SAFETY-95: a maintenance drain that ends hands back smoothly (N>=2)
When a battery's drain ended (done, Off, timeout, abort, stale link, refusal), its drain floor stayed in the site target and landed on the others: B 0 -> +1600 W in one cycle at a 1200 W house, exporting; under a solar surplus B gave into the export. Now, on that cycle, the loop starts from what the others stood at plus the battery's new command, raised to the house's own point when the house needs more (never above last cycle's start). While the battery settles, the loop counts the batteries at its start instead of chasing the drain's tail on the meter. Then one slew step a cycle. N=1 is unchanged. test_safety95.py; DECISIONS/SAFETY-95-drain-end.md; one DOCS line. test_modes.py: opt11 n2_maint re-pinned on purpose (its drain ends by a refusal at 1655 s; B now stays at the house's 1420 W instead of 2500 W). Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
This commit is contained in:
co-authored by
Claude Opus 5.5
parent
b2f55732b6
commit
bdec66e97a
@@ -1702,6 +1702,9 @@ When a charge ends, the other batteries take over one slew step a cycle,
|
||||
and none starts charging from the grid (SAFETY-93).
|
||||
When a battery's link drops, the others take over one slew step a cycle,
|
||||
and control does not stall on the dropped battery's power (SAFETY-96).
|
||||
When a drain ends (done, Off, timeout, abort, link, refusal), the others
|
||||
cover the house at once but never take over its export; from there control
|
||||
moves one slew step a cycle (SAFETY-95).
|
||||
|
||||