SAFETY-04 review fixes: the freeze deadlocked, the bound was too loose
S-1. The frozen branch admitted a correction only if it shrank |i_w|. That is unsatisfiable for BOTH signs of error whenever |correction| > 2*|i_w|, i.e. whenever the integrator is near zero, so the loop stopped moving and the freeze could never clear - it clears when the inverter tracks, and not tracking is what saturation means. Measured: 0 W held into a 2 kW import indefinitely, where release/1.0 recovers on the next cycle. Re-encoded as the same asymmetric rule the output freeze has always used: may not wind further in the direction it is already pushing, may fall, cross zero or reverse. Same interpretation, an encoding that cannot deadlock. S-2. integrator_max_w defaulted to 1.5x max_w, which ADDED windup: in release/1.0 the accumulator was the post-clamp command and could never pass the rail. Default is now "follow max_w" (config 0 = unset). Measured on the 4000 W load-drop sim, first cycle after the drop: 1000 W at the new default, 1800 W at 3000. DOCS row inverted - the useful direction is below max_w, and the 14 768 W anecdote is a vendor controller, not evidence about this code. S-3. The claim that i_w=None preserved release/1.0 exactly was false, because the S-1 gate ran regardless of seeding. It is true again, and now asserted rather than asserted-about: 3024-case exhaustive comparison against a transcription of the old law, over both freeze states, both signs and either side of the deadband. Added the carried-i_w convergence/overshoot sim that the shipped configuration was missing. S-4. Cycles are distinct meter values, not seconds: cycle() runs only when the meter reading changes, so the window has no wall-clock bound. Comment and DOCS corrected; the stall is detection latency, not a windup hazard, because the same condition stalls the whole loop. test_control.py: 33 -> 41 checks, all passing. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
This commit is contained in:
co-authored by
Claude Opus 5
parent
37bac79ad8
commit
e46175559b
@@ -60,7 +60,7 @@ phase having charged nothing.
|
||||
| `step_w` | 10 | Quantisation |
|
||||
| `saturation_w` | 500 | Divergence that counts as "the inverter is at a limit" |
|
||||
| `saturation_cycles` | 3 | How many consecutive cycles before freezing. **Do not set to 1** |
|
||||
| `integrator_max_w` | 3000 | Bound on the loop's accumulator, separate from `max_w`. Caps how much stale error can be waiting to unwind when the sign flips. **Keep it above `max_w`, and do not set it equal to `max_w`** |
|
||||
| `integrator_max_w` | 0 | Bound on the loop's accumulator, and 0 means "same as `max_w`". Caps how much stale error can be waiting to unwind when the sign flips. **Do not raise it above `max_w`** - the output clamp already bounds what is commanded, so the only thing extra headroom buys is more cycles of wrong-direction power after every saturation event. Lowering it below `max_w` is the useful direction |
|
||||
| `heartbeat_s` | 10 | Refresh interval; must stay well under the firmware watchdog |
|
||||
| `stale_input_s` | 15 | How long inputs may be missing before commanding 0 W |
|
||||
| `auto_start` | false | Start controlling on boot (only after commissioning) |
|
||||
|
||||