SAFETY-90 review: count the start-up seconds like a gap
While the add-on is down the batteries are at 0 W (it sets 0 W when it stops; the ESP32 watchdog after 30 s), so the import before its first reading was the house, not the aim. Those seconds now count at gap_w(limit, the import seen first), and after a restart the restored reading's held 30 s is topped up the same way. Status row: "counted as high use". Tests take the pre-start import as the house (batteries at 0 W) and add restarts of 10/60/150 s with a restored averager. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
This commit is contained in:
@@ -22,7 +22,7 @@ resort (SAFETY-91 test, O2).
|
||||
up to `gap_w` too. The guard then grades the quarter as usual, so it is not
|
||||
blind and gives what keeps the quarter at the aim.
|
||||
- **The bound.** The count is at or above the true import as long as, during
|
||||
the gap, the house load stayed at or under the higher of the loads seen just
|
||||
the gap, the house load (less solar) stayed at or under the higher of the loads seen just
|
||||
before and just after it, or under the limit, and the batteries did not
|
||||
start charging (during a gap they hold their last command, then go to 0 W).
|
||||
It never counts the gap below the limit. A load that rises above all three
|
||||
@@ -33,14 +33,21 @@ resort (SAFETY-91 test, O2).
|
||||
- **While the gap lasts** nothing changes: the reading is too old to steer by,
|
||||
the guard is blind (floor 0 W) and the "inputs missing" stop sets 0 W, as
|
||||
before.
|
||||
- **Before the first reading** (start-up or restart mid-quarter) nothing is
|
||||
known, not even the house load, so a conservative count has no basis: the
|
||||
connection rating would make every restart drain at full power and raise
|
||||
"Load too high". Those seconds count **at the aim**, so the guard keeps the
|
||||
rest of the quarter on the aim, and the page says so: the status row "Peak
|
||||
guard: part of this 15-minute period was not measured, counted as on
|
||||
target" and the home line "Part of this 15-minute period was not measured." /
|
||||
"Een deel van dit kwartier is niet gemeten." until the quarter ends.
|
||||
- **Before the first reading** (start-up or restart mid-quarter) the
|
||||
add-on was down, so the batteries were at 0 W (it sets 0 W when it stops,
|
||||
the ESP32 watchdog after 30 s). Those seconds count like a gap, at
|
||||
`gap_w(the limit, the import seen first)`; after a restart the restored
|
||||
reading's held `meter_max_age_s` is topped up the same way. The bound is
|
||||
the gap's, with only the "after" side known. A load the batteries cannot
|
||||
make up then raises "Load too high", which is true: that quarter is going
|
||||
over. The page says so: the status row "Peak guard: part of this
|
||||
15-minute period was not measured, counted as high use" and the home line
|
||||
"Part of this 15-minute period was not measured." / "Een deel van dit
|
||||
kwartier is niet gemeten." until the quarter ends.
|
||||
*Review:* the first version counted them at the aim, with "nothing is
|
||||
known" as the reason. The first reading does show the load, and with the
|
||||
batteries at 0 W the import was that load, not the aim: a 60 s restart
|
||||
during a 6500 W HOLD landed 3653 W against 3450 W.
|
||||
- The bill record (`quarter_blocks`) is unchanged: it still banks only what
|
||||
was measured. The estimate steers the guard and is never banked.
|
||||
- The action log gets one `PEAK_GUARD_GAP` row per gap, with the seconds and
|
||||
@@ -61,7 +68,8 @@ it, gap starting 300 s in; 10 s battery lag; aim 3450 W):
|
||||
| gap across the edge, next quarter, N=1 / N=2 | 4100.0 / 3621.2 | 3446.3 / 3382.2 |
|
||||
| house 3000 -> 6500 W inside a 60 s gap, N=1 | 5255.6 | 3368.3 |
|
||||
| house 6500 -> 2000 W late in a 5 min gap, N=1 | 3629.2 | 3145.1 |
|
||||
| start-up 450 s into the quarter, N=1 (first half at the aim) | 4975.0 | 3450.0 |
|
||||
| start-up 450 s in, N=1, house 5000 W (batteries at 0 W before it) | 5000.0 | 3450.0 |
|
||||
| restart, down 60 s / 150 s, N=1, house 6500 W | 4039.1 / 5483.3 | 3450.0 / 3450.0 |
|
||||
| meter never drops, N=1 and N=2 | | rows identical |
|
||||
|
||||
**Not changed.** The late-reading edge (SAFETY-91 test, O1): a reading late by
|
||||
|
||||