SAFETY-47: what a shadow run can show, and the watts on its status row
checks / unit (pull_request) Successful in 7m48s

Not a leak and not a write-path defect. Shadow mode's safety is intact -
the substitution, the re-seed, the authorisation gate and the clamp are
untouched. What was wrong is what three merged documents SAY a shadow run
can show you, and a number on the status row that can be 6.61x what a live
controller would command.

SHADOW MODE CANNOT SURFACE A CLOSED-LOOP DEFECT, AND THE DOCUMENTS NOW SAY
SO. The battery is held at 0 W and the carried command is re-seeded to it,
so every measured input - the meter, the billed-quarter accumulator behind
it, the battery power, the SoC - describes a plant that did not respond. A
closed-loop defect is one whose stimulus IS that response. This is the same
property that makes shadow mode safe, so it is not a gap to close later:
the closed-loop answer comes from the closed-loop rig or from a live run.
SAFETY-10 §5 already conceded this for the grid-following loop. It was
never the loop leg's limitation; it is the general case.

THE "STRATEGIES ARE UNAFFECTED" EXEMPTION WAS TRUE UNTIL SAFETY-45 MERGED,
ONE COMMIT EARLIER. That card sizes the buy leg as min(asked, headroom)
with headroom = (900/remaining) x (ceiling - projected), and `projected`
reads the open quarter's accumulator - the meter - which is a function of
what the battery did earlier in that quarter. Measured on TEST-23 stage 3
at peak_cap_w 1500 / house 1200 / max_w 2000, one hour at 5 s:

  SAFETY-45's limit cycle  NOT visible. 28 onsets live vs 1; grid
                           -455.5..+3200.0 W vs flat at the 1200 W house;
                           guard engaged 410/720 cycles vs 0/720.
  SAFETY-46's SoC churn    NOT visible. The SoC moves 0.000000000 pp.
  TARIFF-14's wrong hour   VISIBLE, and it is the only one: which hour, at
                           what price, clearing what spread - identical on
                           720 of 720 charging cycles at a binding cap.

The exemption narrows to exactly what survives: WHICH hour a strategy picks
and WHY are unaffected; HOW HARD it trades is not. The peak guard's ceiling
and reasons are worth reading from a shadow run; its ENGAGEMENTS are not.

THE NUMBER IS CAVEATED, NOT RE-COMPUTED, AND THAT IS THE DECISION. The
arithmetic is not wrong - 900/remaining is correct for a meter genuinely
under the ceiling, and in shadow the meter genuinely is. It is the right
answer to a question nobody asked. Both surfaces now introduce the watts as
what would have been commanded ON THIS CYCLE, in every state, and carry
shadow.SIZED_FROM_METER whenever a measured billed quarter sized them.
Rejected, and recorded in the decision doc: re-computing it (the recorded
decision would no longer be the decision the shipped path reached, while the
arbiter, clamp, SAFETY-28 gate, log and MQTT all ran on the real one - a
second controller everywhere except the wire); recording nothing (blanks the
row exactly when arbitrage is trading, and the log's edge key is the watts);
and recording the unsized ask beside it (a second number, no warning, and at
the shipped 3500/2000 both figures read 2000 W).

"UPPER BOUND" AND NOT "SMALLER", AND THE DIFFERENCE WAS MEASURED. Charging
only adds offtake, so the shadow size is >= the live size with EQUALITY at
the start of every quarter. Pairwise over 3600 charging cycles in five
configurations: 0 below, 730 exactly equal. The first draft said "smaller",
which would have been false on every one of those 730.

AND THE PREDICATE IS NOT KEYED ON WHETHER THE TRADE WAS CAPPED. arbitrage's
own sentence says "SIZED BY THE CAPACITY-TARIFF GUARD" only when the
headroom came out below the ask - in a shadow run, the START of the quarter,
where the two runs agree to the float. By the end, 900/remaining has
multiplied the headroom past the ask, the trade is not capped, the sentence
is silent, and the record is at its most wrong. A caveat keyed on it would
be quietest exactly where it is needed loudest.

SAFETY-10 §6's COMMITTED EVIDENCE COULD NEVER HAVE FAILED, FOR TWO
INDEPENDENT REASONS, AND CLOSING EITHER ALONE CLOSES NOTHING. Its fixture is
peak_cap_w 15000 against a 350 W house, so the guard never engages and the
sizing is inert - the harness's own comment says so. AND every identity row
reads the FIRST charging sample, where at elapsed=0 the projection IS the
held level and the two runs agree to the float even at a cap that does bind.
Measured: widening the fixture alone leaves that comparison passing. That
second reason is a new shape for MUTATION.md's habit-4 list - an INDEX, not
a fixture - and it is recorded there as the twelfth instance. §6 is re-taken
at a binding cap across the whole run: 716 of 720 charging cycles differ,
headroom 300.0..54000.0 W in shadow against 299.9..307.8 W live, recorded
-2000.0 W against a live -302.4 W.

THE GRADER IS test_arbitrage.py PART 3d, beside SAFETY-45's own closed-loop
regression and built on the same s45_loop() harness, so the runs differ in
one argument. Three lines stand in for _write_unit()'s substitution and
_shadow_settle()'s record and re-seed, marked as a transcription;
test_clamp.py part 8 remains the check on the shipped placement. The section
carries its own precondition into every check: a mutation that stopped
either run trading made it raise on its first min(), kill the file and
report ZERO reds - FCST-06's shape, driven rather than imagined.

AND THE FIX'S OWN FIRST DRAFT CARRIED THE SAME DEFECT. Deleting the caveat
from the action-log line left all 29 files green, because the sentence was
an f-string inside _shadow_settle() and the only suite that drives it uses a
meter_source:off fixture where no arbitrage decision exists. It is
shadow.log_line() now, for the reason words() is a function.

14 mutations, no survivors; M13 and M14 are +0 B and were confirmed on disk
by sha256 with every run purged. M14's first form was aimed at the wrong
direction and correctly survived - min->max makes the shadow record larger,
which is still an upper bound. All 29 check files green.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
This commit is contained in:
glenn schrooyen
2026-09-15 01:26:57 +02:00
co-authored by Claude Opus 5
parent e6da478f87
commit e3ccd9f6ea
10 changed files with 1446 additions and 64 deletions
+53 -6
View File
@@ -842,6 +842,18 @@ class Controller:
# how a shadow run starts telling an operator a number nothing is
# doing.
self.shadow_would_w = None
# SAFETY-47. Was the number above SIZED FROM THE BILLED-QUARTER METER
# on the cycle it was recorded? ⚠️ IT IS RECORDED WHERE THE DECISION
# WAS TAKEN, NOT RE-DERIVED WHERE THE PAGE IS RENDERED. The status page
# runs on its own task and `self.peak_guard` has moved on by then, so a
# page that asked the question again would be answering it about a
# different cycle from the one whose watts it is displaying - which is
# the same two-facts-one-field defect the comment above this one is
# about. ⚠️ False AND NOT None BEFORE THE FIRST SHADOW CYCLE, unlike
# the field above: this one is a claim ABOUT a number, and there is no
# number yet, so the honest value is "nothing to disclose". The row's
# `would_w is None` branch renders no watts at all there.
self.shadow_sized_from_meter = False
# Edge state for the action log, both of them. `_shadow_was` is None
# until the first cycle, so an install that comes up IN shadow mode
# says so in the log it will be read from rather than leaving the
@@ -923,6 +935,12 @@ class Controller:
# None (startup) or the PREVIOUS cycle's decision (an input hold), and
# the status row rendered all three identically.
self.arb_at = None
# SAFETY-45/47. The billed-quarter charging headroom the arbitrage step
# was handed on the cycle above, or None when nothing measured it. It
# is CARRIED rather than recomputed for `arbitrage.sized_from_meter()`,
# because `self.peak_guard` is a different cycle's decision by the time
# the status page renders.
self.arb_headroom_w = None
# TARIFF-11. When the most recent cycle() STARTED. `arb_at < cycle_at`
# is the exact, derived statement of "the latest cycle did not get as
# far as the arbitrage step", which is the fact the *Arbitrage* row
@@ -2818,9 +2836,16 @@ class Controller:
# `arb_at` is then the age the status row reports rather than a
# decision presented as current.
self.arb, self.arb_at = None, now
self.arb_headroom_w = None
if arbitrage.enabled(self.o):
floor_pct, ceiling_pct = arbitrage.soc_bounds(self.o)
charge_w, discharge_w = self.trade_power_w(floor_pct, ceiling_pct)
# SAFETY-47. HOISTED OUT OF THE CALL, NOT COPIED. One evaluation of
# the shipped expression feeds both the sizing below and
# `arbitrage.sized_from_meter()` in `_shadow_settle()`, so the
# caveat on the recorded watts can never be answered from a
# different cycle's guard than the watts were.
self.arb_headroom_w = peakguard.charge_headroom_w(self.peak_guard)
self.arb = arbitrage.decide(
self.fresh_tariff_plan(now), now,
peak_guard_active=arbitrage.guard_state(self.peak_guard),
@@ -2839,7 +2864,7 @@ class Controller:
# peak block's conclusion, ~50 lines up, so it must stay after
# it. Evaluated earlier it would size this quarter's trade from
# the previous cycle's quarter.
charge_headroom_w=peakguard.charge_headroom_w(self.peak_guard),
charge_headroom_w=self.arb_headroom_w,
# The emptiest pack again, and for the sell side that is the
# right reduction. ⚠️ THE BUY SIDE WANTS THE FULLEST, and there
# is one `soc` argument - `pack_floor_soc` names that residual
@@ -3424,20 +3449,37 @@ class Controller:
"%+.0f W that was standing on the wire.", shadow.WIRE_W)
if not engaged:
self.shadow_would_w = None
self.shadow_sized_from_meter = False
self._shadow_winner = None
return
self.shadow_would_w = float(resolution.target_w)
# SAFETY-47. ⚠️ NO LOGIC HERE, DELIBERATELY. All three rungs - the
# arbiter's winner, the leg being a CHARGE, and the headroom having
# been MEASURED - live inside `arbitrage.sized_from_meter()`, which
# says why, including why it is NOT keyed on whether the trade was
# capped. A rung written at a call site is a rung no check can reach
# with the other two clear, which is TEST-16's rule.
self.shadow_sized_from_meter = arbitrage.sized_from_meter(
self.arb, self.arb_headroom_w, winner=resolution.winner)
# ⚠️ THE WINNER AND THE ROUNDED WATTS, NOT THE WATTS ALONE. A decision
# that moves from the loop to the peak guard at the same number is a
# different decision and the operator needs the line; a loop target
# that wanders by a watt is not, and 15 s of those would be the whole
# log.
edge = (resolution.winner, round(float(resolution.target_w)))
# ⚠️ SAFETY-47 ADDS THE CAVEAT FLAG TO THE EDGE. The same winner at the
# same watts with and without the caveat are two different claims about
# the same number, and an edge key blind to that would print the first
# one and silently keep it standing. It cannot flood: the flag only
# moves when arbitrage starts or stops owning the resolution, or when
# the guard starts or stops measuring the quarter, and both of those
# move the winner or the watts as well on every cycle measured.
edge = (resolution.winner, round(float(resolution.target_w)),
self.shadow_sized_from_meter)
if edge != self._shadow_winner:
self._shadow_winner = edge
self.log_event(
f"SHADOW: would have commanded {resolution.target_w:+.0f} W - "
+ resolution.explain())
self.log_event(shadow.log_line(
would_w=resolution.target_w, reason=resolution.explain(),
sized_from_meter=self.shadow_sized_from_meter))
self.target = shadow.WIRE_W
for inv in self.inverters:
inv.target = shadow.WIRE_W
@@ -4865,7 +4907,12 @@ class Controller:
# learn something is a surface you have to already know about.
("Shadow mode", shadow.words(
self.o, control_started=self.auto,
would_w=self.shadow_would_w, reason=self.reason)),
would_w=self.shadow_would_w,
# SAFETY-47. THE FLAG THE CYCLE RECORDED, NOT ONE DERIVED HERE
# - the page runs on its own task and `self.peak_guard` has
# moved on. See `Controller.__init__`.
sized_from_meter=self.shadow_sized_from_meter,
reason=self.reason)),
("Why", self.reason),
("Maintenance phase", self.maint.phase if len(self.inverters) <= 1
else f"{self.maint.phase} ({self.maint_unit.name})"),