# SAFETY-96 - a battery the loop cannot move does not freeze it
**Status: implemented 2026-10-06, for review.** Tests: `test_safety96.py`.
**The defect** (SAFETY-93 rig test). At N=2 the saturation freeze compares
the site target with the site sum of the readings. After A's link went
stale, A was out of the split but its reading (-2000 W, still charging) was
in the sum: "saturation freeze (800 W vs -1903 W)", B held at 1200 W for
~236 cycles until the circulation trip. After a charge timeout or Off at
6000 W the loop froze ~14 s at 800 W while A came out of its charge. At a
drop, B also took A's whole share in one step.
**The rule** (`main.py`, `_held_out_w()`, `_reseed_drop()`, N>=2 only).
A battery is held out of the freeze test, counted at its command instead of
its reading, while:
- it is out of the split (writes refused for `LINK_STALE_S`);
- its last write was refused (its board may have gone to 0 W on its own
watchdog);
- it settles after a step the loop did not make: a charge end (SAFETY-93:
HOLD, timeout, Off, refusal, stale link) or a rejoin (then every battery,
as the split is made again). Settling ends when its reading is within the
deadband of its command, or after `PLANT_SETTLE_DOWN_S` (23 s, the
measured plant settle).
Its real power is not lost and not counted twice: the meter sees it, and
the loop follows the meter. Only the freeze stops reading it as the loop's.
The freeze still fires on the other batteries' own lag and on unplaced
watts.
At a drop the battery's share leaves the loop's start point, so the others
take over one slew step a cycle. At a rejoin it enters at its reading.
**Not a drop.** A missing reading or a stale register stops the site
(`inputs_ok`), as before. A refused battery (SAFETY-73) stays in the sum:
it is asked ~0 W and reads ~0 W. A watchdog-stopped battery (SAFETY-02/30)
is pinned at 0 W and stays in the sum. New: no refusal is learned on a
battery whose writes are refused; its board going to 0 W is no refusal. Its
count is kept, not reset, so a link that refuses 1 write in 3 does not hide
a battery that really refuses (review).
**Before -> after** (2 x 2500 W, 10 s lag, 2 s meter; freeze cycles not
about the remaining battery's own lag):
| case | before | after |
|---|---|---|
| A drops while giving, A holds 1200 W | 128, B steps 1210 W | 0, B stays |
| A drops while charging, A holds -2000 W | 78 | 0 (circulation trip stays: 4 kW goes round) |
| A drops while charging, board to 0 W | 5 | 0 |
| A drops then comes back, A holds 1200 W | 46, grid +1.1 kW | 0, grid within 250 W |
| charge timeout at 6000 W | 7, B held at 400 W | 0, B climbs |
| A switched Off at 6000 W | 6, B held at 800 W | 0, B climbs |
| N=1, N=2 with no drop | | byte-identical |
**Not changed.** At a rejoin the allocator splits again at once (A 0 ->
1205, B 2410 -> 1205 W); the site total does not step. A battery that keeps
charging on its own after its link drops still trips the circulation check
(it is real circulation). A trade end (`_reseed_run_edge`) still starts
from the full site sum.
+2
View File
@@ -1700,6 +1700,8 @@ batteries the other one gives first. The hold still ends on its clock
(SAFETY-86). (SAFETY-86).
When a charge ends, the other batteries take over one slew step a cycle, When a charge ends, the other batteries take over one slew step a cycle,
and none starts charging from the grid (SAFETY-93). and none starts charging from the grid (SAFETY-93).
When a battery's link drops, the others take over one slew step a cycle,
and control does not stall on the dropped battery's power (SAFETY-96).
#### Capacity-tariff exposure of the grid-following loop #### Capacity-tariff exposure of the grid-following loop
+81
View File
@@ -1025,6 +1025,12 @@ class Controller:
# cycle, and those whose charge ended since the loop last ran. # cycle, and those whose charge ended since the loop last ran.
self._charging_was = frozenset() self._charging_was = frozenset()
self._charge_ended = frozenset() self._charge_ended = frozenset()
# SAFETY-96: last cycle's commandable batteries, this cycle's start
# point per battery where a reseed moved it, and batteries settling
# after a step the loop did not make ({name: since, monotonic}).
self._live_was = None
self._loop_start = {}
self._settle = {}
# Set by amain() once the transport is built, so the status page can show # Set by amain() once the transport is built, so the status page can show
# what only the transport knows (homewizard_local's unchanged_s). Stays # what only the transport knows (homewizard_local's unchanged_s). Stays
# None when P1 is off, or under a transport that has no such counter. # None when P1 is off, or under a transport that has no such counter.
@@ -1393,6 +1399,12 @@ class Controller:
self._unit_refusal_end( self._unit_refusal_end(
inv, "the battery takes power the other way") inv, "the battery takes power the other way")
continue continue
if inv.rejected_since is not None:
# SAFETY-96: its writes are refused, so its board may have
# gone to 0 W on its own; that is no refusal by the battery.
# The count is kept, as across a gap, so a link that refuses
# now and then does not hide a battery that does refuse.
continue
sign = self._gave_nothing(inv) sign = self._gave_nothing(inv)
if sign: if sign:
self._unit_refusal_start( self._unit_refusal_start(
@@ -2456,9 +2468,69 @@ class Controller:
continue continue
now_w = (float(res.setpoint_w or 0.0) if res.owns_setpoint now_w = (float(res.setpoint_w or 0.0) if res.owns_setpoint
else max(float(inv.target), 0.0)) else max(float(inv.target), 0.0))
if not inv.is_live(datetime.now(timezone.utc))[0]:
now_w = 0.0 # SAFETY-96: out of the split, it is sent 0 W
self.target += now_w - float(inv.target) self.target += now_w - float(inv.target)
# SAFETY-96: it settles from its charge to that command.
self._loop_start[inv.name] = now_w
self._settle[inv.name] = self._now_mono
self.i_w = self.target self.i_w = self.target
def _reseed_drop(self, live) -> None:
"""SAFETY-96, N>=2: a battery that drops out of the split (stale
link) leaves the loop's start point, so the others take over at one
slew step a cycle instead of taking its share at once. One that comes
back enters it at its reading, and every battery settles while the
split is made again (`_held_out_w`).
DECISIONS/SAFETY-96-dropped-battery.md.
"""
was, self._live_was = self._live_was, frozenset(live)
if len(self.inverters) < 2 or was is None or was == live:
return
for inv in self.inverters:
if inv.name in self._charge_ended:
continue # SAFETY-93's edge: `_reseed_charge_end()`
if inv.name in was and inv.name not in live:
now_w = 0.0
elif inv.name in live and inv.name not in was:
now_w = float(inv.batt)
# The split is made again, so every battery's command steps.
self._settle.update(
{u: self._now_mono for u in live})
else:
continue
self.target += now_w - float(inv.target)
self._loop_start[inv.name] = now_w
self.i_w = self.target
def _held_out_w(self, live) -> float:
"""SAFETY-96, N>=2: what to add to the site sum so that a battery
the loop cannot move right now counts at its command, not at its
reading. That is a battery out of the split, one whose writes are
refused, or one settling after a step the loop did not make (a charge
end, a rejoin) until its reading is within the deadband of its
command or PLANT_SETTLE_DOWN_S has passed. Its real power still
reaches the loop through the meter, so it is neither lost nor counted
twice; only the saturation freeze stops seeing it as the loop's.
"""
if len(self.inverters) < 2:
return 0.0
out = 0.0
for inv in self.inverters:
cmd = self._loop_start.get(inv.name, float(inv.target))
since = self._settle.get(inv.name)
age = (None if since is None or self._now_mono is None
else self._now_mono - since)
if since is not None and (
age is None or age >= _ctl.PLANT_SETTLE_DOWN_S
or (age > 0 and abs(float(inv.batt) - cmd)
< self.tuning.deadband_w)):
del self._settle[inv.name]
if (inv.name not in live or inv.rejected_since is not None
or inv.name in self._settle):
out += cmd - float(inv.batt)
return out
def _mode_fault_log(self, resolution) -> None: def _mode_fault_log(self, resolution) -> None:
"""OPT-11: say once, per battery, that its mode was dropped as a fault. """OPT-11: say once, per battery, that its mode was dropped as a fault.
@@ -4730,6 +4802,8 @@ class Controller:
mode_trade = self._mode_trade(claims, now) mode_trade = self._mode_trade(claims, now)
self._mode_trade_was = mode_trade self._mode_trade_was = mode_trade
self._charge_track(claims, maint_results) self._charge_track(claims, maint_results)
_live96 = set(self.live_units())
self._loop_start = {}
if (self.auto or self.shadow) and self.inputs_ok: if (self.auto or self.shadow) and self.inputs_ok:
# ⚠️ prev is the ARBITER's last output, not the loop's own last # ⚠️ prev is the ARBITER's last output, not the loop's own last
# wish. If something outranked the loop, that is what the hardware # wish. If something outranked the loop, that is what the hardware
@@ -4756,6 +4830,9 @@ class Controller:
# is what seeds it, and dropping it there restarts the ~70 s cycle. # is what seeds it, and dropping it there restarts the ~70 s cycle.
if self.loop_w is not None and self.target != self.loop_w: if self.loop_w is not None and self.target != self.loop_w:
self._refusal_end("another writer") self._refusal_end("another writer")
# SAFETY-96: a battery that dropped out of the split leaves the
# loop's start point (SAFETY-93's own if its charge ended too).
self._reseed_drop(_live96)
# SAFETY-93: a charge that ended leaves the loop's start point. # SAFETY-93: a charge that ended leaves the loop's start point.
self._reseed_charge_end(maint_results) self._reseed_charge_end(maint_results)
probe = self._refusal_probe() probe = self._refusal_probe()
@@ -4775,6 +4852,9 @@ class Controller:
# level: the two halves of §6.2's identity break in opposite # level: the two halves of §6.2's identity break in opposite
# directions. See `site_batt_w` and test_alloc.py part 8. # directions. See `site_batt_w` and test_alloc.py part 8.
site_batt = self.site_batt_w site_batt = self.site_batt_w
# SAFETY-96: a battery the loop cannot move counts at its command,
# so its own power does not freeze the loop (the meter has it).
site_batt += self._held_out_w(_live96)
# TEL-10. ⚠️ ONE NAME FOR THE COMMAND THE LOOP WAS MEASURED # TEL-10. ⚠️ ONE NAME FOR THE COMMAND THE LOOP WAS MEASURED
# AGAINST. `self.target` is reassigned further down this method, so # AGAINST. `self.target` is reassigned further down this method, so
# a `decision.i_w - self.target` written at publish time would # a `decision.i_w - self.target` written at publish time would
@@ -4883,6 +4963,7 @@ class Controller:
# Stopped or blind: no accumulation may survive the outage. # Stopped or blind: no accumulation may survive the outage.
self.i_w = 0.0 self.i_w = 0.0
self.loop_w = None self.loop_w = None
self._live_was = frozenset(_live96)
# TEL-10, and it is the same zero the line above writes rather than # TEL-10, and it is the same zero the line above writes rather than
# a second opinion about it. ⚠️ `not-running` rather than a stale # a second opinion about it. ⚠️ `not-running` rather than a stale
# `tracking`: a reason row that keeps repeating the last word the # `tracking`: a reason row that keeps repeating the last word the
+1 -1
View File
@@ -187,7 +187,7 @@ check("⭐ a draining battery that is dropped (stale link) adds no floor: B "
"covers the 1500 W house, not the 2000 W drain rate, and the wait is " "covers the 1500 W house, not the 2000 W drain rate, and the wait is "
"logged once", "logged once",
"dropped inverter-a" in _l_rows[-1][7] "dropped inverter-a" in _l_rows[-1][7]
and cmd(_l_rows[-1])["b"] == 1500.0 and cmd(_l_rows[-1])["b"] == 1510.0
and sum("cannot give power now" in e for e in _l.events) == 1) and sum("cannot give power now" in e for e in _l.events) == 1)
# ============================================================================ # # ============================================================================ #
+573
View File
@@ -0,0 +1,573 @@
"""Runnable check for SAFETY-96: a battery the loop cannot move does not
freeze the loop. `python3 test_safety96.py`
At N=2, after A's link went stale the site sum still counted A's power, so
`compute()` saw the site "not following" and froze B (SAFETY-93 rig test:
B held at 1200 W for ~236 cycles). After a charge timeout or Off at 6000 W
it froze ~14 s while A came out of its charge. Now a battery out of the
split, with refused writes, or settling after a step the loop did not make
counts at its command; its real power reaches the loop through the meter.
Drives the REAL Controller on a lagging battery (10 s, 2 s meter).
DECISIONS/SAFETY-96-dropped-battery.md.
1. A's link drops while it discharges: A holds its last command (stuck), or
its board goes to 0 W 25 s after the first refused write.
2. A's link drops while it charges (maintenance).
3. B's link drops; both drop.
4. A drops, then comes back.
5. A's charge times out, or A is switched Off, at 6000 W.
6. N=1 is untouched; the rule's parts one by one.
Mutations (MUTATION.md, purged copies) are listed in the pull request.
"""
import hashlib
import logging
import math
import os
import sys
from datetime import datetime, timedelta, timezone
HERE = os.path.dirname(os.path.abspath(__file__))
sys.path.insert(0, HERE)
sys.path.insert(0, os.path.join(HERE, "tools"))
logging.disable(logging.WARNING)
import opt11_identity as rig # noqa: E402
import safety79_identity as s79 # noqa: E402
import safety84_identity as s84 # noqa: E402
from app import packmode # noqa: E402
from app.main import Controller # noqa: E402
from app.maintenance import CHARGE_TIMEOUT_MIN, IDLE, MaintResult # noqa: E402
from app.store import unit_key # noqa: E402
from named_absence import first, present # noqa: E402
fails = []
SLEW = 400.0
FROZEN = ("saturated-freeze", "freeze-released")
OPT = dict(s84.OPT, peak_cap_w=3500)
PLAIN = dict(s79.P1, peak_cap_w=3500)
def check(name, cond):
print(f" {'ok ' if cond else 'FAIL'} {name}")
if not cond:
fails.append(name)
# None on a tree without the fix, where this file prints the base numbers
# and runs red.
fixed = getattr(Controller, "_held_out_w", None)
real_drop = getattr(Controller, "_reseed_drop", None)
def without(fn):
"""Run `fn` with SAFETY-96 taken out (the base behaviour)."""
if fixed is None:
return fn()
Controller._held_out_w = lambda self, live: 0.0
Controller._reseed_drop = lambda self, live: setattr(
self, "_live_was", frozenset(live))
try:
return fn()
finally:
Controller._held_out_w, Controller._reseed_drop = fixed, real_drop
def run(n=2, *, house=lambda t: 2400.0, dur=600.0, store=None, opt=None,
soc=None, reject=None, back=None, wd=None, before=None, lag=10.0,
blind=None, flaky=None, dead=None):
"""Rows of one run. Writes to the units in `reject` (name -> from s) are
refused from that time until `back` s; the add-on sees the refusal at
once (a heartbeat write). A refused unit holds its last command, or with
`wd` its board goes to 0 W `wd` s after the first refused write. B's
reading is missing in the `blind` (from, to) window. `flaky(u, t)`:
writes to u refused at t, each cycle's verdict seen (a heartbeat).
`dead` (u, from s): u gives nothing from then on, whatever it is told.
Each row: (t, plant commands, add-on commands, loop reason, site target,
grid, circulation tripped)."""
reject = reject or {}
real_p, real_s, real_tick = rig._Hass.power, rig._Hass.set_number, rig.TICK
def refused(u, t):
if flaky is not None:
return flaky(u, t)
return u in reject and t >= reject[u] and (back is None or t < back)
def power(self, u):
st = self.__dict__.setdefault("_plant", {})
a, tgt, tl = st.get(u, (0.0, 0.0, self.t))
for k in range(int(round((self.t - tl) / 0.1))):
now = tl + (k + 1) * 0.1
c = self.cmd[u]
if wd is not None and refused(u, now) and now - reject[u] >= wd:
c = 0.0
if dead is not None and u == dead[0] and now >= dead[1]:
c = 0.0
d = c - tgt
tgt += math.copysign(min(abs(d), 80.0), d)
a += (tgt - a) * (1 - math.exp(-0.1 / lag))
st[u] = (a, tgt, self.t)
return float(round(a))
async def set_number(self, e, v):
if refused(e[-1], self.t):
return False
self.cmd[e[-1]] = float(v)
return True
rows = []
def hook(c, t):
for inv in c.inverters:
if flaky is not None:
inv.note_write(not flaky(inv.name[-1], t),
rig.BASE + timedelta(seconds=t))
elif refused(inv.name[-1], t) and inv.rejected_since is None:
inv.rejected_since = rig.BASE + timedelta(seconds=t)
if before is not None:
before(c, t)
if blind is not None and not getattr(c.hass, "_s96", False):
read = c.hass.number
async def number(e, invert=False):
if e == "sensor.batt_b" and blind[0] <= c.hass.t < blind[1]:
return None
return await read(e, invert)
c.hass.number, c.hass._s96 = number, True
(s84.feed(True) if opt is not None else s79._feed)(c, t)
def on_cycle(c, t):
rows.append((t, tuple(sorted(c.hass.cmd.items())),
tuple(inv.target for inv in c.inverters), c.loop_reason,
c.target, c.hass.grid(), c.circ_wd.tripped,
tuple(inv.batt for inv in c.inverters)))
rig._Hass.power, rig._Hass.set_number, rig.TICK = power, set_number, 2.0
try:
_r, ctl = rig.run(n, extra=dict(opt if opt is not None else PLAIN),
dur=dur, load=house, soc=soc or (lambda u, t: 60.0),
cut=lambda u, t: False, before=hook,
on_cycle=on_cycle, store=store or rig._Store())
finally:
rig._Hass.power, rig._Hass.set_number, rig.TICK = real_p, real_s, \
real_tick
return rows, ctl
def freeze(rows, lo, hi=1e9):
return sum(1 for r in rows if lo <= r[0] < hi and r[3] in FROZEN)
def phantom(rows, k, lo, hi=1e9):
"""Freeze cycles while battery `k` (the one taking over) reads within
saturation_w (500 W) of what the loop last asked of it plus anything
unplaced (last site target less the other's command): the freeze is
then about the other battery, not about `k`'s own lag."""
return sum(1 for a, b in zip(rows, rows[1:]) if lo <= b[0] < hi
and b[3] in FROZEN
and abs(a[4] - a[2][1 - k] - b[7][k]) <= 500.0)
def ramp(rows, k, lo, hi=1e9):
"""The largest change of unit `k`'s command (0 = A) between cycles."""
return max(abs(b[2][k] - a[2][k]) for a, b in zip(rows, rows[1:])
if lo < b[0] <= hi)
def site_step(rows, lo, hi=1e9):
return max(abs(b[4] - a[4]) for a, b in zip(rows, rows[1:])
if lo < b[0] <= hi)
def grid_err(rows, lo, hi=1e9):
"""Mean |grid - aim| over [lo, hi) (aim -10 W)."""
xs = [abs(r[5] + 10.0) for r in rows if lo <= r[0] < hi]
return sum(xs) / len(xs)
def trip_at(rows):
"""When the circulation guard tripped (its own 0 W step is no ramp)."""
return next((r[0] for r in rows if r[6]), 1e9)
def tripped(rows):
return rows[-1][6]
def at(rows, t, k):
return first((r[2][k] for r in rows if r[0] == t), f"row {t}")
TABLE = []
LAST = [None] # the controller of the last run with the fix
def case(name, fn, lo, k, hi=1e9):
"""Run `fn` with and without SAFETY-96, print and record the numbers:
freeze cycles (and those not about `k`'s own lag), `k`'s largest step,
the mean grid error, a circulation trip."""
(now, LAST[0]), old = fn(), without(fn)[0]
row = (name, freeze(now, lo, hi), freeze(old, lo, hi),
phantom(now, k, lo, hi), phantom(old, k, lo, hi),
ramp(now, k, lo, min(hi, trip_at(now) - 1)),
ramp(old, k, lo, min(hi, trip_at(old) - 1)),
grid_err(now, lo, hi), grid_err(old, lo, hi),
tripped(now), tripped(old))
TABLE.append(row)
print(f" {name}: freeze {row[1]} (base {row[2]}), not about its own lag "
f"{row[3]} (base {row[4]}); step {row[5]:.0f} (base {row[6]:.0f}) "
f"W/cycle; grid error {row[7]:.0f} (base {row[8]:.0f}) W; "
f"circulation trip {row[9]} (base {row[10]})")
return now, old
STUCK, BOARD = ("stuck", None), ("board 0 W", 25.0)
# ============================================================================ #
print("1. A's link drops while it discharges (house 2400 W, each 1200 W)")
for v, w in (STUCK, BOARD):
now, old = case(f"A drop discharging, {v}",
lambda w=w: run(reject={"a": 300.0}, wd=w), 300.0, 1)
check(f"⭐ {v}: no freeze about A, B moves at most one slew step a "
f"cycle, no circulation trip", phantom(now, 1, 300) == 0
and ramp(now, 1, 300) <= SLEW and not tripped(now))
check(f"non-vacuous ({v}): without the fix the loop freezes about A, or "
f"B jumps more than a slew step at the drop",
phantom(old, 1, 300) >= 10 or ramp(old, 1, 300) > SLEW)
if w is None:
check("stuck: B stays at its share, since A still gives its 1200 W "
"(no freeze at all, grid within 15 W on average)",
freeze(now, 300) == 0 and grid_err(now, 300) < 15.0
and freeze(old, 300) >= 100)
else:
check("board 0 W: B ends up carrying the whole house (2410 W)",
abs(now[-1][2][1] - 2410.0) <= 20.0)
# ============================================================================ #
print("\n2. A's link drops while it charges (maintenance, house 1200 W)")
def charging(**kw):
return run(house=lambda t: 1200.0, dur=1500.0,
store=s79.store_charging(2), opt=dict(
OPT, maintenance_hold_min=600),
soc=lambda u, t: 90.0 if u == "a" else 60.0, **kw)
for v, w in (STUCK, BOARD):
now, old = case(f"A drop charging, {v}",
lambda w=w: charging(reject={"a": 1300.0}, wd=w),
1300.0, 1)
trip = trip_at(now)
check(f"⭐ {v}: no freeze about A, and B climbs at most one slew step a "
f"cycle and never charges (until any circulation trip)",
phantom(now, 1, 1300, trip) == 0
and ramp(now, 1, 1300, trip - 1) <= SLEW
and min(r[2][1] for r in now if r[0] >= 1300) >= 0.0)
check(f"non-vacuous ({v}): without the fix the loop freezes about A",
phantom(old, 1, 1300) >= 3)
if w is None:
check("stuck (A charges 2000 W on its own): B reaches its 2500 W "
"before the circulation trip, which still trips on the real "
"4000 W going round (as on base)",
max(r[2][1] for r in now if r[0] < trip) == 2500.0
and tripped(now) and tripped(old))
else:
check("board 0 W: B carries the house (grid within 50 W from 100 s "
"after the drop), no circulation trip",
grid_err(now, 1400) < 50.0 and not tripped(now))
# ============================================================================ #
print("\n3. B's link drops; both drop")
for v, w in (STUCK, BOARD):
now, old = case(f"B drop discharging, {v}",
lambda w=w: run(reject={"b": 300.0}, wd=w), 300.0, 0)
check(f"⭐ B drops ({v}): no freeze about B, A moves at most one slew "
f"step a cycle, no circulation trip", phantom(now, 0, 300) == 0
and ramp(now, 0, 300) <= SLEW and not tripped(now))
for v, w in (STUCK, BOARD):
now, old = case(f"both drop, {v}",
lambda w=w: run(reject={"a": 300.0, "b": 300.0}, wd=w),
300.0, 1)
check(f"⭐ both drop ({v}): no freeze; both are commanded 0 W once "
f"nothing can be placed", freeze(now, 300) == 0
and now[-1][2] == (0.0, 0.0) and not tripped(now))
# ============================================================================ #
print("\n4. A drops, then comes back")
def rejoined(rows):
return next((r[0] for r in rows if r[0] > 420 and r[2][0] != 0.0), 1e9)
for v, w in (STUCK, BOARD):
now, old = case(f"A drop and rejoin, {v}",
lambda w=w: run(reject={"a": 300.0}, back=420.0, wd=w,
dur=700.0), 300.0, 1)
back = rejoined(now)
check(f"rejoin ({v}): A is back in the split within 4 s of its link "
f"returning (no refusal was learned while its writes were refused)",
back <= 424.0 and not any("REFUSES" in e for e in LAST[0].events))
print(f" A back in the split at {back:.0f} s; A "
f"{[r[2][0] for r in now if back - 2 <= r[0] <= back + 6]}, B "
f"{[r[2][1] for r in now if back - 2 <= r[0] <= back + 6]}; grid "
f"{[round(r[5]) for r in now if back - 2 <= r[0] <= back + 6]}; "
f"base grid {[round(r[5]) for r in old if back - 2 <= r[0] <= back + 6]}")
a0 = first((r for r in now if r[0] == back - 2), "row before the rejoin")
a1 = first((r for r in now if r[0] == back), "the rejoin row")
check(f"⭐ rejoin ({v}): no freeze after it; the site target takes in only "
f"A's own reading, then moves at most one slew step a cycle; the "
f"grid stays within 250 W of its aim; no circulation trip",
present(a0) and present(a1) and freeze(now, back) == 0
and abs(a1[4] - a0[4] - a0[7][0]) <= SLEW
and site_step(now, back) <= SLEW
and max((abs(r[5] + 10.0) for r in now if r[0] >= back),
default=1e9) < 250.0
and not tripped(now))
if w is None:
check("non-vacuous (stuck): without the fix the grid swings over "
"1000 W after the rejoin", max((abs(r[5] + 10.0) for r in old
if r[0] >= back), default=0.0)
>= 1000.0)
# Review: a battery that does refuse, behind a link that refuses one write
# in three, is still found out (the count is kept over a refused write).
_fl_rows, _fl = run(dur=700.0, dead=("a", 300.0),
flaky=lambda u, t: u == "a" and t >= 300.0
and int(t / 2) % 3 == 0)
_fl_at = next((r[0] for r in _fl_rows if r[2][0] == 0.0 and r[0] > 300.0),
None)
_fl_end = first((r[2] for r in _fl_rows[-1:]), "the last row")
print(f" A gives nothing from 300 s, 1 write in 3 refused: A's share is "
f"taken off at {_fl_at} s; A {_fl.inverters[0].refused}, last "
f"commands {_fl_end}")
check("⭐ a battery that refuses behind a link refusing 1 write in 3: its "
"refusal is still learned and B carries the house",
_fl.inverters[0].refused == 1 and _fl_at is not None
and _fl_at <= 400.0 and present(_fl_end)
and abs(_fl_end[1] - 2410.0) <= 20.0)
# Review: a fast battery whose board goes to 0 W 1 s after the first refused
# write reads ~0 W long before its link is stale (30 s): no refusal either.
_ref5 = []
_e5_rows, _e5 = run(reject={"a": 300.0}, back=420.0, wd=1.0, lag=1.0,
dur=700.0,
before=lambda c, t: _ref5.append(c.inverters[0].refused))
check("fast battery, board 0 W 1 s after the first refused write: no "
"refusal is learned, A is back in the split within 4 s of its link "
"returning",
not any(_ref5) and rejoined(_e5_rows) <= 424.0)
_seen = []
def blind_seen(c, t):
"""Record the last cycle: whether the loop ran, is A live, what settles."""
if t > 340.0:
_seen.append((t - 2.0, c.loop_reason, "inverter-a" in c.live_units(),
dict(c._settle)))
run(reject={"a": 300.0}, back=420.0, blind=(340.0, 470.0), dur=490.0,
before=blind_seen)
_back = first((x for x in _seen if x[1] != "not-running" and x[0] > 400),
"the restart")
print(f" B's reading missing 340-470 s, A back at 420 s: control holds from "
f"{first((x[0] for x in _seen if x[1] == 'not-running'), '?')} s, "
f"restarts at {_back[0]:.0f} s, settling then: {_back[3]}")
check("A drops, then comes back while control holds (a reading missing): no "
"rejoin at the restart, which starts from what is on the wire",
any(x[1] == "not-running" and x[2] for x in _seen) and _back[3] == {})
# ============================================================================ #
print("\n5. A's charge times out, or A is switched Off, at a 6000 W house")
def timed_out(end):
"""A's charge passes CHARGE_TIMEOUT_MIN at `end` s; A then stays free
(its cycle started today, so no restart) and B is not due."""
s = s79.store_charging(2)
s.data[unit_key("inverter-a", "phase_started")] = (
rig.BASE + timedelta(seconds=end - CHARGE_TIMEOUT_MIN * 60 - 1)
).isoformat()
s.data[unit_key("inverter-a", "last_start_attempt")] = rig.BASE.isoformat()
s.data[unit_key("inverter-b", "last_completed")] = rig.BASE.isoformat()
return s
def b_done():
s = s79.store_charging(2)
s.data[unit_key("inverter-b", "last_completed")] = rig.BASE.isoformat()
return s
def switch_off(at_t):
def before(c, t):
if t >= at_t:
c.store.data[unit_key("inverter-a", packmode.USE_KEY)] = False
return before
def high(t):
return 6000.0 if t >= 1760.0 else 1200.0
ENDS = {
"timeout": lambda: run(house=high, dur=1798.0, store=timed_out(1780.0),
opt=dict(OPT, maintenance_hold_min=600),
soc=lambda u, t: 90.0 if u == "a" else 60.0),
"Off": lambda: run(house=high, dur=1798.0, store=b_done(),
before=switch_off(1780.0),
opt=dict(OPT, maintenance_hold_min=600,
battery_modes_enabled=True),
soc=lambda u, t: 90.0 if u == "a" else 60.0),
}
for k, fn in ENDS.items():
now, old = case(f"{k} at 6000 W", fn, 1780.0, 1)
print(f" B {[r[2][1] for r in now if 1778 <= r[0] <= 1796]}, base "
f"{[r[2][1] for r in old if 1778 <= r[0] <= 1796]}")
check(f"⭐ {k}: no freeze about A while it comes out of its charge; B "
f"climbs one slew step a cycle and never charges",
phantom(now, 1, 1780) == 0 and ramp(now, 1, 1780) <= SLEW
and min(r[2][1] for r in now if r[0] >= 1780) >= 0.0)
check(f"non-vacuous ({k}): without the fix the loop freezes about A and "
f"B ends lower", phantom(old, 1, 1780) >= 3
and at(now, 1796.0, 1) > at(old, 1796.0, 1))
# ============================================================================ #
print("\n6. N=1 is untouched; the rule's parts")
def digest(rows):
return hashlib.sha256(repr(rows).encode()).hexdigest()
def wave(t):
return 2400.0 + 1500 * math.sin(t / 40)
_n1 = [lambda: run(1, reject={"a": 300.0}, back=420.0, wd=25.0),
lambda: run(1, house=high, dur=1798.0, store=timed_out(1780.0),
opt=dict(OPT, maintenance_hold_min=600)),
lambda: run(1, house=wave)]
check("⭐ N=1 (a refused link that comes back, a charge timeout, a moving "
"house): every row byte-identical with and without SAFETY-96",
[digest(f()[0]) for f in _n1] == [digest(without(f)[0]) for f in _n1])
check("N=2 healthy (a moving house, no drop): every row byte-identical with "
"and without SAFETY-96",
digest(run(house=wave)[0]) == digest(without(lambda: run(
house=wave))[0]))
if fixed is None:
print(f"\n{len(fails)} FAILED (no _held_out_w): " + ", ".join(fails))
sys.exit(1)
_c = run(dur=4.0)[1]
AB = ("inverter-a", "inverter-b")
def held(batts, targets, live=AB, rejected=(), settle=None, now=100.0,
start=None):
for inv, b, t in zip(_c.inverters, batts, targets):
inv.batt, inv.target = b, t
inv.rejected_since = rig.BASE if inv.name in rejected else None
_c._settle = dict(settle or {})
_c._loop_start = dict(start or {})
_c._now_mono = now
return _c._held_out_w(set(live))
check("a healthy pair: nothing held out, however far a reading lags",
held((-2000.0, 400.0), (0.0, 400.0)) == 0.0)
check("a dropped battery counts at its command (0 W), not its reading",
held((-2000.0, 800.0), (0.0, 800.0), live=("inverter-b",)) == 2000.0)
check("a battery whose writes are refused counts at its command",
held((900.0, 800.0), (1200.0, 800.0), rejected=("inverter-a",))
== 300.0)
check("a settling battery counts at its command until its reading is within "
"the deadband (15 W) of it, then it is the loop's again",
held((-20.0, 800.0), (0.0, 800.0), settle={"inverter-a": 95.0})
== 20.0 and "inverter-a" in _c._settle
and held((-10.0, 800.0), (0.0, 800.0), settle={"inverter-a": 95.0})
== 0.0 and "inverter-a" not in _c._settle)
check("...but not on the cycle it starts",
held((-10.0, 800.0), (0.0, 800.0), settle={"inverter-a": 100.0})
== 10.0 and "inverter-a" in _c._settle)
check("...or until PLANT_SETTLE_DOWN_S (23 s) has passed, whichever is first",
held((-2000.0, 800.0), (0.0, 800.0), settle={"inverter-a": 77.1})
== 2000.0 and held((-2000.0, 800.0), (0.0, 800.0),
settle={"inverter-a": 77.0}) == 0.0)
check("a reseeded start (SAFETY-93's charge end) is the command it counts at",
held((-2000.0, 800.0), (-2000.0, 800.0), settle={"inverter-a": 99.0},
start={"inverter-a": 0.0}) == 2000.0)
def dropped(was, live, target, shares, batts=(0.0, 0.0), start=None):
_c._live_was, _c.target, _c.i_w = (None if not was else frozenset(was),
target, 123.0)
_c._loop_start, _c._settle, _c._now_mono = dict(start or {}), {}, 50.0
for inv, b in zip(_c.inverters, batts):
inv.target, inv.batt = shares[inv.name[-1]], b
_c._reseed_drop(set(live))
return _c.target, _c.i_w
check("a drop: the dropped battery's share leaves the start point, the "
"integrator with it", dropped(AB, ("inverter-b",), 2400.0,
{"a": 1200.0, "b": 1200.0})
== (1200.0, 1200.0) and _c._live_was == frozenset({"inverter-b"}))
_c._charge_ended = frozenset({"inverter-a"})
check("...but a battery whose charge ended too is left to SAFETY-93's reseed",
dropped(AB, ("inverter-b",), -2000.0, {"a": -2000.0, "b": 0.0})
== (-2000.0, -2000.0))
_c._charge_ended = frozenset()
_free = MaintResult(IDLE, False, None, False, [])
def charge_end(rejected_s):
"""SAFETY-93's reseed for A (giving 1385 W under the loop, its charge
suspended), A's writes refused for `rejected_s` s: (target, start)."""
_c.target, _c.i_w, _c._charge_ended = 2770.0, 0.0, frozenset({AB[0]})
_c._loop_start, _c._settle = {}, {}
for inv in _c.inverters:
inv.target, inv.rejected_since = 1385.0, None
_c.inverters[0].rejected_since = datetime.now(timezone.utc) - timedelta(
seconds=rejected_s)
_c._reseed_charge_end([_free, _free])
_c.inverters[0].rejected_since = None
return _c.target, _c._loop_start[AB[0]]
check("a charge that ends as its battery drops: the battery's start is 0 W "
"(it is sent 0 W), not its last give; still live, its give stays",
charge_end(31.0) == (1385.0, 0.0) and charge_end(5.0) == (2770.0, 1385.0))
check("a rejoin: the battery enters the start point at its reading, and "
"both settle while the split is made again",
dropped(("inverter-b",), AB, 1200.0, {"a": 0.0, "b": 1200.0},
batts=(-700.0, 1200.0)) == (500.0, 500.0)
and _c._settle == {"inverter-a": 50.0, "inverter-b": 50.0})
check("no change: nothing moves (the integrator either)",
dropped(AB, AB, 1200.0, {"a": 600.0, "b": 600.0}) == (1200.0, 123.0)
and dropped((), ("inverter-b",), 1200.0, {"a": 0.0, "b": 1200.0})
== (1200.0, 123.0))
_n1c = run(1, dur=4.0)[1]
_n1c._live_was, _n1c.target, _n1c.i_w = frozenset({"inverter-a"}), 900.0, 5.0
_n1c._reseed_drop(set())
check("N=1: nothing moves and nothing is held out",
(_n1c.target, _n1c.i_w) == (900.0, 5.0)
and _n1c._held_out_w(set()) == 0.0)
print("\n case | freeze head/base | not about its own lag head/base | "
"step W head/base | grid error W head/base | circulation trip head/base")
for r in TABLE:
print(f" {r[0]} | {r[1]}/{r[2]} | {r[3]}/{r[4]} | {r[5]:.0f}/{r[6]:.0f} |"
f" {r[7]:.0f}/{r[8]:.0f} | {r[9]}/{r[10]}")
print()
if fails:
print(f"{len(fails)} FAILED: " + ", ".join(fails))
sys.exit(1)
print("all SAFETY-96 checks passed")