SAFETY-07 can command a discharge to hold a billed quarter down, and nothing below it consulted the state of charge. On the 2026-08-20 replay it asks for 878 Wh in a day. Relying on the BMS is not absurd - it is a real floor and it works - but it is the pack's protection rather than the operator's, and a month of aggressive quarters leaves the battery repeatedly at that cut-out with no EMS-side record of why. The first symptom is a pack never available when wanted, which is indistinguishable from the SoC drift MAINT-01 exists to correct. decide() now takes soc and soc_floor, both required and neither defaulted, and discharge_permitted() is the one place the question is answered. Above the floor nothing changes. At or below it the guard files a 0 W floor instead of a sized one - one-directional, so charging stays blocked and no discharge is capped - and reports floor_limited with the reason it bound. It is not a trip: every stop in 11.2's table still outranks the claim, and the floor is never negative, so 9.1's asymmetry survives as a property of the object (0 negative floors over 1296 swept combinations, SoC included). The SoC is graded only after `wanted > 0` is established, so it is never evaluated where it governs nothing. An unreadable SoC is floor-limited, not a full battery - a full battery is exactly the value that would disarm the floor, and this project shipped that defaulting once already. Failing to shave is not silent: one notification per episode (goodwe_peak_soc_floor), distinct from the saturation alarm because the two ask for opposite operator actions, plus its own status row and an action-log line. Verified by replay. The 2026-08-20 capture is driven against a modelled pack sized from the day's own measured appetite, so it genuinely exhausts: without the floor it reaches the BMS cut-out and holds there for 1227 guard cycles; with it the pack stops at 20.0 % and never touches the BMS. The energy withheld equals the energy between the two floors to within one cycle at the rail. The honest half is reported too - the worst quarter goes 4338 W -> 5030 W, because a floor-limited guard shaves less on purpose. Two new options, mirrored once in peakguard.PEAK_OPTION_DEFAULTS (TARIFF-02's pattern), imported by validate.py and main.py rather than typed as literals and pinned to config.yaml by a check that reads the file - so CFG-03 still tracks three places. validate.py rule 8 refuses peak_soc_floor <= bms_soc_floor at startup, in CFG-01/MAINT-04's manner. maintenance_soc_floor is deliberately not reused and not renamed: it is a drain target, not a spend limit, and the rename is recorded as a decision to revisit if a third floor appears. Eleven mutations of the shipped source were run against the checks; all eleven go red and there are no survivors. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_015VXjA3LWccN1rJsk3okyPC
This commit is contained in:
co-authored by
Claude Opus 5
parent
e7c95bfd8a
commit
e709554857
@@ -420,7 +420,7 @@ help - see "Why the tuning is what it is".
|
||||
| `maintenance_start_hour` | 10 | Hour of day a due cycle begins |
|
||||
| `maintenance_discharge_w` | 2000 | Drain rate (exports the surplus). Above `max_w` it is **clamped** to `max_w` — the drain phase SETs the setpoint and the arbiter bounds it, saying so on the status page (`limited by supervised(max_w)`). Warned about, not refused: the cycle still completes, just slower |
|
||||
| `maintenance_charge_w` | 2000 | Charge ceiling, capped again by peak headroom. Must stay **at or below `max_w`** or the cheap-window shaping (`hi = -maintenance_charge_w`) contradicts the supervised limit (`lo = -max_w`), the arbiter resolves it to **0 W**, and maintenance silently never charges in a cheap window — **the add-on refuses to start** |
|
||||
| `maintenance_soc_floor` | 11 | Drain target — stay just above the inverter's own floor |
|
||||
| `maintenance_soc_floor` | 11 | Drain target — stay just above the inverter's own floor. ⚠️ **This is not `peak_soc_floor`.** It is the depth the monthly recalibration deliberately goes to, once, on purpose; `peak_soc_floor` is the depth a money-saving discharge may never reach on any day. The right values differ (11 vs 20 as shipped), which is why they are two keys |
|
||||
| `maintenance_soc_target` | 99 | Charge target |
|
||||
| `maintenance_hold_min` | 120 | Hold at full so the BMS can balance |
|
||||
|
||||
@@ -430,6 +430,8 @@ help - see "Why the tuning is what it is".
|
||||
|---|---|
|
||||
| `peak_forecast_entity` | Quarter-hour demand forecast, for capacity-tariff markets. Empty = no cap |
|
||||
| `peak_cap_w` | The site's capacity-tariff target |
|
||||
| `peak_soc_floor` (20) | **The percent below which the capacity-peak guard will not discharge the battery.** Not optional and not the same thing as `maintenance_soc_floor` — see below |
|
||||
| `bms_soc_floor` (10) | The pack's **own** cut-out percent, the number the BMS enforces whatever you set above. `peak_soc_floor` must be **strictly above** it or the add-on refuses to start |
|
||||
| `price_now_entity`, `price_avg_entity` | Dynamic tariff. Empty = never force a paid grid top-up |
|
||||
|
||||
On a capacity-tariff site the maintenance charge is capped by the headroom left
|
||||
@@ -530,11 +532,46 @@ projected over — raises one notification (`goodwe_peak_saturated`), because th
|
||||
is the one state where the money will be spent and shedding load is the only
|
||||
thing left that changes the bill.
|
||||
|
||||
**No new option.** The ceiling is `peak_cap_w`, which already shipped. The
|
||||
**No new option for the CEILING.** It is `peak_cap_w`, which already shipped. The
|
||||
coverage threshold is `meter_max_age_s`, the freeze predicate is
|
||||
`meter_freeze_s`, and the achievable discharge comes from `max_w` and the device
|
||||
rating — every one of them a key that already exists.
|
||||
|
||||
#### The energy floor under the forced discharge (`peak_soc_floor`)
|
||||
|
||||
The guard above can **command a discharge**, and until SAFETY-24 nothing in the
|
||||
add-on bounded how far down it took the pack — the BMS was the only backstop.
|
||||
On the 2026-08-20 replay the guard asks for **878 Wh in a day**.
|
||||
|
||||
That is not absurd: the BMS floor is real and it works. But it is *the pack's*
|
||||
protection, not *yours*. A month of aggressive quarters can leave the battery
|
||||
repeatedly parked at that cut-out with no record on this side of why, and the
|
||||
first symptom — a battery that is never available when you want it — looks
|
||||
exactly like the SoC drift the monthly maintenance cycle exists to correct.
|
||||
|
||||
- **`peak_soc_floor` (20 %)** is where the forced discharge stops. Below it the
|
||||
guard files a **0 W** floor instead of a sized one: charging stays blocked
|
||||
(that can only ever lower your offtake), and no further discharge is asked for.
|
||||
- **It does not stop the ordinary self-consumption loop.** That loop still has no
|
||||
SoC guard of its own. This bounds what the *peak guard* spends for money.
|
||||
- **When it binds you are told**, once per episode, with notification
|
||||
`goodwe_peak_soc_floor` and a status-page row reading `PEAK GUARD
|
||||
FLOOR-LIMITED`: the quarter **will** go over the ceiling, so shedding load is
|
||||
the only thing left that changes the bill. Failing to shave is never silent —
|
||||
the euro figure is the whole point of the guard.
|
||||
- **An unreadable SoC is treated as floor-limited, not as a full battery.** A
|
||||
full battery is exactly the value that would disarm this floor.
|
||||
- **`bms_soc_floor` (10 %)** is the pack's own cut-out — register `0x0560` on the
|
||||
reference GW5000S-BP, consistent with DoD 90. It exists so the add-on can
|
||||
**refuse to start** when `peak_soc_floor` is at or below it: such a floor can
|
||||
never be the thing that stops the discharge, and a guard that advertises a
|
||||
backstop it does not have is the one thing this project will not ship. Equal is
|
||||
refused too — equal buys zero margin.
|
||||
|
||||
Why 20 %: the reference pack is 13.8 kWh usable, so 10 points of margin over the
|
||||
BMS cut-out is about 1.6× the guard's worst measured day. If your pack is
|
||||
smaller, or your quarters are worse, raise it.
|
||||
|
||||
### The winding-loop alarm (the output clamp)
|
||||
|
||||
Every setpoint this add-on writes is clamped to `max_w` before it leaves the
|
||||
|
||||