A meter gap past meter_max_age_s left seconds the quarter average never counted, so the guard was blind for the rest of the quarter (rig case 7b: 3964.8 W against a 3450 W aim). Once readings are back, the missed seconds now count at the higher of the limit and the import seen just before and just after the gap with the batteries at 0 W (peakguard.gap_w/fill_gaps); the gap's first meter_max_age_s is topped up to that too. Seconds before the add-on's first reading count at the aim, and the page says part of the period was not measured (EN/NL). The bill record is unchanged; no option. DECISIONS/SAFETY-90-peak-guard-after-a-gap.md, test_safety90.py. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
This commit is contained in:
@@ -0,0 +1,73 @@
|
||||
# SAFETY-90 - the peak guard goes on after a P1 meter gap
|
||||
|
||||
**Status: DEV 2026-10-05, for review.** Tests: `test_safety90.py`.
|
||||
|
||||
**The defect.** A meter gap longer than `meter_max_age_s` leaves seconds the
|
||||
quarter average does not count (`p1.QuarterAverager`, on purpose: a guess must
|
||||
not reach the bill record). `peakguard.blindness()` then called the projection
|
||||
blind for the rest of the quarter, so the floor was 0 W. During a HOLD the
|
||||
battery gave nothing and the quarter went over: SAFETY-86 rig case 7b, N=2,
|
||||
3964.8 W against a 3450 W aim, the month peak raised; N=1, 3701 W (review).
|
||||
The page still read "Keeping the grid near zero". At start-up mid-quarter the
|
||||
same rule left the start-up quarter blind, and a held battery was drawn as last
|
||||
resort (SAFETY-91 test, O2).
|
||||
|
||||
**The fix** (`peakguard.fill_gaps()`, `peakguard.gap_w()`,
|
||||
`Controller._fill_peak_gaps()`).
|
||||
- Once readings are back, every second of a silence longer than
|
||||
`meter_max_age_s` counts at `gap_w = max(the limit, the import just before
|
||||
the gap, the import just after it)`, where "import" is the grid plus the
|
||||
batteries' discharge, i.e. with the batteries at 0 W. The gap's first
|
||||
`meter_max_age_s`, which the averager credits at the last reading, is topped
|
||||
up to `gap_w` too. The guard then grades the quarter as usual, so it is not
|
||||
blind and gives what keeps the quarter at the aim.
|
||||
- **The bound.** The count is at or above the true import as long as, during
|
||||
the gap, the house load stayed at or under the higher of the loads seen just
|
||||
before and just after it, or under the limit, and the batteries did not
|
||||
start charging (during a gap they hold their last command, then go to 0 W).
|
||||
It never counts the gap below the limit. A load that rises above all three
|
||||
only inside the gap is the one case it can miss.
|
||||
- **Cost of the bound.** It is conservative: with the house at 6500 W, a 30 s
|
||||
to 5 min gap lands the quarter 100-180 W under the aim (table below), paid in
|
||||
battery energy.
|
||||
- **While the gap lasts** nothing changes: the reading is too old to steer by,
|
||||
the guard is blind (floor 0 W) and the "inputs missing" stop sets 0 W, as
|
||||
before.
|
||||
- **Before the first reading** (start-up or restart mid-quarter) nothing is
|
||||
known, not even the house load, so a conservative count has no basis: the
|
||||
connection rating would make every restart drain at full power and raise
|
||||
"Load too high". Those seconds count **at the aim**, so the guard keeps the
|
||||
rest of the quarter on the aim, and the page says so: the status row "Peak
|
||||
guard: part of this 15-minute period was not measured, counted as on
|
||||
target" and the home line "Part of this 15-minute period was not measured." /
|
||||
"Een deel van dit kwartier is niet gemeten." until the quarter ends.
|
||||
- The bill record (`quarter_blocks`) is unchanged: it still banks only what
|
||||
was measured. The estimate steers the guard and is never banked.
|
||||
- The action log gets one `PEAK_GUARD_GAP` row per gap, with the seconds and
|
||||
the watts it was counted at.
|
||||
- No option. The threshold is `meter_max_age_s`, the limit and the aim are
|
||||
`peak_cap_w` and `peak_margin_w`.
|
||||
|
||||
**Before -> after** (`test_safety90.py`, quarter as the meter really averages
|
||||
it, gap starting 300 s in; 10 s battery lag; aim 3450 W):
|
||||
|
||||
| case | before | after |
|
||||
|---|---|---|
|
||||
| N=1 HOLD 6500 W, gap 30 s / 60 s | 3456.6 / 5329.2 | 3346.2 / 3272.2 |
|
||||
| N=1 HOLD 5500 W, gap 5 min | 4717.9 | 3330.6 |
|
||||
| N=2 HOLD, B able, 6500 W, gap 30 s / 60 s | 3456.6 / 3865.6 | 3346.3 / 3272.7 |
|
||||
| N=2 HOLD, B able, 5500 W, gap 5 min | 3745.4 | 3288.9 |
|
||||
| N=2 HOLD, B held, 5500 W, gap 60 s | 3254.9, B drawn 2500 W | 3335.4, B 0 W |
|
||||
| gap across the edge, next quarter, N=1 / N=2 | 4100.0 / 3621.2 | 3446.3 / 3382.2 |
|
||||
| house 3000 -> 6500 W inside a 60 s gap, N=1 | 5255.6 | 3368.3 |
|
||||
| house 6500 -> 2000 W late in a 5 min gap, N=1 | 3629.2 | 3145.1 |
|
||||
| start-up 450 s into the quarter, N=1 (first half at the aim) | 4975.0 | 3450.0 |
|
||||
| meter never drops, N=1 and N=2 | | rows identical |
|
||||
|
||||
**Not changed.** The late-reading edge (SAFETY-91 test, O1): a reading late by
|
||||
less than `meter_max_age_s` is not a gap, and the seconds since it are not
|
||||
counted in the projection (on any quarter, not only after a gap). Near a
|
||||
quarter's end the 900/remaining gain turns that into a large negative excess
|
||||
and the floor drops for a cycle or more. Counting those seconds at the held
|
||||
reading would fix it, but it changes every quarter's last seconds on a
|
||||
healthy meter; it is handed back as its own card.
|
||||