SAFETY-07 can command a discharge to hold a billed quarter down, and nothing below it consulted the state of charge. On the 2026-08-20 replay it asks for 878 Wh in a day. Relying on the BMS is not absurd - it is a real floor and it works - but it is the pack's protection rather than the operator's, and a month of aggressive quarters leaves the battery repeatedly at that cut-out with no EMS-side record of why. The first symptom is a pack never available when wanted, which is indistinguishable from the SoC drift MAINT-01 exists to correct. decide() now takes soc and soc_floor, both required and neither defaulted, and discharge_permitted() is the one place the question is answered. Above the floor nothing changes. At or below it the guard files a 0 W floor instead of a sized one - one-directional, so charging stays blocked and no discharge is capped - and reports floor_limited with the reason it bound. It is not a trip: every stop in 11.2's table still outranks the claim, and the floor is never negative, so 9.1's asymmetry survives as a property of the object (0 negative floors over 1296 swept combinations, SoC included). The SoC is graded only after `wanted > 0` is established, so it is never evaluated where it governs nothing. An unreadable SoC is floor-limited, not a full battery - a full battery is exactly the value that would disarm the floor, and this project shipped that defaulting once already. Failing to shave is not silent: one notification per episode (goodwe_peak_soc_floor), distinct from the saturation alarm because the two ask for opposite operator actions, plus its own status row and an action-log line. Verified by replay. The 2026-08-20 capture is driven against a modelled pack sized from the day's own measured appetite, so it genuinely exhausts: without the floor it reaches the BMS cut-out and holds there for 1227 guard cycles; with it the pack stops at 20.0 % and never touches the BMS. The energy withheld equals the energy between the two floors to within one cycle at the rail. The honest half is reported too - the worst quarter goes 4338 W -> 5030 W, because a floor-limited guard shaves less on purpose. Two new options, mirrored once in peakguard.PEAK_OPTION_DEFAULTS (TARIFF-02's pattern), imported by validate.py and main.py rather than typed as literals and pinned to config.yaml by a check that reads the file - so CFG-03 still tracks three places. validate.py rule 8 refuses peak_soc_floor <= bms_soc_floor at startup, in CFG-01/MAINT-04's manner. maintenance_soc_floor is deliberately not reused and not renamed: it is a drain target, not a spend limit, and the rename is recorded as a decision to revisit if a third floor appears. Eleven mutations of the shipped source were run against the checks; all eleven go red and there are no survivors. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_015VXjA3LWccN1rJsk3okyPC
This commit is contained in:
co-authored by
Claude Opus 5
parent
e7c95bfd8a
commit
e709554857
@@ -199,14 +199,25 @@ class Controller:
|
||||
# the action log and the notification fire on transitions rather than
|
||||
# once per cycle for a quarter of an hour.
|
||||
#
|
||||
# ⚠️ NO CONFIG OF ITS OWN, for the reason the clamp watchdog gives ~90
|
||||
# lines up and TARIFF-01 repeats: the ceiling is `peak_cap_w`, already
|
||||
# shipped and already validated, and every other term is read off
|
||||
# something the arbiter or the averager already owns. CFG-03 still
|
||||
# tracks three places, not four.
|
||||
# ⚠️ THE CEILING HAS NO CONFIG OF ITS OWN, for the reason the clamp
|
||||
# watchdog gives ~90 lines up and TARIFF-01 repeats: it is `peak_cap_w`,
|
||||
# already shipped and already validated, and every other term of the
|
||||
# projection is read off something the arbiter or the averager already
|
||||
# owns.
|
||||
#
|
||||
# ⚠️ SAFETY-24'S FLOOR DOES HAVE ONE, AND IT COULD NOT NOT HAVE. How far
|
||||
# down the guard may spend the pack for money is a number only the site
|
||||
# knows, and refusing one set below the pack's own cut-out means knowing
|
||||
# that cut-out too. So this card adds exactly two keys and reads their
|
||||
# defaults from `peakguard.PEAK_OPTION_DEFAULTS` - TARIFF-02's mirror
|
||||
# pattern - rather than typing literals here. THAT is what keeps CFG-03
|
||||
# at three places: the divergence validate.py's rule 6 documents
|
||||
# (`maintenance_charge_w` 2000 there, 2500 here) is exactly what a
|
||||
# literal in this file would repeat.
|
||||
self.peak_guard = None
|
||||
self._peak_engaged = False
|
||||
self._peak_saturated = False
|
||||
self._peak_floor_limited = False
|
||||
self._maint_shape_suspended = False
|
||||
# Set by amain() once the transport is built, so the status page can show
|
||||
# what only the transport knows (homewizard_local's unchanged_s). Stays
|
||||
@@ -494,6 +505,17 @@ class Controller:
|
||||
cap_w=float(self.o.get("peak_cap_w", 3500)),
|
||||
reading=self.peak.peak(now),
|
||||
achievable_w=min(max_w, abs(float(dev_top))),
|
||||
# ⚠️ SAFETY-24. `self.soc` IS THE MEASURED READING AND MAY BE None,
|
||||
# and it is handed over as None rather than defaulted here. An early
|
||||
# draft of the stage-5 loop read SoC as `| float(100)` and thereby
|
||||
# invented a full battery (NOTES.md 4.4b); a full battery is
|
||||
# precisely the value that disarms this floor. decide() treats None
|
||||
# as floor-limited, which is the direction that costs a shave rather
|
||||
# than the pack.
|
||||
soc=self.soc,
|
||||
soc_floor=float(self.o.get(
|
||||
"peak_soc_floor",
|
||||
peakguard.PEAK_OPTION_DEFAULTS["peak_soc_floor"])),
|
||||
max_hold_s=self.p1.averager.max_hold_s,
|
||||
frozen=looks_frozen(getattr(self.p1_source, "unchanged_s", None),
|
||||
standing, max_w, self.freeze_wd.cfg),
|
||||
@@ -682,6 +704,16 @@ class Controller:
|
||||
# method assigned above and nothing since has touched.
|
||||
await self.check_peak_saturated()
|
||||
|
||||
# --- SAFETY-24's alarm, and it is the OTHER way the money gets spent --
|
||||
# Same boundary argument as check_peak_saturated(): it grades
|
||||
# `self.peak_guard`, which cycle() assigned above and nothing since has
|
||||
# touched. Kept as its own method rather than folded into that one,
|
||||
# because the two states are mutually exclusive and want OPPOSITE
|
||||
# operator actions - saturation says "shed load, the inverter is already
|
||||
# flat out"; this says "the pack is at its floor and this quarter is not
|
||||
# being shaved at all".
|
||||
await self.check_peak_floor_limited()
|
||||
|
||||
# --- TARIFF-01, and it is LAST on purpose -----------------------------
|
||||
# Banking a quarter is bookkeeping about a moment that has already
|
||||
# happened; a slow SD card must never sit between the meter and the
|
||||
@@ -826,6 +858,70 @@ class Controller:
|
||||
f"thing that changes the bill."),
|
||||
})
|
||||
|
||||
async def check_peak_floor_limited(self) -> None:
|
||||
"""SAFETY-24. Alarm when the EMS SoC floor stops the guard shaving.
|
||||
|
||||
⚠️ FAILING TO SHAVE MUST NOT BE SILENT, AND THAT IS THE WHOLE POINT.
|
||||
The guard exists for one euro figure - the capaciteitstarief bills the
|
||||
month's single worst quarter - so a cycle in which it CHOSE not to shave
|
||||
is a cycle in which money is being spent on purpose. Under-shaving
|
||||
quietly would leave the operator with a bill and a status page full of
|
||||
green.
|
||||
|
||||
The distinction from check_peak_saturated() is the operator's action,
|
||||
which is why these are two notifications and not one:
|
||||
|
||||
saturated the guard asked for everything the inverter has and it
|
||||
was not enough. SHED LOAD - the controller has already
|
||||
done all it can, and it is still discharging.
|
||||
floor-limited the guard asked for NOTHING, because the pack is at or
|
||||
under the EMS floor, or its SoC could not be read.
|
||||
Nothing is being discharged for this quarter at all.
|
||||
|
||||
They cannot both be true: peakguard.decide()'s floor-limited branch
|
||||
returns before the `achievable_w` clamp that sets `saturated`.
|
||||
|
||||
Edge-triggered, and de-asserting arms it again - FreezeWatchdog's shape,
|
||||
for FreezeWatchdog's reason: one notification per episode, not one per
|
||||
cycle for a quarter of an hour.
|
||||
"""
|
||||
g = self.peak_guard
|
||||
limited = bool(g is not None and g.floor_limited)
|
||||
was, self._peak_floor_limited = self._peak_floor_limited, limited
|
||||
if not limited or was:
|
||||
return
|
||||
# No prefix: `reason` already opens with PEAK GUARD FLOOR-LIMITED, and
|
||||
# a second copy is the kind of stutter that makes a 40-line action log
|
||||
# read like boilerplate. The saturated path needs its prefix because its
|
||||
# reason carries the word in the middle of a sentence, not at the front.
|
||||
self.log_event(g.reason)
|
||||
_LOG.error(
|
||||
"SAFETY-24 - %s. The controller is STILL RUNNING and charging is "
|
||||
"still blocked, but it is not discharging to hold this quarter, so "
|
||||
"the quarter will set or raise the month's billed capacity peak. "
|
||||
"Shed load, or lower peak_soc_floor if this pack can afford it.",
|
||||
g.reason)
|
||||
# A fixed notification_id, and a DIFFERENT one from every other alarm
|
||||
# here - check_meter_frozen() gives the reasoning. A battery at its
|
||||
# energy floor is not a saturated inverter and is not a frozen meter,
|
||||
# and an operator who has to dismiss three identical-looking cards
|
||||
# learns to dismiss the one that mattered.
|
||||
await self.hass.call("persistent_notification", "create", {
|
||||
"notification_id": "goodwe_peak_soc_floor",
|
||||
"title": "GoodWe: the capacity-peak guard has run out of battery",
|
||||
"message": (
|
||||
f"{g.reason}.\n\nTHIS QUARTER WILL GO OVER THE "
|
||||
f"{g.ceiling_w:.0f} W ceiling and will set or raise the "
|
||||
f"month's billed capaciteitstarief peak, because the peak guard "
|
||||
f"is not allowed to discharge any further: {g.soc_floor_reason}."
|
||||
f" This is not a controller fault - it is the EMS-side energy "
|
||||
f"floor (peak_soc_floor) doing what it is set to do, and it sits "
|
||||
f"deliberately above the pack's own BMS cut-out. Charging stays "
|
||||
f"blocked. Shedding load is the only thing that changes the bill "
|
||||
f"now; if this pack can afford a deeper discharge, lower "
|
||||
f"peak_soc_floor."),
|
||||
})
|
||||
|
||||
async def check_meter_frozen(self) -> None:
|
||||
"""SAFETY-18. Alarm on a meter that answers forever without changing.
|
||||
|
||||
@@ -1116,6 +1212,13 @@ class Controller:
|
||||
elif _pg.saturated:
|
||||
out.append({"ok": False, "warn": False,
|
||||
"text": "PEAK GUARD SATURATED - " + _pg.reason})
|
||||
elif _pg.floor_limited:
|
||||
# SAFETY-24. NOT ok, like saturation: in both states the money
|
||||
# is going to be spent and a human is the only actuator left. A
|
||||
# separate row from saturation because the two ask for opposite
|
||||
# things - see check_peak_floor_limited().
|
||||
out.append({"ok": False, "warn": False,
|
||||
"text": _pg.explain()})
|
||||
elif _pg.blind:
|
||||
out.append({"ok": False, "warn": True, "text": _pg.explain()})
|
||||
else:
|
||||
|
||||