Merge pull request 'SAFETY-31 AC 4: the alarm's attribution was graded by nothing, and a mutation proved it' (#68) from SAFETY-31-attribution into release/1.0
This commit was merged in pull request #68.
This commit is contained in:
@@ -149,8 +149,70 @@ each swept across the **whole range `config.yaml` accepts** for the two settings
|
||||
that decide how fast the site can turn around: `gain` `float(0.05,1.0)` and
|
||||
`slew_w` `int(50,5000)`.
|
||||
|
||||
### ⚠️ THE HARNESS BEHIND EVERY FIGURE ABOVE IS NOT COMMITTED, AND UNTIL 2026-09-07 THAT MADE THEM UNCHECKABLE
|
||||
|
||||
**Read this before quoting any number in this section.** The paragraph below
|
||||
said the campaign harness "is not committed here" and treated that as a
|
||||
packaging detail. It is not: a figure produced by a script that exists in
|
||||
nobody's tree cannot be re-run, cannot be reviewed, and cannot be defended when
|
||||
it is contradicted. It has now been contradicted twice.
|
||||
|
||||
| sweep | worst peak | worst continuous | trips |
|
||||
|---|---:|---:|---:|
|
||||
| the 924-run campaign below — **harness uncommitted** | 1700 W | 505.0 s at 100 W; 5.0 s above 700 W | 0 / 924 |
|
||||
| independent reviewer sweep, 2026-09-07, 48 honest reversals | **2750 W** | **15.0 s above 700 W** | 0 / 48 |
|
||||
| `admin/goodwe` `two_master_circulation`, 840 runs — **committed** | 1048 W | 10.0 s at 100 W; 5.0 s above 700 W | **0 / 840** |
|
||||
|
||||
**This is not proof that anything was fabricated, and it should not be reported
|
||||
as one.** The three swept different grids. What the third one adds is a
|
||||
measurement of *why* the spread is that wide — on one grid, changing nothing but
|
||||
the model:
|
||||
|
||||
| plant / stagger | worst legitimate peak |
|
||||
|---|---:|
|
||||
| modelled plant (lag 10 s, ramp 800 W/s), staggers up to a whole cycle | 1048 W |
|
||||
| `INSTANT` (lag 0, unbounded ramp), staggers up to a whole cycle | 2250 W |
|
||||
| `INSTANT`, staggers strictly under a whole cycle | **0 W** |
|
||||
|
||||
A factor of 2.1×, and a factor of infinity, between three defensible
|
||||
descriptions of the same rig. **The plant model and the write-stagger set are
|
||||
terms of the number**, and a worst case quoted without them is not a
|
||||
measurement. That is enough to explain the whole spread above without anybody
|
||||
having invented anything — and it is exactly what cannot be established when the
|
||||
instrument is missing.
|
||||
|
||||
**What survives, and what does not.**
|
||||
|
||||
* **The window argument survives, and is now committed.** The claim that
|
||||
decides `circulation_hold_s: 75` is *"the worst continuous legitimate episode
|
||||
above 700 W is about one control cycle"*. All three sweeps agree on the shape
|
||||
of that (5.0 s, 15.0 s, 5.0 s — one to three cycles against a fifteen-cycle
|
||||
window), and **all three trip zero times**. `two_master_circulation` re-runs
|
||||
it on every pull request in `admin/goodwe`.
|
||||
* **The threshold curve does NOT survive as stated.** `505.0 s at 100 W` is the
|
||||
number the "knee at 400 W" argument for `circulation_w: 700` rests on, and the
|
||||
committed sweep measures **10.0 s** at 100 W on its grid — 50× smaller. The
|
||||
curve still *falls* with the threshold (126 of 840 runs cross 100 W against 1
|
||||
that crosses 700 W), so the knee is real in direction; its depth is not
|
||||
established by anything anybody can run. **Do not quote 505.0 s.**
|
||||
* **Nothing about the guard is compromised.** 0 trips in 924 + 48 + 840
|
||||
non-faulty runs, from three independent grids.
|
||||
|
||||
**What would settle it:** the original harness, committed. Until then the
|
||||
committed sweep is the only figure in this section anybody can check, and it is
|
||||
labelled as its own grid's rather than as a reproduction.
|
||||
|
||||
### Reproducing it
|
||||
|
||||
⚠️ **THE COMMITTED VERSION IS `admin/goodwe`'s `sim/inject.py
|
||||
two_master_circulation`** (`sim/sitesim.py:circulation_findings`, runnable on its
|
||||
own as `python3 sim/sitesim.py --circulation`, `norig`, ~36 s, graded by
|
||||
`checks.yml` on every pull request there). It produces the fault with
|
||||
`plantsim.Inverter.wedge()` — a unit answering its bus and no longer steering its
|
||||
power stage, which is HW-01 — and sweeps the legitimate family with the
|
||||
serialised write path staggered up to a whole control cycle. The paragraph below
|
||||
describes the ORIGINAL campaign, which is the one that is not committed.
|
||||
|
||||
The rig lives in `admin/goodwe` (`sim/`) and was used **read-only**; the harness
|
||||
is not committed here because it imports that repo's `plantsim`/`frame_check`,
|
||||
which are not present in this one or in CI. What it does is small enough to
|
||||
@@ -206,7 +268,11 @@ margin above the knee is what absorbs that without re-opening this card.
|
||||
**Revisit when SPIKE-04 lands, not before.**
|
||||
|
||||
The **schema floor is the knee itself**, 400 W, so a legally configured install
|
||||
cannot land in the 445–505 s regime. What the threshold costs: a circulating
|
||||
cannot land in the 445–505 s regime — ⚠️ and those two figures are from the
|
||||
uncommitted campaign; the committed sweep measures 10.0 s at 100 W on its own
|
||||
grid. See the disclosure at the head of this section. The floor is still the
|
||||
right shape (fewer runs cross a higher threshold, measured 126/840 at 100 W
|
||||
against 1/840 at 700 W); its DEPTH is not established by anything re-runnable. What the threshold costs: a circulating
|
||||
loop smaller than 350 W per unit is not reported, which is deliberate — at that
|
||||
scale the round-trip loss is a few watts.
|
||||
|
||||
@@ -289,6 +355,32 @@ SAFETY-25 — so no stale `.pyc` could exist to be read. Byte deltas recorded;
|
||||
| M17 | `circulation.py` | default `700` → `500` | **+0 B** | **RED** — the CFG-03 pin and the not-a-round-number check |
|
||||
| M18 | `main.py` | `await self.check_circulating()` removed | −39 B | **RED** — all four notification checks |
|
||||
| M19 | `main.py` | publish `round(x or 0.0)` instead of `None` | −68 B | **survivor on the first battery — GAP CLOSED**, then RED |
|
||||
| **M20** | `main.py` | **`pos, neg = opposing(...)` → `([], [])`** — the attribution clause deleted from the alarm | −102 B | **SURVIVED ALL 26 FILES on the shipped battery — GAP CLOSED**, then RED on §6a |
|
||||
| M21 | `main.py` | `pos` and `neg` exchanged — the alarm names both packs, both the wrong way round | **+0 B** | **RED** — §6a ×3 (the mirrored run, and "only its own sentence") |
|
||||
| M22 | `main.py` | `opposing(..., min_w=cfg.min_w / 2.0)` → `min_w=0.0` | −25 B | **RED** — §6a's resting-pack check |
|
||||
|
||||
**And four in `admin/goodwe`**, graded through `python3 sim/sitesim.py
|
||||
--circulation` rather than through the injector — deliberately, because
|
||||
`inject.py` is the file that takes the rig lock, and "run the injector to grade a
|
||||
mutation" is not a sentence anybody should have to type. Byte deltas over
|
||||
`plantsim.py` + `sitesim.py` together.
|
||||
|
||||
| # | file | mutation | Δ | result |
|
||||
|---|---|---|---|---|
|
||||
| S1 | `plantsim.py` | `wedge()` no longer stops the latch reaching the power stage | −20 B | **RED** — the opposing-signs precondition **and** "the watchdog did not trip" |
|
||||
| S2 | `sitesim.py` | the sensor computed over the **allocation record** instead of register 0x0518 | **+0 B** | **RED** ×3 — this is M10 restated on the rig |
|
||||
| S3 | `sitesim.py` | the campaign run on `plant=INSTANT` | −51 B | **RED** — the plant is a *term* of the figures; it was a SURVIVOR until that check was added, and finding out why produced §3's 1048/2250/0 W table |
|
||||
| S4 | `sitesim.py` | the write stagger removed from the legitimate campaign | −19 B | **RED** — "the legitimate campaign produced no opposition at all" |
|
||||
|
||||
**S3 is recorded as a survivor because it was one, and it is the most useful
|
||||
result in this table.** The scenario first shipped with a vacuity check whose
|
||||
text claimed `plant=INSTANT` would make the sweep measure 0 W. S3 was run and
|
||||
**passed**: `INSTANT` with a stagger of exactly one control cycle samples the
|
||||
plant before the second unit has stepped, so it produces opposition anyway — and
|
||||
a *larger* worst peak (2250 W) than the modelled plant does (1048 W). The claim
|
||||
in the check's own text was wrong. It was corrected against the measurement, the
|
||||
plant was pinned as an explicit term, and S3 is red now for a stated reason
|
||||
rather than by accident. §3's spread table is that measurement.
|
||||
|
||||
**M19 is recorded as a survivor because it was one.** The first battery found no
|
||||
check grading what `publish()` does when a per-unit reading is missing, so
|
||||
@@ -297,6 +389,30 @@ watches went unnoticed — the sensor's own `None` rule, defeated one layer out.
|
||||
A check was added and the mutation re-run; it is red now. The run that found it
|
||||
was purged, so it is a result and not an artefact.
|
||||
|
||||
**M20 IS RECORDED AS A SURVIVOR BECAUSE IT WAS ONE, AND IT IS THE MORE
|
||||
UNCOMFORTABLE OF THE TWO.** The commit message for this card claimed *"18
|
||||
mutations, all RED"*, and M1–M19 above have no entry for the notification's
|
||||
attribution clause. Verification on 2026-09-07 ran it and it **survived the
|
||||
whole 26-file suite**: the alarm still fires, still stops the site, still says
|
||||
the meter cannot see it — and no longer says *which two packs* or *which way
|
||||
round*. `circulation.py`'s own docstring calls that sentence the first thing
|
||||
somebody woken by this alarm needs and *"impossible to reconstruct from the
|
||||
number alone"*.
|
||||
|
||||
It survived for one reason, and it is not reachability: **M18 (the whole call
|
||||
removed) is red**, so `check_circulating()` is exercised. The three checks on
|
||||
that notification asserted `METER CANNOT SEE`, `CONTROL HAS BEEN STOPPED` and
|
||||
`isolator` — and **never an inverter name**. Nothing graded the attribution.
|
||||
|
||||
`test_watchdog.py` §6a closes it, and closes it on a fixture that can tell the
|
||||
three failures apart. It runs a roster of **`["garage", "shed", "cellar"]`** —
|
||||
operator names, none of them `UNIT_A`, for test_maintenance.py §11's reason:
|
||||
on a fixture whose names are the module's own constants a check cannot tell the
|
||||
roster from the constant. It runs the site **twice, mirrored**, so the sentence
|
||||
is not symmetric and a swap (M21, `+0 B`) is a different red from a deletion.
|
||||
And it carries a **third pack resting at 5 W**, so the floor that stops a pack
|
||||
in standby being named as a participant in a 6 kW loop (M22) is graded too.
|
||||
|
||||
## 7. What this card does NOT close
|
||||
|
||||
* **Inverter B's ramp and lag are placeholders.** Every transient number in §3
|
||||
@@ -305,7 +421,9 @@ was purged, so it is a result and not an artefact.
|
||||
margin. **Do not present any figure here as a measurement of inverter B.**
|
||||
* **A wedged inverter still cannot be stopped by this add-on.** §1 says so; the
|
||||
notification says so; there is no software fix and this card does not pretend
|
||||
to one.
|
||||
to one. It *can* now be produced on demand: `plantsim.Inverter.wedge()`.
|
||||
* **The depth of the threshold curve is not established by anything committed.**
|
||||
§3's disclosure. The window is; the knee's magnitude is not.
|
||||
* **A loop below ~350 W per unit is not reported.** Deliberate, §3.
|
||||
* **The saturation freeze fires under a wedged unit and leaves a standing grid
|
||||
error.** Observed on the rig while producing §2's numbers: with B wedged, the
|
||||
|
||||