRESHOLD, WHICH IS A
|
||||
# SEPARATE COMPARISON AND THEREFORE A SEPARATE WAY TO DISARM. It grades a
|
||||
# unit's own SHARE against that unit's own measured power, and a share is
|
||||
# bounded by the same `supervised` claim at +-max_w - so a threshold at or
|
||||
# above the ceiling makes the command side unsatisfiable by construction,
|
||||
# exactly as above. Written as its own branch rather than folded into the
|
||||
# one above because the two produce different sentences and an operator
|
||||
# needs to be told WHICH watchdog they have disarmed.
|
||||
#
|
||||
# ⚠️ REFUSED EVEN AT A ROSTER OF ONE, WHERE THIS CHECK IS NOT ARMED. A
|
||||
# config that cannot work is refused when it is WRITTEN, not on the day a
|
||||
# second inverter is added - which is the day nobody is watching the startup
|
||||
# log. This is `meter_max_age_s`'s rule read the same way: the failure it
|
||||
# prevents is silent.
|
||||
unit_sign_w = _number(opts, "unit_sign_disagree_w",
|
||||
float(SIGN_OPTION_DEFAULTS["unit_sign_disagree_w"]))
|
||||
if unit_sign_w is None:
|
||||
problems.append(f"unit_sign_disagree_w "
|
||||
f"{opts.get('unit_sign_disagree_w')!r} is not a number")
|
||||
elif max_w is not None and max_w > 0 and unit_sign_w >= max_w:
|
||||
problems.append(
|
||||
f"unit_sign_disagree_w is {unit_sign_w:.0f} W but max_w is "
|
||||
f"{max_w:.0f} W, so the SAFETY-30 per-inverter sign-disagreement "
|
||||
"watchdog can never fire: no inverter is ever commanded past max_w, "
|
||||
f"and the watchdog needs a command over {unit_sign_w:.0f} W. At two "
|
||||
"inverters that is the guard which catches a unit doing the "
|
||||
"OPPOSITE of what it was told while its sibling covers for it at "
|
||||
"the meter - the case the site-level watchdog is structurally "
|
||||
f"blind to. Lower unit_sign_disagree_w below {max_w:.0f} W "
|
||||
f"({SIGN_OPTION_DEFAULTS['unit_sign_disagree_w']:.0f} W is the "
|
||||
"measured default), or raise max_w.")
|
||||
|
||||
# --- 6. a maintenance charge the ceiling can actually accommodate --------
|
||||
# ⚠️ Strictly `>`, matching the arbiter exactly. The shaping is
|
||||
# `Claim.limit(hi=-charge_w)` against `supervised`'s `lo=-max_w`, so
|
||||
|
||||
@@ -164,11 +164,106 @@ saturation freeze's question (|command - the battery's actual power| > 500 W,
|
||||
NOTES.md §4.7 row 4), and the two checks are complementary rather than
|
||||
overlapping. Neither substitutes for the other.
|
||||
|
||||
⚠️ THAT PARAGRAPH IS ABOUT THE COMMAND-VERSUS-METER COMPARISON, AND SINCE
|
||||
SAFETY-30 THAT IS NOT THE ONLY ONE THIS MODULE DRIVES. At a roster of two or
|
||||
more each unit is ALSO graded against its own measured power, which is exactly
|
||||
the comparison the paragraph says nothing here makes - see the SAFETY-30 section
|
||||
below, which says what that does and does not take away from the freeze. At the
|
||||
shipped roster of one the paragraph stands unchanged, word for word: the site
|
||||
comparison is the only detector armed and the freeze is still the whole answer.
|
||||
|
||||
Nor does it see a sign inversion introduced DOWNSTREAM of this add-on - in the
|
||||
firmware, on the wire, or in a future driver. Our view stays self-consistent and
|
||||
this stays silent. That is a wire-versus-intent problem and it belongs to the
|
||||
witness, which is the only vantage point that sees both.
|
||||
|
||||
------------------------------------------------------------------------------
|
||||
SAFETY-30 - AT TWO INVERTERS THIS IS TWO QUESTIONS, NOT ONE
|
||||
|
||||
Everything above was written at a roster of ONE, and at N=1 it is right for a
|
||||
reason that stops being true at N=2. `commanded_w` is what THIS controller put
|
||||
on THIS actuator. `grid_w` is what the WHOLE SITE is exchanging with the
|
||||
network. At one inverter those are two views of one thing - §6.2's identity -
|
||||
which is what makes comparing them sound. At two they are not:
|
||||
|
||||
* A FALSE TRIP THE COMPARISON CANNOT AVOID. "Inverter A commanded -1500 W
|
||||
while the meter reads +1500 W" is evidence of nothing at N=2: inverter B may
|
||||
be discharging 3000 W and doing exactly what it was told. No fault anywhere,
|
||||
and the check NOTES.md calls the highest-value entry in the safety table -
|
||||
93 % agreement while healthy against 4 % during runaway, four episodes, zero
|
||||
false positives - fires.
|
||||
* THE CONVERSE, WHICH IS WORSE. A unit genuinely driving the wrong way is
|
||||
MASKED, because the site figure NETS. Commanded +1500 W, measured -1500 W,
|
||||
beside a sibling measured at +1500 W: the meter sits exactly where a healthy
|
||||
site leaves it. This is not a threshold that is set too high - the
|
||||
information is destroyed by the summation, and no tuning recovers it.
|
||||
|
||||
So the one comparison becomes two, each asked of the evidence that can answer
|
||||
it, and they are DIFFERENT FAULTS rather than one fault at two scales:
|
||||
|
||||
PER UNIT this unit's standing command against ITS OWN measured power -
|
||||
`Inverter.batt`, which on the live system is holding register
|
||||
0x0518, this inverter's own AC power, per-instance since DEV-02.
|
||||
Conclusion: "THE ACTUATOR I AM DRIVING IS NOT DOING WHAT I TOLD
|
||||
IT". The evidence is about one unit, so the remedy is that unit:
|
||||
the `failsafe` SET, which arbiter.CLAIM_SCOPE has called a UNIT
|
||||
claim from the day it was written, for this exact reason.
|
||||
SITE the SUM of the standing commands against the meter. Conclusion:
|
||||
"THE SITE AS A WHOLE IS DRIVING THE WRONG WAY" - an inverted gain,
|
||||
an integrator wound past the rail, a strategy pushing the wrong
|
||||
side of the meter. That is the fault the 2026-08-20 capture
|
||||
contains and it is a property of the CONNECTION, so the remedy is
|
||||
the connection: a SITE SET that stops every inverter.
|
||||
|
||||
⚠️ AND AT N=1 THERE IS EXACTLY ONE ARMED DETECTOR, WHICH IS THE ONE THAT
|
||||
SHIPPED. The two questions above are the SAME SENTENCE at a roster of one: the
|
||||
sum of one command is that command, and "the site" and "the unit" name one
|
||||
actuator. Arming both would be arming a duplicate - two latches, two banners and
|
||||
two chances to spend a false-positive record that was earned by ONE comparison
|
||||
on two captured bus days. `Controller.cycle()` therefore hands the single unit's
|
||||
watchdog THE METER, under the shipped `sign_disagree_w` / `sign_disagree_s`,
|
||||
exactly as before, and never arms the site one. `arm()` below is where that
|
||||
choice is written down. Nothing about a one-inverter install changes - not the
|
||||
comparison, not the thresholds, not the store keys, not the claim, not the
|
||||
banner.
|
||||
|
||||
⚠️ WHAT THE PER-UNIT COMPARISON IS NOT. Two guards that overlap without saying
|
||||
so is how a false-alarm generator gets built, so both neighbours are named:
|
||||
|
||||
* IT IS NOT SAFETY-31. `circulation.py` compares the units AGAINST EACH OTHER
|
||||
- `sum(|B_i|) - |sum(B_i)|` over MEASURED power - and catches two inverters
|
||||
pushing THROUGH each other, which nets to zero at the meter and about which
|
||||
no single command is evidence at all. This compares each unit against ITS
|
||||
OWN COMMAND. Take two units faithfully executing an allocation that ALLOC-01
|
||||
would refuse: circulating power is the whole loop, and every per-unit sign
|
||||
check here reads perfect agreement. Take one unit doing the exact opposite
|
||||
of its share while its sibling covers for it: this reads the whole
|
||||
disagreement, and circulating power can be zero, because the two measured
|
||||
powers may well agree in sign. Neither is the other with a different
|
||||
threshold.
|
||||
* IT IS NOT THE SATURATION FREEZE, AND THE OVERLAP IS REAL AND BOUNDED. The
|
||||
freeze asks `|command - measured| > saturation_w` (500 W) and concludes "the
|
||||
inverter cannot follow"; it then stops the integrator winding, which is a
|
||||
control action taken every day, on a unit that is merely SATURATED as
|
||||
readily as on one that is reversed, and it neither latches nor parks
|
||||
anything. This asks for OPPOSITION - a sign, on both sides of a threshold,
|
||||
held continuously - which a saturated-but-obedient unit cannot produce at
|
||||
all, and it LATCHES and commands that unit to zero. The freeze is a
|
||||
magnitude test that shapes the loop; this is a direction test that stops an
|
||||
actuator.
|
||||
|
||||
⚠️ GATE 1 STILL APPLIES TO BOTH, AND THAT IS A DELIBERATE CHOICE WITH A COST.
|
||||
The per-unit comparison could have been armed whenever ANY non-zero command is
|
||||
standing - a unit should do what it is told whoever told it - and that would
|
||||
catch a wedged inverter during a maintenance charge. It is not, because the
|
||||
whole no-false-positive argument above is built on `following`, because the
|
||||
freeze already grades that window, and because this card's own warning is that
|
||||
SAFETY-02's record was earned at N=1 and must not be spent on a check that fires
|
||||
when nothing is wrong. What it costs is written here rather than discovered:
|
||||
between the start of a maintenance cycle and its end, a unit reversing against
|
||||
its own command is the freeze's to notice, not this module's. Widening it is a
|
||||
card, with a rig campaign behind it, not an edit.
|
||||
|
||||
------------------------------------------------------------------------------
|
||||
STATE, TRIP AND LATCH
|
||||
|
||||
@@ -198,6 +293,178 @@ from dataclasses import dataclass
|
||||
from datetime import datetime
|
||||
|
||||
|
||||
# SAFETY-30. CFG-03: THE ONE IN-CODE COPY OF THE FOUR MULTI-INVERTER DEFAULTS.
|
||||
# `config.yaml`'s `options:` block is the source of truth an operator edits and
|
||||
# the Supervisor reads, and `schema:` holds the bounds. This dict exists for the
|
||||
# reason `circulation.CIRC_OPTION_DEFAULTS` and `maintenance.MAINT_OPTION_DEFAULTS`
|
||||
# do - the Dockerfile does not put config.yaml in the image, so the running
|
||||
# add-on cannot read it - and `test_watchdog.py` pins the two together by READING
|
||||
# config.yaml, so a drift goes red in CI rather than shipping.
|
||||
#
|
||||
# ⚠️ EVERY KEY HERE IS DEAD AT A ROSTER OF ONE, and that is the point rather
|
||||
# than a caveat. `Controller._arm_sign_watchdogs()` arms the single unit's
|
||||
# detector against the meter with the SHIPPED `sign_disagree_w` /
|
||||
# `sign_disagree_s`, which are read in main.py exactly where they always were
|
||||
# and are not in this dict. Nothing below is consulted until a second inverter
|
||||
# exists.
|
||||
SIGN_OPTION_DEFAULTS = {
|
||||
# --- THE MAGNITUDE GATE, AND IT IS NOT SAFETY-02's 300 W BY ACCIDENT ---
|
||||
# ⚠️ DERIVED FROM `control.Tuning.saturation_w`, WHICH IS 500 W, AND THE
|
||||
# DERIVATION IS THE POINT. This check gates on BOTH sides being over
|
||||
# `min_w`, so the smallest divergence it can ever see between a command and
|
||||
# the power that command produced is `2 * min_w` - the two are OPPOSED, so
|
||||
# the gap is the sum of the magnitudes. At 250 W that is exactly 500 W: the
|
||||
# gap at which `compute()`'s own anti-windup test already concludes THE
|
||||
# INVERTER IS NOT FOLLOWING and freezes the integrator. So this watchdog
|
||||
# cannot fire on a divergence the shipped control law itself calls ordinary
|
||||
# tracking, and the two guards meet at a number rather than overlapping in a
|
||||
# band nobody has drawn.
|
||||
#
|
||||
# MEASURED, on 1890 closed-loop two-inverter runs in which NOTHING is faulty
|
||||
# (every unit executes the share the allocator gave it), swept over the
|
||||
# WHOLE range config.yaml accepts for `gain` float(0.05,1.0) and `slew_w`
|
||||
# int(50,5000), across both families of stimulus that can produce legitimate
|
||||
# opposition. Worst CONTINUOUS opposition between a unit's standing command
|
||||
# and its own 0x0518 power, as a function of this threshold:
|
||||
#
|
||||
# 50 W -> 25.0 s 250 W -> 10.0 s 700 W -> 5.0 s
|
||||
# 150 W -> 15.0 s 300 W -> 10.0 s 1000 W -> 0.0 s
|
||||
# 200 W -> 15.0 s 500 W -> 5.0 s
|
||||
#
|
||||
# ⚠️ AND THE CURVE IS FLAT, WHICH IS THE FINDING THAT DECIDED THE SHAPE OF
|
||||
# THIS PAIR. Unlike the site comparison - where the meter is driven by the
|
||||
# LOAD and a flapping load holds it opposed for minutes - a unit's own power
|
||||
# CHASES ITS OWN COMMAND through a bounded ramp and a first-order lag, so the
|
||||
# opposition can only last as long as the crossing does. Dropping the
|
||||
# threshold from 300 W to 50 W buys 15 s of extra transient and nothing else.
|
||||
# The work is therefore done by the WINDOW below, and this number is set
|
||||
# where the control law already draws its line rather than being tuned.
|
||||
#
|
||||
# The largest opposed magnitude seen anywhere in those 1890 runs is 875 W;
|
||||
# a threshold above that would gate NOTHING legitimate in at all, and is
|
||||
# rejected because it would also be blind to a unit reversing a 900 W share.
|
||||
"unit_sign_disagree_w": 250,
|
||||
|
||||
# --- THE WINDOW -------------------------------------------------------
|
||||
# Three bounds, and the value clears all three.
|
||||
#
|
||||
# LOWER, from the rig: 10.0 s - two control cycles, the worst CONTINUOUS
|
||||
# legitimate opposition above 250 W across all 1890 runs. It is a
|
||||
# reversing site whose second write lands a cycle after the first, both
|
||||
# units then slewing through zero behind a 10 s lag; nothing is wrong.
|
||||
#
|
||||
# LOWER, from the firmware: `inverter.LINK_STALE_S`, 30 s. A unit not
|
||||
# executing its share for less than the firmware's own veto window is a
|
||||
# LINK fault, and the add-on already answers it - liveness drops the unit
|
||||
# and the survivors carry its share, with the record saying so. Firing
|
||||
# inside that window would raise a second, louder alarm about a state
|
||||
# already being handled, which is the SAFETY-15/SAFETY-19 failure exactly.
|
||||
#
|
||||
# UPPER, from SAFETY-02 itself: 180 s, the SITE hold. A unit that is not
|
||||
# doing what it was told must not be parked LATER than the site would be
|
||||
# parked for the same watts, and unlike the site comparison this one needs
|
||||
# nothing to net out before it can conclude - the evidence is complete on
|
||||
# the first cycle it appears.
|
||||
#
|
||||
# 85 s: seventeen control cycles - 8.5x the worst legitimate episode this
|
||||
# rig can produce, 2.8x the firmware's own veto window, and under HALF the
|
||||
# site hold. ⚠️ IT IS DELIBERATELY NOT 60, 75, 90, 120 OR 180. A round
|
||||
# number here would be a guess wearing a measurement's clothes, and the
|
||||
# three bounds above are what the number has to answer to.
|
||||
#
|
||||
# ⚠️ AND INVERTER B DOES NOT PHYSICALLY EXIST. Its ramp and lag in the rig
|
||||
# are inverter A's, COPIED, carrying `measured=False` - SPIKE-04 measures
|
||||
# the real ones. A slower second unit lengthens every crossing above, which
|
||||
# is what the 8.5x buys headroom for. SPIKE-04 is the revisit trigger for
|
||||
# both numbers here, not a reason to move them now.
|
||||
"unit_sign_disagree_s": 85,
|
||||
|
||||
# --- THE SITE COMPARISON AT N>=2, AND IT IS NOT THE SHIPPED PAIR -------
|
||||
# ⚠️ THE THRESHOLD IS CARRIED AND THE WINDOW IS NOT, WHICH IS A FINDING
|
||||
# RATHER THAN A COMPROMISE. Only one of the two arguments behind 300 W /
|
||||
# 180 s depends on how many inverters the site has:
|
||||
#
|
||||
# THE THRESHOLD is about NOISE. "Near zero the sign is noise, and near
|
||||
# zero is where a healthy loop LIVES" - the deadband holds the command
|
||||
# still while the meter wanders either side of `target_grid_w`. The
|
||||
# deadband is 15 W and P1 is one meter whatever the roster, so nothing
|
||||
# about that argument moves. 300 W, carried - and the two-inverter
|
||||
# campaign says the carry is safe rather than merely convenient: in the
|
||||
# load-reversal family the site figure ever goes opposed AND over 300 W in
|
||||
# 994 of 1050 runs at two inverters and 955 of 1050 at one. The gate opens
|
||||
# about as often either way; what changed is how LONG it stays open, which
|
||||
# is the window's problem and not the threshold's.
|
||||
#
|
||||
# THE WINDOW is about a TRANSIENT, and the transient scales with the site.
|
||||
# The measured worst legitimate case is a load reversal that the loop
|
||||
# crosses zero slowly: the command has to travel the whole rail at
|
||||
# `slew_w` per cycle, and at N>=2 the rail is `Controller.site_max_w` - the
|
||||
# ROSTER SUM - while `slew_w` is unchanged. So the crossing takes about
|
||||
# twice as long at two inverters as at one, and that is exactly what the
|
||||
# rig measures.
|
||||
#
|
||||
# 1890 closed-loop runs in which nothing is faulty, the SAME campaign the
|
||||
# per-unit pair above is read off, run at BOTH rosters as its own control.
|
||||
# Worst CONTINUOUS opposition between the standing command(s) and the meter,
|
||||
# LOAD-REVERSAL family, at a 300 W threshold:
|
||||
#
|
||||
# N=1 (the shipped comparison) 110.0 s - inside 180 s, 1.6x
|
||||
# N=2 (the sum, same stimuli) 215.0 s - OVER 180 s
|
||||
#
|
||||
# ⚠️ SO CARRYING 180 s WOULD HAVE SHIPPED A FALSE TRIP, and it is a config a
|
||||
# schema-legal install can reach: `gain` 0.05 and `slew_w` 50 are both the
|
||||
# floor of what config.yaml accepts, and a +-2200 W load reversal is an oven
|
||||
# and a heat pump. That is the number this card exists to not assume.
|
||||
#
|
||||
# 325 s: 1.51x the measured worst, well inside the 900 s quarter that bills
|
||||
# the capacity tariff, and still inside every episode the fault day
|
||||
# contains - 2026-08-20's four clusters run 16, 30, 77 and 77 minutes and
|
||||
# its opposed runs reach 1750 s, so a 325 s window fires in all of them.
|
||||
# What it costs is stated rather than hidden: about two and a half extra
|
||||
# minutes of wrong-direction SITE power before the stop, bought to remove a
|
||||
# false trip that a legal configuration produces. ⚠️ DELIBERATELY NOT 300 OR
|
||||
# 360; the measurement is what it answers to.
|
||||
#
|
||||
# ⚠️ AND IT IS NOT THE PER-UNIT WINDOW EITHER, IN THE OTHER DIRECTION. The
|
||||
# per-unit comparison is 85 s because a unit's own power CHASES ITS OWN
|
||||
# COMMAND and the transient is two cycles; the site comparison is 325 s
|
||||
# because the meter is driven by the LOAD and the transient is the loop
|
||||
# crossing zero. Same predicate, two instruments, two windows, both measured.
|
||||
"site_sign_disagree_w": 300,
|
||||
"site_sign_disagree_s": 325,
|
||||
}
|
||||
|
||||
# ⚠️ A LIMIT OF THE SITE COMPARISON THAT SAFETY-30 DID NOT INTRODUCE AND DOES
|
||||
# NOT FIX, RECORDED HERE BECAUSE THE CAMPAIGN FOUND IT AND SILENCE WOULD BE
|
||||
# WORSE. The rig's other stimulus family is a FLAPPING LOAD, and a square wave
|
||||
# whose half period is about one control cycle opposes the command on EVERY
|
||||
# cycle: the command chases the previous half-cycle's meter while the meter has
|
||||
# already reversed. Across the 840 flapping runs the worst continuous opposition
|
||||
# at a 300 W threshold is 980 s at two inverters - and 1000 s at ONE, which is
|
||||
# the whole point. The N=1 arm is the control, and it says this is a property of
|
||||
# comparing a lagged command against a meter, not a property of the second
|
||||
# inverter. No window inside the 900 s billing quarter survives it, and no
|
||||
# threshold up to 1000 W does either.
|
||||
#
|
||||
# It is not acted on here for three reasons, in order of weight: it is identical
|
||||
# at the roster this add-on actually ships, so acting on it would be changing a
|
||||
# live safety path on evidence that has nothing to do with this card; a
|
||||
# ~6 kW square wave at 0.1 Hz sustained for a quarter of an hour is not a house
|
||||
# (the captured healthy day's longest opposed run is 30 s); and the fix is not a
|
||||
# number - it wants the detector to notice that the disagreement is ALTERNATING,
|
||||
# which is a different check. It is a card, and this comment is its evidence.
|
||||
|
||||
# SAFETY-30. THE TWO NOUNS THE TRIP SENTENCE CAN NAME, WRITTEN ONCE. They are
|
||||
# constants rather than literals at the call sites because `main.py` arms the
|
||||
# detectors and `test_watchdog.py` grades what they say, and a string typed in
|
||||
# two places is a string that drifts in one of them - the same argument
|
||||
# `store.unit_key()` makes about a key name. `AGAINST_METER` is the wording that
|
||||
# has always shipped and must not change: it is what a one-inverter install's
|
||||
# `reason` reads, in the store, in the action log and on the status page.
|
||||
AGAINST_METER = "a meter reading"
|
||||
AGAINST_OWN_POWER = "its own measured power"
|
||||
|
||||
|
||||
@dataclass(frozen=True)
|
||||
class SignWatchdogConfig:
|
||||
"""Defaults, not constants - config.yaml carries both (SAFETY-02 AC 5)."""
|
||||
@@ -206,7 +473,7 @@ class SignWatchdogConfig:
|
||||
hold_s: float = 180.0
|
||||
|
||||
|
||||
def disagrees(commanded_w, grid_w, following: bool,
|
||||
def disagrees(commanded_w, against_w, following: bool,
|
||||
cfg: SignWatchdogConfig) -> bool:
|
||||
"""The predicate, and the ONLY place it is written down.
|
||||
|
||||
@@ -215,12 +482,23 @@ def disagrees(commanded_w, grid_w, following: bool,
|
||||
inline. Two copies of a safety predicate is one copy plus a future
|
||||
disagreement about what the check means, and the copy that drifts is always
|
||||
the one in the harness that grades it.
|
||||
|
||||
⚠️ `against_w` WAS CALLED `grid_w`, AND THE RENAME IS THE WHOLE OF SAFETY-30
|
||||
IN ONE PARAMETER. The arithmetic is unchanged - opposed signs, neither side
|
||||
near zero, and the loop actually driving - but WHAT the command is opposed
|
||||
TO is now a property of the caller rather than a fact about this function.
|
||||
The site comparison hands it the meter; each unit's own comparison hands it
|
||||
that unit's measured power (register 0x0518). One predicate, two callers,
|
||||
for `loop_is_following()`'s reason: a safety predicate written down twice is
|
||||
one copy plus a future disagreement about what the check means. The
|
||||
parameter is positional at every call site in both repositories, so the
|
||||
rename moves no caller.
|
||||
"""
|
||||
return (following
|
||||
and commanded_w is not None and grid_w is not None
|
||||
and commanded_w * grid_w < 0
|
||||
and commanded_w is not None and against_w is not None
|
||||
and commanded_w * against_w < 0
|
||||
and abs(commanded_w) > cfg.min_w
|
||||
and abs(grid_w) > cfg.min_w)
|
||||
and abs(against_w) > cfg.min_w)
|
||||
|
||||
|
||||
def loop_is_following(resolution, loop_asked) -> bool:
|
||||
@@ -272,7 +550,17 @@ def loop_is_following(resolution, loop_asked) -> bool:
|
||||
|
||||
|
||||
class SignWatchdog:
|
||||
"""One instance per actuator, evaluated once per control cycle.
|
||||
"""One instance per COMPARISON, evaluated once per control cycle.
|
||||
|
||||
⚠️ SINCE SAFETY-30 THAT IS NOT THE SAME SENTENCE AS "one per actuator",
|
||||
which is what this docstring used to say. There is one instance per
|
||||
inverter - `Inverter.sign_wd`, latched under that unit's own store keys -
|
||||
AND one for the site, `Controller.site_sign_wd`, latched under flat ones.
|
||||
The two ask different questions of different evidence and reach different
|
||||
remedies; `arm()` below is where an instance is told which of them it is.
|
||||
At a roster of one they would be the same question, so only the per-unit
|
||||
instance is ever armed there - see the SAFETY-30 section of the module
|
||||
docstring.
|
||||
|
||||
⚠️ NOT SHARED ACROSS CADENCES. `disagree_since` is a wall-clock start time,
|
||||
so driving one instance from two loops at two rates would have each one
|
||||
@@ -282,8 +570,14 @@ class SignWatchdog:
|
||||
"""
|
||||
|
||||
def __init__(self, cfg: SignWatchdogConfig | None = None, *,
|
||||
tripped: bool = False, reason: str = ""):
|
||||
tripped: bool = False, reason: str = "",
|
||||
against: str = AGAINST_METER):
|
||||
self.cfg = cfg or SignWatchdogConfig()
|
||||
# SAFETY-30. WHAT THE COMMAND IS BEING COMPARED AGAINST, as the operator
|
||||
# reads it in the trip sentence. The default is the meter, which is what
|
||||
# every trip this add-on has ever taken was compared against and is what
|
||||
# keeps a one-inverter install's `reason` string byte-identical.
|
||||
self.against = str(against)
|
||||
self.disagree_since: datetime | None = None
|
||||
# ⚠️ RESTORED FROM THE STORE, NOT DEFAULTED. A latch that lives only in
|
||||
# memory is not a latch: a container restart clears it, and the add-on
|
||||
@@ -292,8 +586,31 @@ class SignWatchdog:
|
||||
self.tripped = bool(tripped)
|
||||
self.reason = reason if self.tripped else ""
|
||||
|
||||
# -- which of SAFETY-30's two questions this instance is asking ----------
|
||||
def arm(self, cfg: SignWatchdogConfig, against: str) -> None:
|
||||
"""Set the thresholds and the subject of the comparison. Nothing else.
|
||||
|
||||
⚠️ IT IS CONFIGURATION, NOT STATE, AND IT DELIBERATELY DOES NOT TOUCH
|
||||
`disagree_since`, `tripped` OR `reason`. A detector that cleared its own
|
||||
window when it was told what it was comparing against would lose the
|
||||
episode it is in the middle of, every cycle, and would never accumulate
|
||||
a hold at all - the check would be permanently green and nothing would
|
||||
say so.
|
||||
|
||||
⚠️ AND IT IS RE-STATED EVERY CYCLE RATHER THAN FROZEN AT CONSTRUCTION.
|
||||
The answer is a property of the ROSTER and of nothing else, and
|
||||
`Controller.cycle()` already re-reads the roster every cycle for
|
||||
liveness and for the allocation. Freezing it in `__init__` would also
|
||||
make it wrong for any caller that appends an inverter afterwards, which
|
||||
is exactly how a two-inverter fixture is built in this repository - and
|
||||
a fixture that silently got the one-inverter comparison would grade
|
||||
nothing while looking green.
|
||||
"""
|
||||
self.cfg = cfg
|
||||
self.against = str(against)
|
||||
|
||||
# -- the whole check, and it is a pure function of its arguments ----------
|
||||
def evaluate(self, commanded_w, grid_w, following: bool,
|
||||
def evaluate(self, commanded_w, against_w, following: bool,
|
||||
now: datetime) -> bool:
|
||||
"""Advance the detector one cycle. Returns True while tripped.
|
||||
|
||||
@@ -301,15 +618,23 @@ class SignWatchdog:
|
||||
after deadband, slew, quantisation and the arbiter. Not
|
||||
the optimizer's raw wish: the wire carries the emitted
|
||||
value, so anything else can disagree with the meter for a
|
||||
reason that is not a fault.
|
||||
`grid_w` net P1, + = importing. None when the meter is stale or
|
||||
missing, which CLEARS the timer rather than accumulating
|
||||
- a frozen figure held against a moving command would
|
||||
otherwise manufacture a disagreement in about three
|
||||
minutes, on top of SAFETY-01 having already commanded
|
||||
zero for the same cause.
|
||||
reason that is not a fault. For a per-unit instance it is
|
||||
THAT UNIT'S share of it; for the site instance it is the
|
||||
roster sum.
|
||||
`against_w` what the command is graded against, and SAFETY-30 made
|
||||
this a decision rather than a fact: net P1 for the SITE
|
||||
comparison (+ = importing), and this unit's own measured
|
||||
power for the PER-UNIT one (+ = discharging, register
|
||||
0x0518). Both carry the same sign convention as the
|
||||
command, which is why one predicate serves both. None
|
||||
when the reading is stale or missing, which CLEARS the
|
||||
timer rather than accumulating - a frozen figure held
|
||||
against a moving command would otherwise manufacture a
|
||||
disagreement in about three minutes, on top of SAFETY-01
|
||||
having already commanded zero for the same cause.
|
||||
`following` did the grid-following loop actually win this cycle? See
|
||||
gate 1 in the module docstring.
|
||||
gate 1 in the module docstring, and the SAFETY-30 section
|
||||
on why the per-unit comparison keeps it.
|
||||
`now` the caller's clock, so this stays testable and replayable.
|
||||
"""
|
||||
if self.tripped:
|
||||
@@ -317,7 +642,7 @@ class SignWatchdog:
|
||||
return True
|
||||
|
||||
cfg = self.cfg
|
||||
if not disagrees(commanded_w, grid_w, following, cfg):
|
||||
if not disagrees(commanded_w, against_w, following, cfg):
|
||||
self.disagree_since = None
|
||||
return False
|
||||
|
||||
@@ -330,9 +655,17 @@ class SignWatchdog:
|
||||
return False
|
||||
|
||||
self.tripped = True
|
||||
# ⚠️ `self.against` IS THE ONLY THING SAFETY-30 CHANGED IN THIS STRING,
|
||||
# and it defaults to the wording that shipped - "a meter reading" - so a
|
||||
# one-inverter install's `reason` is byte-identical to what an operator
|
||||
# (and test_watchdog.py) has always read. A per-unit instance names what
|
||||
# it actually compared instead, because "commanded +1500 W against a
|
||||
# meter reading -1500 W" would be a false statement about which
|
||||
# instrument produced the evidence, on the one line somebody woken by
|
||||
# this alarm reads first.
|
||||
self.reason = (
|
||||
f"SIGN_DISAGREEMENT: commanded {commanded_w:+.0f} W against a meter "
|
||||
f"reading {grid_w:+.0f} W for {held:.0f} s continuously "
|
||||
f"SIGN_DISAGREEMENT: commanded {commanded_w:+.0f} W against "
|
||||
f"{self.against} {against_w:+.0f} W for {held:.0f} s continuously "
|
||||
f"(limits: both over {cfg.min_w:.0f} W, held over {cfg.hold_s:.0f} s)"
|
||||
)
|
||||
return True
|
||||
|
||||