Merge release/1.0 (SAFETY-81, #155) into opt11-p4-solar-forecast

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
This commit is contained in:
glenn schrooyen
2026-09-29 22:08:52 +02:00
co-authored by Claude Opus 5.5
7 changed files with 558 additions and 9 deletions
@@ -0,0 +1,63 @@
# SAFETY-81 — no false "Load too high for battery" alarms
**Status: 2026-09-29, owner go for the card. Review kept the 10 W tolerance
as a constant and added the 10 s hold.**
## Defect
The SAFETY-79 test (SAFETY-79-test-report.md, F1/F2) saw 6 false alarms in 7.
The alarm fired whenever `decide()` clamped its floor to the rating
(`saturated`). Three things set that while the quarter landed on target:
- **Double count.** `decide()` sizes from the held meter reading plus the
battery reading. When the meter sample predates the battery's last increase,
the increase is counted twice. It happens under noise, and at each quarter
start, where the battery is back while the held sample is still the spike.
- **The aim, not the cap.** `saturated` is graded against cap − margin, so at
margin 50 noise needs 50 W less to trip it (F2).
- **Last seconds.** The gain 900 / remaining turns a few W over the aim into
thousands of W wanted, with the battery far from its rating.
## Decision
The alarm needs `saturated` and `peakguard.load_too_high()`: with the battery
at full power from now on, the quarter still ends more than `ALARM_MISS_W`
(10 W) over the real limit (`ceiling_w`). That is the miss itself, without the
gain. The battery reading it uses is the lower of this cycle's and the last
one's. It must hold for `ALARM_HOLD_S` (10 s). At most one notification per
quarter, because near the threshold the test flickers with the meter; the
ERROR log line is written for every episode.
**Why 10 W:** at margin 0 the guard itself lands up to +5.7 W over (SAFETY-79
test, check 5), and those misses are real but tiny; the alarm would fire in
the last second of most guarded quarters. The margin (default 50) is the fix
for them. Cost: a real miss of 10 W or less is not alarmed; at a capacity
tariff of the order of EUR 50 per kW a year, 10 W in one month is cents.
Review measured +13 W on a 10 kW two-unit site at margin 0, not saturated, so
no alarm: the tolerance only matters when the battery is at its rating. A
constant, not an option: `peak_margin_w` is the owner's knob.
**Why the hold (review):** the test assumes the load now lasts the rest of
the quarter. A load over cap + battery for ~5 s every 30 s (`sine4500_fast`,
a cycling hob or heater) alarmed at each quarter start while the quarter
landed under the aim. The hold stops that.
**Cost:** a real alarm comes 10-12 s later than on 5a4cdc2 (`step6500` at
1211 s, not 1201 s); a slow ramp 20 s later (`ramp6500`), as it waits for the
real cap. While the battery refuses or its reading is lost, the alarm waits
until the quarter is lost even at full battery (27-60 s later in review runs);
those faults have their own alarms. A load over cap + battery for more than
10 s still alarms even if the quarter later lands under. `ALARM_HOLD_S = 0`
removes the hold.
## Not changed: the 1 s spike itself
The cycle after a quarter boundary and before the new quarter's first meter
sample still sees 0 s left, files no claim, and an Off battery drops to 0 W for
one cycle. That is the same edge tick as OPT-15 F1, so it is left to OPT-15.
Control is unchanged here: every command in `tools/safety81_sim.py` is
byte-identical to 5a4cdc2 (test_safety81.py part 1).
The double count also moves control, not only the alarm: on a late sample the
guard asks for the full rating for one cycle (edge4600 at 902 s: 2000 W where
1150 W holds the aim). Left to a follow-up card.
+8 -4
View File
@@ -1752,7 +1752,8 @@ control action and goes to the action log and the status page. A *saturated*
guard — asking for everything the inverter has while the quarter is still
projected over — raises one notification (`goodwe_peak_saturated`), because that
is the one state where the money will be spent and shedding load is the only
thing left that changes the bill.
thing left that changes the bill. SAFETY-81 keeps a 1 s meter spike, noise and
a quarter's last seconds from raising it: see `peakguard.load_too_high()`.
**And it sizes a price-driven charge, not only a forced discharge (SAFETY-45).**
The same arithmetic read the other way answers *"how hard may this site charge
@@ -3224,9 +3225,12 @@ reason code `OUTPUT_CLAMP`.
**Load too high for battery.** The capacity-peak guard (SAFETY-07) asks for
everything the inverter can discharge and the running 15-minute average is
still projected over the peak limit, so the month's billed peak
(capaciteitstarief) goes up. In shadow mode the guard's projection is made on a
plant that did not respond (SAFETY-47), and the text says so. See *The
capacity-peak guard*.
(capaciteitstarief) goes up. It fires only when, for 10 s, the period would
still end more than 10 W over the real limit (not the margin's aim) with the
battery at full power. It notifies at most once per period; later overloads
in the same period go to the log (SAFETY-81). In shadow mode the
guard's projection is made on a plant that did not respond (SAFETY-47), and
the text says so. See *The capacity-peak guard*.
**Battery stopped limiting the peak.** The peak guard may not discharge below
`peak_soc_floor` (label “Peak reserve”, SAFETY-24). It also stops when the
+46 -5
View File
@@ -929,6 +929,11 @@ class Controller:
"peak_margin_w", peakguard.PEAK_OPTION_DEFAULTS["peak_margin_w"]))
self._peak_engaged = False
self._peak_saturated = False
# SAFETY-81: what the alarm is graded on, beside the guard's decision.
self._peak_proj = None
self._peak_batt_prev = None
self._peak_alarm_block = None
self._peak_high_since = None
self._peak_floor_limited = False
self._maint_shape_suspended = False
# OPT-11. Battery modes, off by default so an install that has not
@@ -3821,8 +3826,10 @@ class Controller:
# is not measured on that path, and the honest report is NOT COVERED -
# the same answer, for the same reason, that the status page already
# gives for SAFETY-18 on a transport that cannot see `unchanged_s`.
self._peak_proj = (None if not self.p1_enabled
else self.peak.project(self.p1.averager, now))
self.peak_guard = None if not self.p1_enabled else peakguard.decide(
self.peak.project(self.p1.averager, now),
self._peak_proj,
# ⚠️ THE SITE SUM. The guard sizes a floor from what the battery is
# ALREADY removing from the meter, and the meter sees every
# inverter. One unit's power here would size the floor from a
@@ -4925,22 +4932,56 @@ class Controller:
available to it. That is the one state where the money is going to be
spent and a human is the only remaining actuator.
SAFETY-81: `g.saturated` alone is not enough. It is graded against the
aim, and a 1 s meter spike, noise or the last seconds of a quarter set
it while the quarter lands on target; `peakguard.load_too_high()` must
agree too, for `ALARM_HOLD_S`. The battery reading it gets is the lower
of this cycle's and the last one's - see there.
Edge-triggered, and de-asserting arms it again - the same shape as
FreezeWatchdog's `evaluate()`, and for the same reason: one notification
per episode, not one per cycle.
per episode, not one per cycle. SAFETY-81: the notification and action
log line at most once per quarter; the ERROR line once per episode.
"""
g = self.peak_guard
saturated = bool(g is not None and g.saturated)
batt, prev = self.site_batt_w, self._peak_batt_prev
if batt is None:
# Unknown, not "fine": the hold below neither grows nor restarts.
return
self._peak_batt_prev = batt
if prev is not None:
batt = min(float(batt), float(prev))
p = self._peak_proj
high = bool(
g is not None and g.saturated and p is not None
and p.block_start is not None
and peakguard.load_too_high(
p, batt_w=batt, ceiling_w=g.ceiling_w,
achievable_w=self.site_rating_w))
# SAFETY-81: and for ALARM_HOLD_S, on the projection's clock.
saturated = False
if high:
t = p.block_start + timedelta(seconds=float(p.elapsed_s))
if self._peak_high_since is None:
self._peak_high_since = t
saturated = ((t - self._peak_high_since).total_seconds()
>= peakguard.ALARM_HOLD_S)
else:
self._peak_high_since = None
was, self._peak_saturated = self._peak_saturated, saturated
if not saturated or was:
return
self.log_event("PEAK_GUARD_SATURATED - " + g.reason,
hint=messages.hint("peak_saturated"))
_LOG.error(
"Switch off large loads, the battery alone cannot keep this "
"15-minute period under the peak limit: %s.",
messages.reason_code(g.reason))
_LOG.debug("Evidence: %s.", g.reason)
# SAFETY-81: notified once per quarter; a later episode is logged only.
if p.block_start == self._peak_alarm_block:
return
self._peak_alarm_block = p.block_start
self.log_event("PEAK_GUARD_SATURATED - " + g.reason,
hint=messages.hint("peak_saturated"))
# A fixed notification_id, and a DIFFERENT one from every other alarm
# here - check_meter_frozen() gives the reasoning. A saturated peak guard
# is not a frozen meter and is not an out-of-range setpoint.
+34
View File
@@ -866,6 +866,40 @@ def decide(projection, *, batt_w, cap_w, margin_w, reading, achievable_w, soc,
if saturated else "")))
# SAFETY-81. A quarter must end this many W over the real limit before
# "Load too high for battery" fires. Above the guard's own landing error at
# margin 0 (up to +5.7 W, SAFETY-79 test check 5), which margin 0 accepts.
ALARM_MISS_W = 10.0
# ...and for this long without a break, so a load that peaks for a few seconds
# (a hob or heater cycling) is not read as the rest of the quarter.
ALARM_HOLD_S = 10.0
def load_too_high(projection, *, batt_w, ceiling_w, achievable_w) -> bool:
"""SAFETY-81. May "Load too high for battery" fire? Only if, with the
battery at full power from now on, the quarter still ends more than
`ALARM_MISS_W` over the real limit (`ceiling_w`, not the aim).
This is the miss itself, in W of the quarter average, so it does not have
`decide()`'s gain (900 / remaining): near a quarter's end that gain turns
a watt over the aim into thousands of W wanted.
The load is the held meter reading plus `batt_w`. The caller passes the
lower of this cycle's and the last cycle's battery reading, so a meter
sample taken before the battery's last increase is not counted twice
(DECISIONS/SAFETY-81-load-too-high.md). A real overload shows on the meter
before the battery moves, so that filter costs it no cycle.
"""
remaining = QUARTER_S - float(projection.elapsed_s)
if batt_w is None or remaining <= 0.0:
return False
rest = float(projection.held_w) + float(batt_w) - float(achievable_w)
done_ws = (QUARTER_S * float(projection.projected_w)
- max(float(projection.held_w), 0.0) * remaining)
ends_w = (done_ws + max(rest, 0.0) * remaining) / QUARTER_S
return ends_w - float(ceiling_w) > ALARM_MISS_W
def charge_headroom_w(decision) -> float | None:
"""SAFETY-45. The hardest this SITE may charge without putting the billed
quarter over the ceiling, in W, positive - or None when nothing measured it.
+7
View File
@@ -1259,6 +1259,13 @@ check(f"the saturating fixture ({NET2:.0f} W) is a load the real ingest "
f"accepts, not one it rejects as implausible", NET2 < PLAUSIBLE_MAX_W)
print(f" saturated case: {c2.peak_guard.explain()}")
check("a load larger than the inverter saturates the guard", c2.peak_guard.saturated)
# SAFETY-81 review: the alarm must hold ALARM_HOLD_S first. The fixture runs on
# the wall clock, so the start of the hold is moved back instead of waited out.
check("...but not on its first cycle: it must hold peakguard.ALARM_HOLD_S "
"(SAFETY-81)", hass2.notifications.count("goodwe_peak_saturated") == 0
and c2._peak_high_since is not None)
c2._peak_high_since -= timedelta(seconds=peakguard.ALARM_HOLD_S)
asyncio.get_event_loop_policy().new_event_loop().run_until_complete(c2.cycle())
check("...and THAT raises exactly one notification, with its own id - the one "
"state where the money will be spent and a human is the only remaining "
"actuator", hass2.notifications.count("goodwe_peak_saturated") == 1)
+171
View File
@@ -0,0 +1,171 @@
"""Runnable check for SAFETY-81, no false "Load too high for battery" alarms.
`python3 test_safety81.py`
Drives the REAL Controller through tools/safety81_sim.py (a 1 s cycle on a
plant shaped like the SAFETY-79 rig, one sample in ten late).
DECISIONS/SAFETY-81-load-too-high.md has the record.
1. Every command is byte-identical to release/1.0 5a4cdc2.
2. No alarm on the quarter-edge spike, the last seconds, noise (margin 50
and 0) or a burst the quarter absorbs.
3. Real overloads still alarm, ALARM_HOLD_S after 5a4cdc2.
4. peakguard.load_too_high() on its own.
5. The hold across a cycle with no battery reading (review).
Mutations (MUTATION.md, purged copies) are listed in the pull request.
"""
import asyncio
import os
import sys
from datetime import datetime, timedelta, timezone
from types import SimpleNamespace
HERE = os.path.dirname(os.path.abspath(__file__))
sys.path.insert(0, os.path.join(HERE, "tools"))
import safety81_sim as sim # noqa: E402
from app.main import Controller # noqa: E402
from app.peakguard import load_too_high # noqa: E402
fails = []
def check(name, cond):
print(f" {'ok ' if cond else 'FAIL'} {name}")
if not cond:
fails.append(name)
# Printed by `python3 tools/safety81_sim.py` on release/1.0 5a4cdc2 (the tool
# copied in, nothing else changed), in the CI image: (alarm times, digest).
BASE = {
"const4500": ([2699.0], "6ba6b8634f0df9526adc04f03c82db7d083973268deda0d1f07c5519bc2e5e9d"),
"const4500_m0": ([2699.0], "2bede28f3ea6ba9294be134c9b9733e43d22a7c24deac3bf8210bbbbe09b2039"),
"sine4500": ([2699.0], "bf70c2c23a0eede40c34478d1354b7daa1858e0a0f920693e2dd15fb5046120f"),
"edge4600": ([2.0, 902.0, 1802.0, 2699.0], "3cc0c6fec0c70f138530955babc2b416fe7307373037c1b2e927b6ccdaad3a4d"),
"edge4600_m0": ([2.0, 902.0, 1802.0, 2699.0], "ba9ba2c042ee42b043315b996ece38b3478dc9866aaf833256c9c29c02f0fe9f"),
"burst_end": ([881.0, 1781.0, 2681.0], "5f70e1eb4244820f1d44b494cb80e51f1a4486dee03357c9a8e8f7d371c5d9af"),
"noise5000_m50": ([292.0, 2551.0, 2698.0], "48b446e1a78e6d6032b31cb68a4eadb0f74e3aec4cc1e184162e9c65449bfdc5"),
"noise5000_m0": ([292.0, 2552.0, 2698.0], "1a0527dee6c2b03dc95a90b4682858c7bf5edf7205c2aced249112f04328c960"),
"step6500": ([1201.0, 1801.0], "95e5c90e4a6814526cb4f3bea76286063b449d86a420f888c014531fb6e913a3"),
"miss5560": ([1201.0, 1801.0], "cd991cfe1685750598236701a5a2f2f0342d66645609c536d42ab7ba07216e6c"),
"ramp6500": ([1296.0, 1801.0], "8db7675535f1a01abf38bd6bfb996a6fe57711d3ecca53541bb1c0870748c46b"),
"step7500_reserve": ([], "21eb9c07a4582f47f347084d1c75a28a5d767bc068bc3f74f32433d3239e9ccb"),
# Added in review, printed the same way.
"sine4500_fast": (["112, about one per 30 s"], "710008fd8f2d33a0e2cbb9a626bedafd6d87bc23712bbc5b74a4af9b3ec21897"),
"twice7000": ([1001.0, 1502.0, 2699.0], "1cddda8cf35859efb2ad503f1683f744cb812a6325a390c4fa3df19d717af043"),
"step6500_gap": ([1201.0, 1801.0], "95e5c90e4a6814526cb4f3bea76286063b449d86a420f888c014531fb6e913a3"),
}
OUT = {k: sim.run(**v) for k, v in sim.SCENARIOS.items()}
RUN = {k: v[:2] for k, v in OUT.items()}
ERR = {k: v[4] for k, v in OUT.items()}
# ============================================================================ #
print("1. every command byte-identical to release/1.0 5a4cdc2")
check("the same scenarios as 5a4cdc2", set(RUN) == set(BASE))
for k, (alarms, digest) in RUN.items():
check(f"{k}: digest {digest[:12]}", digest == BASE[k][1])
# ============================================================================ #
print("2. no false alarm (5a4cdc2's are listed)")
for k in ("edge4600", "edge4600_m0", "const4500", "const4500_m0", "sine4500",
"noise5000_m50", "noise5000_m0", "burst_end", "sine4500_fast"):
check(f"{k}: none (5a4cdc2: {BASE[k][0]})", RUN[k][0] == [])
# ============================================================================ #
print("3. real overloads still alarm, ALARM_HOLD_S after 5a4cdc2")
# ALARM_HOLD_S (10 s) plus up to 2 s of late meter samples; at 1800 s the
# quarter-edge tick restarts the hold.
for k, want in (("step6500", [1211.0, 1813.0]),
("miss5560", [1213.0, 1813.0])):
print(f" {k}: load steps up at 1200 s; alarms at {RUN[k][0]}, "
f"5a4cdc2 {BASE[k][0]}")
check(f"{k}: after the hold, and again only at the next quarter",
RUN[k][0] == want)
check("step6500_gap: cycles stopped by a lost battery reading do not "
"restart the hold",
RUN["step6500_gap"][0] == [1215.0, 1813.0])
check("twice7000: notified once in the quarter (5a4cdc2: "
f"{BASE['twice7000'][0]})", RUN["twice7000"][0] == [1011.0])
check("twice7000: the ERROR line for both overloads",
ERR["twice7000"] == [1011.0, 1512.0])
# By design: until 1306 s (then the hold) this quarter would end at most
# ALARM_MISS_W over the real 3500 W cap; 5a4cdc2 alarmed at the aim (cap - 50).
print(f" ramp6500: alarms at {RUN['ramp6500'][0]}, "
f"5a4cdc2 {BASE['ramp6500'][0]}")
check("ramp6500: alarms once the quarter will end over the real cap by "
"more than ALARM_MISS_W",
RUN["ramp6500"][0] == [1316.0, 1813.0])
check("step7500 under the peak reserve: not this alarm (the guard is not "
"allowed to discharge)", RUN["step7500_reserve"][0] == [])
# ============================================================================ #
print("4. load_too_high()")
def proj(elapsed, done_avg, held):
"""A projection `elapsed` s in, averaging `done_avg` so far."""
r = 900.0 - elapsed
return SimpleNamespace(elapsed_s=elapsed, held_w=held,
projected_w=(done_avg * elapsed + max(held, 0) * r)
/ 900.0)
def ltl(p, batt, cap=3500.0, rail=2000.0):
return load_too_high(p, batt_w=batt, ceiling_w=cap, achievable_w=rail)
check("load 6000 W vs 3500 + 2000: yes", ltl(proj(300, 3450, 4000), 2000))
check("already over, the battery can carry the load but not catch up: yes",
ltl(proj(450, 7200, 7200), 0, rail=5000))
check("the last second, a 7 W miss (under ALARM_MISS_W): no",
not ltl(proj(899, 3509, 2500), 1000))
check("a miss of exactly ALARM_MISS_W: no",
not ltl(proj(450, 3520, 3500), 2000))
check("...and 1 W more: yes", ltl(proj(450, 3522, 3500), 2000))
check("over cap + battery, but the quarter lands under the cap: no",
not ltl(proj(880, 3450, 4000), 2000))
check("...and when it does not: yes", ltl(proj(700, 3450, 4000), 2000))
check("no battery reading: no", not ltl(proj(300, 3450, 5000), None))
check("no seconds left: no", not ltl(proj(900, 4000, 5000), 2000))
check("a quarter already over is not won back by export: yes",
ltl(proj(800, 3950, 1000), 0))
# ============================================================================ #
print("5. the hold across a cycle with no battery reading")
# A reading the stale detector drops (STALE_READING) reaches the alarm as None
# while the cycle still runs. Unknown is not "fine": it must not restart the
# hold. Driven on Controller.check_peak_saturated() itself, with stubs.
Q0 = datetime(2026, 9, 20, 11, 0, tzinfo=timezone.utc)
notes = []
async def _call(domain, service, data):
notes.append(data.get("notification_id"))
stub = SimpleNamespace(
peak_guard=SimpleNamespace(saturated=True, ceiling_w=3500.0,
reason="PEAK_GUARD: fixture"),
site_rating_w=2000.0, shadow=False, events=[],
_peak_batt_prev=None, _peak_alarm_block=None, _peak_high_since=None,
_peak_saturated=False, hass=SimpleNamespace(call=_call),
log_event=lambda msg, hint=None: None)
first = None
for sec in range(0, 30):
stub.site_batt_w = None if 4 <= sec < 8 else 2000.0
p = proj(300 + sec, 3450, 6000)
p.block_start = Q0
stub._peak_proj = p
asyncio.run(Controller.check_peak_saturated(stub))
if notes and first is None:
first = sec
check(f"a 4 s gap in the battery reading: alarm at {first} s, not 18 s",
first == 10)
print()
if fails:
print(f"FAILED: {len(fails)} check(s)")
sys.exit(1)
print("all checks passed")
+229
View File
@@ -0,0 +1,229 @@
#!/usr/bin/env python3
"""SAFETY-81: when does "Load too high for battery" fire?
python3 tools/safety81_sim.py # alarms and a control digest per run
The REAL Controller (read_inputs + cycle) at a 1 s cycle, on a plant shaped
like the SAFETY-79 test rig: one battery switched Off (so only the peak guard
makes it give, max 2000 W), a 3500 W cap, and a P1 meter that publishes
0.3 s before each cycle. The battery reaches a new command 0.5 s after it is
written. One meter sample in ten arrives late (the add-on still holds the one
before), so the held meter reading can predate the battery's last change:
the double count behind the rig's false alarms. The cycle on a quarter
boundary, before the new quarter's first sample, files no peak claim, which
is the rig's 1 s grid spike at each quarter change. Each run returns the
alarm times and a digest of every command, so the same runs show both what
changed and what did not.
"""
import asyncio
import hashlib
import logging
import os
import random
import sys
import tempfile
import time
from datetime import timedelta
sys.path.insert(0, os.path.dirname(os.path.abspath(__file__)))
import opt11_identity as rig # noqa: E402
import app.main as m # noqa: E402
from app import packmode # noqa: E402
from app.main import Controller # noqa: E402
from app.p1 import make_sample, split_signed # noqa: E402
from app.store import unit_key # noqa: E402
TICK = 1.0
SAMPLE_LEAD_S = 0.3 # the meter publishes this long before each cycle
RESPONSE_S = 0.5 # a new command reaches the battery this much later
LATE_P = 0.1 # share of meter samples that arrive late
ALARM = "goodwe_peak_saturated"
def constant(w):
return lambda t: w
def noisy(mean, amp, seed=81):
"""`mean` +/- `amp`, a new uniform value every second."""
rnd = random.Random(seed)
table = {}
def f(t):
k = int(t)
if k not in table:
table[k] = mean + rnd.uniform(-amp, amp)
return table[k]
return f
def sine(mean, amp, period=120.0, noise=50.0):
import math
n = noisy(0.0, noise, seed=79)
return lambda t: mean + amp * math.sin(2 * math.pi * t / period) + n(t)
def step(before, after, at):
return lambda t: before if t < at else after
def ramp(before, after, at, secs):
return lambda t: before + (after - before) * min(max(t - at, 0.0) / secs, 1.0)
class _Plant:
"""One battery that reaches its command RESPONSE_S after the write."""
def __init__(self, load, rating, soc, batt_gap=()):
self.load, self.rating, self.soc = load, rating, soc
self.batt_gap = batt_gap # (from, to): the battery reading is lost
self.t = 0.0
self.hist = [(-1e9, 0.0)] # (time the command takes effect, W)
self.notes = []
self.meter = 0.0 # the last meter reading delivered
def batt(self, at):
w = 0.0
for when, v in self.hist:
if when <= at:
w = v
return max(-self.rating, min(self.rating, float(round(w))))
def grid(self, at):
return self.load(at) - self.batt(at)
async def limits(self, e):
return (-5000.0, 5000.0, 1.0)
async def call(self, domain, service, data):
if service == "create":
self.notes.append((self.t, data.get("notification_id")))
return True
async def number(self, e, invert=False):
if e in ("sensor.grid", "sensor.net"):
return self.meter
if e.startswith("sensor.soc"):
return self.soc
if e.startswith("sensor.batt"):
if self.batt_gap and self.batt_gap[0] <= self.t < self.batt_gap[1]:
return None
return self.batt(self.t)
return None
async def set_number(self, e, v):
self.hist.append((self.t + RESPONSE_S, float(v)))
return True
def run(load, *, margin=50, dur=2700.0, rating=2000.0, cap=3500.0,
late_at=(), soc=60.0, batt_gap=()):
"""Alarm times (s from the start of the first quarter), a digest of every
cycle's target and written command, the Controller, the rows, and the
times of the ERROR log line. A sample is also late at each `t % 900` in
`late_at`."""
opts = rig._options(1, {
"meter_source": "ha_signed", "p1_net_entity": "sensor.net",
"meter_phases": 1, "peak_cap_w": cap, "peak_margin_w": margin,
"battery_modes_enabled": True, "max_w": rating})
store = rig._Store()
store.data[unit_key("inverter-a", packmode.USE_KEY)] = False
store.data[packmode.USE_KEY] = False
db = os.path.join(tempfile.mkdtemp(prefix="s81-"), "tariff.db")
async def go():
plant = _Plant(load, rating, soc, batt_gap)
c = Controller(opts, plant, store, rig._Pub(), stop=asyncio.Event(),
peak_db_path=db)
for i in c.inverters:
i.dev_min, i.dev_max = -5000.0, 5000.0
c.auto = True
real_dt, clock = m.datetime, [0.0]
class _DT(real_dt):
@classmethod
def now(cls, tz=None):
return rig.BASE + timedelta(seconds=clock[0])
m.datetime = _DT
rows, late = [], random.Random(8100)
errors = []
class _Err(logging.Handler):
def emit(self, r):
if "battery alone cannot keep" in r.getMessage():
errors.append(plant.t)
h = _Err()
logging.getLogger("goodwe").addHandler(h)
try:
t = 0.0
while t < dur:
plant.t = clock[0] = t
ts = t - SAMPLE_LEAD_S
if late.random() >= LATE_P and t % 900 not in late_at:
plant.meter = plant.grid(ts)
imp, exp = split_signed(plant.meter)
c.p1.submit(make_sample(
"ha_signed", imp, exp, phases=1,
ingest_ts=rig.BASE + timedelta(seconds=ts),
ingest_mono=time.monotonic()))
await c.read_inputs(now_mono=t)
await c.cycle()
rows.append((t, c.target, round(plant.hist[-1][1], 6)))
t += TICK
finally:
m.datetime = real_dt
logging.getLogger("goodwe").removeHandler(h)
return plant, c, rows, errors
plant, c, rows, errors = asyncio.run(go())
alarms = [t for t, nid in plant.notes if nid == ALARM]
return (alarms, hashlib.sha256(repr(rows).encode()).hexdigest(), c, rows,
errors)
# Three quarters each (2700 s); a new quarter starts at 900 s and 1800 s.
SCENARIOS = {
# F1: constant and sine loads the battery carries, across quarter edges.
"const4500": dict(load=constant(4500.0)),
"const4500_m0": dict(load=constant(4500.0), margin=0),
"sine4500": dict(load=sine(4500.0, 400.0)),
# F1 at the start of a quarter: the sample after the battery's return
# is late, so the held reading is the 1 s spike (the battery at 0 W).
"edge4600": dict(load=constant(4600.0), late_at=(2.0,)),
"edge4600_m0": dict(load=constant(4600.0), margin=0, late_at=(2.0,)),
# 6000 W in a quarter's last 20 s: over cap + battery, but the quarter
# still lands between the aim and the cap.
"burst_end": dict(load=lambda t: 6000.0 if t % 900 >= 880 else 4500.0),
# F2: a noisy load the battery carries, at margin 50 and 0.
"noise5000_m50": dict(load=noisy(5000.0, 150.0)),
"noise5000_m0": dict(load=noisy(5000.0, 150.0), margin=0),
# Real: from 1200 s the house needs 1000 W more than cap + battery.
"step6500": dict(load=step(4500.0, 6500.0, 1200.0)),
# Real, small: from 1200 s, 60 W (+/- 20 W noise) more than cap + battery.
"miss5560": dict(load=lambda t: step(4500.0, 5560.0, 1200.0)(t)
+ noisy(0.0, 20.0)(t)),
# Real, slow: 4500 -> 6500 W over 200 s from 1200 s, through the band
# between the aim (cap - 50) and the real cap.
"ramp6500": dict(load=ramp(4500.0, 6500.0, 1200.0, 200.0)),
# The pack under its peak reserve (20 %), and a load far over cap +
# battery: that is "Battery stopped limiting the peak", not this alarm.
"step7500_reserve": dict(load=step(4500.0, 7500.0, 1200.0), soc=15.0),
# Review: a load swinging 4500 +/- 1200 W every 30 s (a hob or heater
# cycling). It tops cap + battery for about 5 s a swing, and the quarter
# still lands under the aim.
"sine4500_fast": dict(load=sine(4500.0, 1200.0, period=30.0, noise=200.0)),
# Review: two real overloads in one quarter, 1000-1100 s and 1500-1700 s.
"twice7000": dict(load=lambda t: 7000.0 if (1000 <= t < 1100
or 1500 <= t < 1700)
else 4500.0),
# Review: step6500, and the battery reading is lost 1203-1215 s.
"step6500_gap": dict(load=step(4500.0, 6500.0, 1200.0),
batt_gap=(1203.0, 1215.0)),
}
if __name__ == "__main__":
for k, v in SCENARIOS.items():
a, d, _, _, _ = run(**v)
print(f"{k:16s} alarms at {a} digest {d}")