MAINT-15: the balancing hold ends on time with no SoC reading
HOLD's time check moves into Maintenance._hold(), used by step() and
_no_soc(). A hold that loses its SoC now ends at hold_min, writes
last_completed and logs the same COMPLETE line. The 15 min HOLD line says
the hold still ends at its normal time. Behaviour with a reading is
unchanged (differential trace against db9e231).
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
This commit is contained in:
@@ -541,11 +541,29 @@ class Maintenance:
|
||||
events.append(msg)
|
||||
return MaintResult(IDLE, True, 0.0, False, events, failed=kind)
|
||||
|
||||
def _hold(self, now: datetime, events: list) -> MaintResult:
|
||||
"""HOLD for one tick, with or without a SoC reading (MAINT-15).
|
||||
|
||||
HOLD needs no level to end: it is reached only after the charge counted
|
||||
as done (MAINT-13/14), so its end is a time check and nothing else.
|
||||
"""
|
||||
elapsed = self._elapsed_min(now)
|
||||
if elapsed >= self.cfg.hold_min:
|
||||
self.store.set_time("last_completed", now)
|
||||
self._enter(IDLE, now, events,
|
||||
f"maintenance: cycle COMPLETE ({elapsed:.0f} min hold) "
|
||||
"- handing back to the loop")
|
||||
return MaintResult(IDLE, False, None, False, events)
|
||||
# 0 W, not "do nothing": commanding zero is what stops the loop
|
||||
# pulling the pack straight back down the moment it is full, which
|
||||
# is exactly when the BMS needs it parked at the top.
|
||||
return MaintResult(HOLD, True, 0.0, False, events)
|
||||
|
||||
def _no_soc(self, now: datetime, phase: str, gate_open: bool,
|
||||
events: list) -> MaintResult:
|
||||
"""MAINT-14: one tick of a pack in a moving phase with no SoC reading.
|
||||
|
||||
HOLD is unchanged (0 W). DRAIN holds at 0 W, like HOLD, and its 12 h
|
||||
HOLD stays at 0 W and ends at its normal time (MAINT-15). DRAIN holds at 0 W, like HOLD, and its 12 h
|
||||
timeout still runs. CHARGE keeps its timeout and wall backstop: out of
|
||||
time is a failure, except when the last SoC seen was within
|
||||
CHARGE_NEAR_FULL_PCT of the target, which counts as done (MAINT-13).
|
||||
@@ -563,7 +581,7 @@ class Maintenance:
|
||||
if (not self._nosoc_said and (now - self._nosoc_since).total_seconds()
|
||||
>= NOSOC_NOTE_MIN * 60):
|
||||
self._nosoc_said = True
|
||||
tail = ("The hold waits for the level to come back."
|
||||
tail = ("The hold still ends at its normal time."
|
||||
if phase == HOLD else
|
||||
f"The time limit of the {phase} still applies.")
|
||||
msg = (f"maintenance: no battery level for {NOSOC_NOTE_MIN} min. "
|
||||
@@ -571,7 +589,7 @@ class Maintenance:
|
||||
_LOG.warning("%s", msg)
|
||||
events.append(msg)
|
||||
if phase == HOLD:
|
||||
return MaintResult(HOLD, True, 0.0, False, events)
|
||||
return self._hold(now, events)
|
||||
elapsed = self._elapsed_min(now)
|
||||
if phase == DRAIN:
|
||||
if elapsed > DRAIN_TIMEOUT_MIN:
|
||||
@@ -736,16 +754,7 @@ class Maintenance:
|
||||
return MaintResult(CHARGE, False, None, True, events)
|
||||
|
||||
if phase == HOLD:
|
||||
if elapsed >= self.cfg.hold_min:
|
||||
self.store.set_time("last_completed", now)
|
||||
self._enter(IDLE, now, events,
|
||||
f"maintenance: cycle COMPLETE ({elapsed:.0f} min hold) "
|
||||
"- handing back to the loop")
|
||||
return MaintResult(IDLE, False, None, False, events)
|
||||
# 0 W, not "do nothing": commanding zero is what stops the loop
|
||||
# pulling the pack straight back down the moment it is full, which
|
||||
# is exactly when the BMS needs it parked at the top.
|
||||
return MaintResult(HOLD, True, 0.0, False, events)
|
||||
return self._hold(now, events)
|
||||
|
||||
_LOG.error("maintenance: unknown phase %r, forcing idle", phase)
|
||||
events += self.abort(now, f"unknown phase {phase!r}")
|
||||
|
||||