SAFETY-83: peak guard outranks the maintenance drain at N=1
checks / unit (pull_request) Successful in 16m54s
infra-pin / fresh (pull_request) Successful in 1s

At N=1 the drain is the site SET at P_MAINTENANCE (60), so the peak floor
(P_PEAK, 50) was not applied and the house imported what the drain left.
Where the floor asks for more than the drain rate, main.py now refiles the
peak claim at P_MAINTENANCE, so it wins; safety SETs still park everything.
Nothing else changes: safety78_identity --diff against 35cdffe changes only
cycles where the guard wanted more than the drain; N=2 is byte-identical.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
This commit is contained in:
2026-09-29 22:40:14 +02:00
co-authored by Claude Opus 5.5
parent 35cdffe766
commit d77f1b1fdf
8 changed files with 402 additions and 27 deletions
+3 -1
View File
@@ -1626,7 +1626,7 @@ help - see "Why the tuning is what it is".
| `maintenance_enabled` | false | Enable the monthly cycle |
| `maintenance_interval_days` | 28 | Minimum gap between cycles |
| `maintenance_start_hour` | 10 | Hour of day a due cycle begins |
| `maintenance_discharge_w` | 2000 | Drain rate (exports the surplus). Above `max_w` it is **clamped** to `max_w` — the drain phase SETs the setpoint and the arbiter bounds it, saying so on the status page (`limited by supervised(max_w)`). Warned about, not refused: the cycle still completes, just slower |
| `maintenance_discharge_w` | 2000 | Drain rate (exports the surplus). The peak guard may ask for more (SAFETY-83). Above `max_w` it is **clamped** to `max_w` — the drain phase SETs the setpoint and the arbiter bounds it, saying so on the status page (`limited by supervised(max_w)`). Warned about, not refused: the cycle still completes, just slower |
| `maintenance_charge_w` | 2000 | Charge ceiling, capped again by peak headroom. Must stay **at or below `max_w`** or the cheap-window shaping (`hi = -maintenance_charge_w`) contradicts the supervised limit (`lo = -max_w`), the arbiter resolves it to **0 W**, and maintenance silently never charges in a cheap window — **the add-on refuses to start** |
| `maintenance_soc_floor` | 11 | Drain target — stay just above the inverter's own floor. ⚠️ **This is not `peak_soc_floor`.** It is the depth the monthly recalibration deliberately goes to, once, on purpose; `peak_soc_floor` is the depth a money-saving discharge may never reach on any day. The right values differ (11 vs 20 as shipped), which is why they are two keys |
| `maintenance_soc_target` | 99 | Charge target |
@@ -1651,6 +1651,8 @@ maintenance schedule.
With two or more batteries, the one being emptied gives its drain rate and the
others only add power when the house needs more; none charges while it drains
(SAFETY-78). Below the drain rate the rest is exported, as with one battery.
If the house would still go over the peak limit, the battery being emptied
gives more than its drain rate, with one battery too (SAFETY-83).