The desk half of SPIKE-04. No control behaviour changes; this is documentation and the check that stops it drifting again. Three places stated inverter B's rating - config.yaml's commented roster example, DOCS.md's, and tools/supervisor_shape_probe.py's "a blob an operator would POST" - and all three said 3000 W, a number nobody had measured or read off anything. The owner supplied B's model and serial on 2026-09-04: a GoodWe GW5048D-ES, serial `55048ESU22AW0992`, max charging and discharging power 4600 W. Serial characters 6-8 are `ESU`, platform 105 / AA55, so SPIKE-01 does not gate this site. All three copies now read 4600. ⚠️ 4600 W IS FROM A DATASHEET AND IS NOT A MEASUREMENT, and the one ambiguity is recorded rather than guessed. The datasheet prints it under BATTERY INPUT DATA, so it is probably DC, while max_w is graded against 0x0518 - the inverter's own AC power. If it is DC the AC ceiling is nearer 4324 W. Neither reading is written in as fact; SAFETY-20's min(max_w, dev_max) already bounds it correctly under either, once dev_max is read off the unit, so `max_w: 4600` is what an operator should configure today. goodwe/NOTES.md §1.1b carries the full record with the date and the method on every figure. A NEW CHECK, BECAUSE A DOCUMENTATION FIX WITHOUT ONE DRIFTS AGAIN. test_validate.py now pins all three documented rosters: findable, in agreement, and equal to 4600 - with an explicit len(...) == 3 guard so that a regex which stopped matching cannot leave "they all agree" green on the two sites still read. It also grades the PROVENANCE beside the number (the datasheet, the 0x0518 it is graded against, and the 4324 W the DC reading would make it) WITHIN 2500 characters of the roster rather than file-wide. ⚠️ The first version of that provenance check searched whole files and was ALREADY VACUOUS on two of them: 0x0518 appeared once in config.yaml and once in DOCS.md before this card, for unrelated reasons, so `"0x0518" in src` was green no matter what happened next to B's rating. That is a check whose data cannot reach the failure it names, in the file that exists to complain about them. It is fixed, and the window is what fixes it - deleting the caveat beside the number now goes red even where the same token survives elsewhere in the file. The windowed version immediately found that the DOCS.md caveat did not name 0x0518 at all; DOCS.md now says it. Four mutations, bytecode purged and counted at 0 before and after each, all RED (two of them 0-byte deltas that change a printed answer): M1 probe's operator blob 4600 -> 3000 0 B RED (value + agreement) M2 DOCS.md's DC/AC caveat deleted -157 B RED (provenance) M3 config.yaml alone 4600 -> 4324 0 B RED (agreement) M4 probe entity renamed, regex finds nothing RED (the vacuity guard) Restored, green again. The probe itself was re-run against Supervisor 2026.08.0's own AppOptions validator with the 4600: all cases passed, exit 0. ⚠️ THE TEST FIXTURES KEEP 3000 W ON PURPOSE AND NOW SAY WHY AT THE LINE. test_inverter.py, test_maintenance.py, test_peakguard.py and test_watchdog.py build a second inverter at 3000 W against A's 5000 W. The only property those checks consume is that B's number is unmistakably not A's, and the real pair is a 400 W gap - narrower than slew_w, inside the range where an off-by-one-unit bug and ordinary control arithmetic produce indistinguishable numbers. Collapsing them onto the real values would buy realism those checks do not use and cost them their separating power, which is exactly what test_peakguard.py's own §10g PRECONDITION exists to prevent. Their comments no longer call 3000 W a hypothesis about B's rating; they call it illustrative, and not a placeholder either - the placeholder era ended on 2026-09-04. Also recorded in the changelog for the cards that own them: 94 % battery-to-AC => ~88 % round trip => ~360 W burned continuously to circulate 3 kW, which is the number SAFETY-31 argues its threshold from without having one; < 13 W night self-consumption per unit, which nothing accounts for; and the A/B asymmetry in opposite directions (~33 % more energy, ~8 % less power), which means MAINT-05's 12 h drain timeout was derived on A and should be re-checked against B. ⚠️ Honest survivors: - goodwe/NOTES.md §1.1b, where all of this is actually recorded, is graded by nothing here. Rewriting its 16 occurrences of 4600 to 3000 and turning every FROM DATASHEET label into MEASURED ON THE UNIT leaves all 19 files GREEN. This CI cannot fetch admin/goodwe - private, and GITHUB_TOKEN is minted for this repository only, as .gitea/workflows/checks.yml already states - so the cross-repo check is not buildable here. - No check can see whether 4600 is the RIGHT number. Everything above pins a datasheet reading against itself. Only the bench half of SPIKE-04 can say whether the unit agrees, and the DC-vs-AC ambiguity is the live example. - The constant is still named B_RATING_HYPOTHESIS in four test files, which reads as a hypothesis about B's rating when it is now an illustrative fixture. It is left alone deliberately: renaming ~20 sites across test_peakguard.py and test_inverter.py would collide hard with the open SAFETY-32 pull request, which rewrites 1255 lines of the first. The comment directly above each definition says what the value is and is not. Suite: 19/19 green in goodwe-addon-ci, mounted :ro, bytecode purged and verified 0 before and after. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
This commit is contained in:
co-authored by
Claude Opus 5
parent
3934ad7ea5
commit
a9993aeda2
@@ -2,6 +2,67 @@
|
||||
|
||||
## Unreleased
|
||||
|
||||
**Inverter B's rating is 4600 W, FROM ITS DATASHEET, and every documented copy
|
||||
of it now says so (SPIKE-04a).** Three places stated B's rating — `config.yaml`'s
|
||||
commented roster example, `DOCS.md`'s, and `tools/supervisor_shape_probe.py`'s
|
||||
"a blob an operator would POST" — and all three said **3000 W**, a number that
|
||||
was never measured, never read off a datasheet, and simply wrong. The owner
|
||||
supplied B's model and serial on 2026-09-04: a **GoodWe GW5048D-ES**, serial
|
||||
`55048ESU22AW0992`, max charging and discharging power **4600 W**. No control
|
||||
behaviour changes here; this is documentation and its pin.
|
||||
|
||||
* **Serial characters 6-8 read `ESU`** → platform 105, AA55, the supported set.
|
||||
Not `ESN`/`ESC` (ES G2, platform 745). SPIKE-01 does not gate this site.
|
||||
⚠️ A passed platform gate is **not** a proven control surface: `specs.md`
|
||||
already calls other platform-105 serials *"same protocol family; untested
|
||||
silicon"*, and this repo's `0x056E`/`0x056F` map was reverse-engineered from a
|
||||
passive tap on **one BPS unit**. That check is the bench half of SPIKE-04.
|
||||
* **⚠️ 4600 W IS FROM A DATASHEET AND IS NOT A MEASUREMENT, and one ambiguity is
|
||||
recorded rather than guessed.** The datasheet prints it under *Battery Input
|
||||
Data*, so it is probably **DC**, while `max_w` is graded against `0x0518` —
|
||||
the inverter's own **AC** power. If it is DC the AC ceiling is nearer
|
||||
4600 × 0.94 ≈ **4324 W**, and the charge direction moves the other way
|
||||
(≈ 4894 W drawn AC-side). **Neither reading is written in as fact.**
|
||||
SAFETY-20's `min(max_w, dev_max)` already bounds it correctly under either,
|
||||
once `dev_max` is read off the unit — so `max_w: 4600` is what to configure
|
||||
today. `goodwe/NOTES.md` §1.1b carries the full record, with the date and the
|
||||
method on every figure.
|
||||
* **A NEW CHECK, BECAUSE A DOCUMENTATION FIX WITHOUT ONE DRIFTS AGAIN.**
|
||||
`test_validate.py` now pins all three documented rosters: they must be
|
||||
findable, they must agree, and they must say **4600**. It also grades the
|
||||
**provenance beside the number** — the datasheet it came from, the `0x0518`
|
||||
it is graded against, and the 4324 W the DC reading would make it — **within
|
||||
2500 characters of the roster, not file-wide.** The first version searched
|
||||
whole files and was already vacuous on two of them, because `0x0518` appeared
|
||||
in `config.yaml` and `DOCS.md` for unrelated reasons before this card: a
|
||||
check whose data could not reach the failure it named, in the file that
|
||||
exists to complain about those. Four mutations were run against the fixed
|
||||
version — the probe back to 3000 (0-byte delta), the `DOCS.md` caveat
|
||||
deleted, `config.yaml` alone "corrected" to 4324 (0-byte delta), and the
|
||||
probe's entity renamed so the regex finds nothing — and all four are red.
|
||||
* **THE TEST FIXTURES KEEP 3000 W ON PURPOSE, AND NOW SAY WHY AT THE LINE.**
|
||||
`test_inverter.py`, `test_maintenance.py`, `test_peakguard.py` and
|
||||
`test_watchdog.py` build a second inverter at 3000 W against A's 5000 W. The
|
||||
only property those checks consume is that B's number is **unmistakably** not
|
||||
A's, and the real pair is a **400 W** gap — narrower than `slew_w`, inside the
|
||||
range where an off-by-one-unit bug and ordinary control arithmetic produce
|
||||
indistinguishable numbers. Collapsing them onto the real values would buy
|
||||
realism those checks do not use and cost them their separating power, which
|
||||
is the defect `test_peakguard.py`'s own §10g precondition exists to prevent.
|
||||
They are **illustrative, not B's rating, and no longer a placeholder for it**.
|
||||
* **Two consequences with numbers, recorded in `goodwe/NOTES.md` §1.1b for the
|
||||
cards that own them.** At 94 % battery-to-AC a round trip is ≈ 88 %, so A
|
||||
charging 3 kW while B discharges 3 kW burns ≈ **360 W continuously** with the
|
||||
meter at zero — SAFETY-31 argues its threshold from *"a few watts"* and has no
|
||||
figure. And **< 13 W night self-consumption per unit** (≈ 26 W for two,
|
||||
≈ 0.6 kWh/day), which nothing in this add-on accounts for anywhere.
|
||||
* **The site is asymmetric in opposite directions:** A = 5000 W / 15.36 kWh
|
||||
nominal, B = 4600 W / 20.48 kWh — ~33 % more energy, ~8 % less power. No
|
||||
stability implication (ARCH-01's ḡ = Σαᵢgᵢ is a convex combination), but a
|
||||
full recalibration of B moves 33 % more energy and **MAINT-05's 12 h `drain`
|
||||
phase timeout was derived on A**; it should be re-checked against B rather
|
||||
than assumed to carry.
|
||||
|
||||
**Every pack is recalibrated on its own schedule, and only one moves power at a
|
||||
time (MAINT-05).** §12's monthly cycle drains a pack to empty and refills it to
|
||||
true its coulomb counter. There was exactly one `Maintenance` state machine and
|
||||
|
||||