MAINT-15: the balancing hold ends on time with no SoC reading
HOLD's time check moves into Maintenance._hold(), used by step() and
_no_soc(). A hold that loses its SoC now ends at hold_min, writes
last_completed and logs the same COMPLETE line. The 15 min HOLD line says
the hold still ends at its normal time. Behaviour with a reading is
unchanged (differential trace against db9e231).
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
This commit is contained in:
@@ -58,10 +58,7 @@ allows discharge.
|
||||
|
||||
## What this does not cover
|
||||
|
||||
- **HOLD with no SoC** still holds 0 W and, as before, does not end while the
|
||||
reading is missing: its time check sits behind the same early return. A HOLD
|
||||
needs no level to end, so this is a candidate follow-up, not part of this fix. It is card MAINT-15. The "no battery level" line in
|
||||
HOLD says only that the hold waits for the level.
|
||||
- **HOLD with no SoC**: closed by MAINT-15 (`MAINT-15-hold-ends-without-soc.md`).
|
||||
- It does not tell the operator why the reading is missing (sensor, register,
|
||||
link). It does not reuse the stale-input gate; it is the cycle's own rule.
|
||||
- The charge itself is still driven by the control loop, which has its own
|
||||
|
||||
@@ -0,0 +1,43 @@
|
||||
# MAINT-15 - the balancing hold ends on time with no SoC reading
|
||||
|
||||
**Status: for review.** Tests: `test_maint15.py`. No option added.
|
||||
|
||||
**The fault.** `step()` sent every tick with no SoC to `_no_soc()`, and for
|
||||
HOLD that returned 0 W without the time check. A hold that lost its reading
|
||||
never ended: `last_completed` was never written and the next due date never
|
||||
moved. Harmless for power (0 W), but the cycle was stuck. This was left open
|
||||
in MAINT-14.
|
||||
|
||||
## Rule
|
||||
|
||||
1. **HOLD ends at `hold_min` whether or not there is a reading.** One helper,
|
||||
`Maintenance._hold()`, holds the time check and is used by both paths. When
|
||||
the time is up it writes `last_completed`, goes IDLE and logs the same
|
||||
"cycle COMPLETE" line. Before the time is up it commands 0 W as before.
|
||||
2. **Text.** The 15-min "no battery level" line in HOLD now reads "The hold
|
||||
still ends at its normal time." Still once per episode.
|
||||
|
||||
## Why
|
||||
|
||||
HOLD is reached only after the charge counted as done. Every entry into HOLD
|
||||
is in `step()` or `_no_soc()` and follows a charge that reached the target,
|
||||
stalled near full (MAINT-13) or timed out near full (MAINT-13/14). Nothing else
|
||||
sets the phase to HOLD (`_enter(HOLD` has four call sites, all after a done
|
||||
charge). The hold is a wait for the BMS to balance; it never needed the level.
|
||||
So a hold that ends with no reading is a completed cycle. The "cycle COMPLETE"
|
||||
line is true without a reading: it names minutes of hold, not a level.
|
||||
|
||||
## Cost
|
||||
|
||||
- If the level was lost during the hold, the cycle is recorded as complete
|
||||
without anyone seeing the final level. The charge had counted as done, so this
|
||||
is the same trust MAINT-14 already gives a charge that ends with no reading.
|
||||
|
||||
## What this does not cover
|
||||
|
||||
- It does not check that the pack is still full at the end of the hold.
|
||||
- It does not say why the reading was lost.
|
||||
- With a reading, nothing changes (proved by a differential trace against
|
||||
release/1.0 in `test_maint15.py`).
|
||||
- A state file written by an older version with `phase: hold` loads and ends on
|
||||
time; the file is not changed in format.
|
||||