DEV-02: zero every unit's target when the operator stops, not just the site's
checks / unit (pull_request) Successful in 4m12s
checks / unit (pull_request) Successful in 4m12s
A hazard THIS CARD CREATED, found by re-reading the operator paths rather than by a failing check - so a check now exists for it. Before DEV-02 the heartbeat re-emitted `self.target`, so the stop button zeroing that one scalar was enough: the next refresh carried the zero. The heartbeat now re-emits `inv.target` - it has to, or it would put the SITE number on every inverter, which is the ARCH-01 broadcast fault arriving once every `heartbeat_s` on a path with no allocator in it. So a stop that zeroed only `self.target` left each unit's LAST SHARE standing. No cycle has run yet at that moment, so nothing else would have cleared it, and the very next heartbeat - up to `heartbeat_s` later - would put it back on the wire. The operator presses stop, watches the inverter go to zero, and sees it resume seconds later. `command_site_zero()` moves both together and carries the reason. It is one method rather than two lines at three call sites precisely because the two lines have to stay together: shutdown(), the stop button and maint_abort all mean the same thing, and 0 W is the one value that may legitimately be written site-wide. test_inverter.py part 6 presses stop with 995/995 standing and then runs the SHIPPED `send_heartbeats()` before any cycle, which is the racing refresh. The mutation that zeroes the site target alone takes it red. 19 files green. Co-Authored-By: Claude Opus 5 (1M context) <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
This commit is contained in:
co-authored by
Claude Opus 5
parent
e306c74cb8
commit
e941bf7f62
@@ -2181,14 +2181,32 @@ class Controller:
|
||||
"""Deterministic wind-down. Do not skip this."""
|
||||
self.stopping = True
|
||||
_LOG.info("shutting down - commanding 0 W on every inverter")
|
||||
# 0 W is the one value that means the same thing to every inverter, so
|
||||
# the site-wide form of the write is legitimate here - see
|
||||
# write_setpoint(). Each unit's target is zeroed too, so a heartbeat
|
||||
# racing this cannot re-emit the old share.
|
||||
await self.command_site_zero()
|
||||
self.mqtt.close()
|
||||
|
||||
async def command_site_zero(self) -> None:
|
||||
"""Every inverter to 0 W, and every inverter's TARGET to 0 W with it.
|
||||
|
||||
⚠️ THE SECOND HALF IS NOT BOOKKEEPING, AND IT IS A HAZARD DEV-02
|
||||
CREATED. Before this card the heartbeat re-emitted `self.target`, so
|
||||
zeroing that one scalar was enough: the stop button set it and the next
|
||||
refresh carried the zero. The heartbeat now re-emits `inv.target` - it
|
||||
has to, or it would broadcast the site number - so a stop that zeroed
|
||||
only `self.target` would leave each unit's LAST SHARE standing, and the
|
||||
very next heartbeat (up to `heartbeat_s` later, and before any cycle has
|
||||
run) would put it back on the wire. The operator would have pressed
|
||||
stop, watched the inverter go to zero, and seen it resume seconds later.
|
||||
Both must move together, which is why this is one method with a reason
|
||||
and not two lines repeated at three call sites.
|
||||
|
||||
⚠️ AND 0 W IS THE ONE VALUE THAT MAY BE WRITTEN SITE-WIDE. It means the
|
||||
same thing to every inverter; a non-zero site-wide write is the ARCH-01
|
||||
broadcast fault, and `write_setpoint()` refuses it.
|
||||
"""
|
||||
self.target = 0.0
|
||||
for inv in self.inverters:
|
||||
inv.target = 0.0
|
||||
await self.write_setpoint(0.0, force=True)
|
||||
self.mqtt.close()
|
||||
|
||||
# -- UI ------------------------------------------------------------------
|
||||
def checks(self, when: datetime | None = None) -> list:
|
||||
@@ -2572,8 +2590,11 @@ class Controller:
|
||||
self.log_event(f"sign-disagreement failsafe cleared by "
|
||||
f"operator on {inv.name}")
|
||||
if not self.auto:
|
||||
self.target = 0.0
|
||||
await self.write_setpoint(0.0, force=True)
|
||||
# ⚠️ THE WHOLE SITE, TARGETS INCLUDED - see command_site_zero().
|
||||
# Zeroing `self.target` alone would leave each unit's last share
|
||||
# standing for its next heartbeat to re-emit, which an operator
|
||||
# would read as the stop button not working.
|
||||
await self.command_site_zero()
|
||||
return {"auto": self.auto}
|
||||
if what == "maint_start":
|
||||
for msg in self.maint.force_start(now):
|
||||
@@ -2582,8 +2603,7 @@ class Controller:
|
||||
if what == "maint_abort":
|
||||
for msg in self.maint.abort(now, "operator"):
|
||||
self.log_event(msg)
|
||||
self.target = 0.0
|
||||
await self.write_setpoint(0.0, force=True)
|
||||
await self.command_site_zero()
|
||||
return {"phase": self.maint.phase}
|
||||
return None
|
||||
|
||||
|
||||