# MAINT-28 - during a real peak the maintenance charge stays paused
**Status: for review.** Tests: `test_maint28.py`. No option added; the peak aim, the month peak and the MAINT-13 numbers are unchanged. MAINT-24 follow-up (rig test finding F-1, `reports/MAINT-24-test-report.md`).
## What happened (rig x10, house 6.5 kW, month aim 5.95 kW, A in maintenance CHARGE)
`peakguard.shaping_suspended()` pauses the charge while the forecast is over the aim or the guard is engaged. MAINT-24 moved the aim from 3450 W to the month aim (SAFETY-80), so the pause no longer lasts the whole peak: the guard gives, its projection drops under 5950 W and it idles ("heading for 5 6xx W, under this month's peak"), the pause ends, the floor charges A 150-460 W, the grid goes to 6.3-6.9 kW, the guard trips again. A flipped charge/give 468 times in 45 min (base 02eac3b 11). The quarters stayed at the aim; the cost was a battery working against itself and a grid that swung 5.4-6.9 kW.
## The change
`peakguard.shaping_held(held, decision, forecast, aim, house)`: the old conjunction, and once it was true the pause stays until the house (`grid + battery power`, the load without our own charge) is `MAINT_RESUME_UNDER_W` = 300 W under the aim. A guard that is engaged or a forecast over the aim still pauses at once. House unread: the forecast stands in; neither read: no pause (SAFETY-63). `ctl_cycle.py` keeps the flag in `_maint_peak_hold`.
Why the house and not the forecast: while A gives, the forecast sits just under the aim by design, so no forecast margin is both safe and reachable. The house does not move when A switches.
Why 300 W: the house wanders +-50 W; once the charge resumes it settles at (aim - house) / 2, so 300 W gives at least 150 W, three times the noise, and charging less than that is not worth a restart.
It only ever keeps the maintenance charge off. No cut-back is delayed or weakened: the guard's claim is filed as before. While the pause is held the loop works as at 02eac3b, so A also gives for the house (quarters then sit under the aim, A's energy goes to the load). A cap on that give would conflict with the guard's `lo` (`lo > hi` resolves to 0 W), so it is not tried here.
## Numbers (sim, real `cycle()`, house 3000 -> 6500 W for 45 min -> 3000 W, +-50 W, aim 5950 W, forecast = quarter average so far plus the rest at the present grid; `scratch/MAINT-28/dev/m28_repro.py`)
See the dev report for the table. Live shape (house 3000 W): no pause, A 1475 W, as MAINT-24.
## Not changed
MAINT-24's rate and its tests, N=1, the drain, modes off (digests of 02eac3b). The pause for a late or missing forecast.
+7 -2
View File
@@ -564,8 +564,13 @@ class CycleMixin:
maint_aim = peakguard.quarter_target_w( maint_aim = peakguard.quarter_target_w(
float(self.o.get("peak_cap_w", 3500)), float(self.o.get("peak_cap_w", 3500)),
self.peak_margin_w, _reading) self.peak_margin_w, _reading)
if peakguard.shaping_suspended( # MAINT-28: stays paused until the house is clear of the aim.
self.peak_guard, self.peak_fc, maint_aim): house = (None if self.grid is None or self.site_batt_w is None
else float(self.grid) + float(self.site_batt_w))
self._maint_peak_hold = peakguard.shaping_held(
self._maint_peak_hold, self.peak_guard, self.peak_fc,
maint_aim, house)
if self._maint_peak_hold:
# Edge-logged: level-logging here would write one line per # Edge-logged: level-logging here would write one line per
# cycle for as long as the event lasts and flush the 40-line # cycle for as long as the event lasts and flush the 40-line
# action log of the very context that explains it. # action log of the very context that explains it.
+1
View File
@@ -505,6 +505,7 @@ class Controller(InputsMixin, WritesMixin, TradeMixin, CycleMixin, AlarmsMixin,
self._land_batt_prev = None self._land_batt_prev = None
self._peak_needed = False self._peak_needed = False
self._maint_shape_suspended = False self._maint_shape_suspended = False
self._maint_peak_hold = False # MAINT-28
# OPT-11: battery modes, off by default (SAFETY-10 section 1). Each # OPT-11: battery modes, off by default (SAFETY-10 section 1). Each
# battery's mode and on/off switch live in the store, not in options, # battery's mode and on/off switch live in the store, not in options,
# so a change applies at once (`pack_use`, `pack_mode`). # so a change applies at once (`pack_use`, `pack_mode`).
+18
View File
@@ -28,6 +28,10 @@ FLOOR_AT_SOC_FLOOR = "the battery level is at or below the peak reserve"
SOURCE = "peak" SOURCE = "peak"
# MAINT-28. Watts the house must sit under the aim before a paused maintenance
# charge resumes. DECISIONS/MAINT-28-hold-the-pause-in-a-peak.md.
MAINT_RESUME_UNDER_W = 300.0
# Mirror of config.yaml's peak options, pinned to the file by # Mirror of config.yaml's peak options, pinned to the file by
# test_peakguard.py. Not a read: `decide()` takes them as arguments. # test_peakguard.py. Not a read: `decide()` takes them as arguments.
PEAK_OPTION_DEFAULTS = { PEAK_OPTION_DEFAULTS = {
@@ -446,6 +450,20 @@ def shaping_suspended(decision, peak_forecast_w, cap_w) -> bool:
return decision is not None and decision.engaged return decision is not None and decision.engaged
def shaping_held(held, decision, peak_forecast_w, aim_w, house_w) -> bool:
"""MAINT-28. `shaping_suspended()`, kept on until the house is
`MAINT_RESUME_UNDER_W` under `aim_w` (`peak_forecast_w` stands in for an
unread house; neither read: not held, as SAFETY-63). Only ever pauses the
maintenance charge, never a cut-back.
DECISIONS/MAINT-28-hold-the-pause-in-a-peak.md."""
if shaping_suspended(decision, peak_forecast_w, aim_w):
return True
if not held:
return False
level = house_w if house_w is not None else peak_forecast_w
return level is not None and level > float(aim_w) - MAINT_RESUME_UNDER_W
def cap_floor(decision, cap_w): def cap_floor(decision, cap_w):
"""SAFETY-128: the floor no higher than `cap_w` (the command standing while """SAFETY-128: the floor no higher than `cap_w` (the command standing while
the readings have not answered it), or `decision` unchanged when None. the readings have not answered it), or `decision` unchanged when None.
+231
View File
@@ -0,0 +1,231 @@
"""Runnable check for MAINT-28. `python3 test_maint28.py`
MAINT-24 follow-up. With A in maintenance CHARGE and a real peak (house over
the month aim), MAINT-24's pause ended every time the guard idled: the
forecast dipped under the aim, the floor charged A, the guard tripped again,
and A flipped charge/give every few seconds (rig x10: 468 flips in 45 min,
base 02eac3b 11). Now the pause is held (`peakguard.shaping_held()`) until the
house is MAINT_RESUME_UNDER_W under the aim.
All on the real Controller through `cycle()` (tools/opt20_scen.py): cheap
window, cap 3500 / margin 50, a month peak of 6000 W banked (aim 5950 W), a
peak forecast like the live sensor (quarter average so far, the rest at the
present grid), house +-50 W every 5 s.
1. A real peak (house 3000 W, then 6500 W for 20 min, then 3000 W): once the
guard has stepped in, A does not charge and does not flip; every quarter is
at or under the aim; A's charge is back within 10 cycles after the load.
2. peakguard.shaping_held(): the pure rule, with its edges.
3. Unchanged: the MAINT-24 live shape (A 1475 W, no pause), N=1, the SAFETY-78
drain and battery modes off (digests of release/1.0 02eac3b, as
test_maint24.py).
Mutations: DECISIONS/MAINT-28-hold-the-pause-in-a-peak.md.
"""
import logging
import os
import random
import sys
HERE = os.path.dirname(os.path.abspath(__file__))
sys.path.insert(0, HERE)
sys.path.insert(0, os.path.join(HERE, "tools"))
logging.disable(logging.WARNING)
import main_files # noqa: E402
import opt11p3_replay as rp # noqa: E402
import opt20_scen as sc # noqa: E402
from app import peakguard, tariff # noqa: E402
from app.maintenance import DRAIN, MaintResult # noqa: E402
fails = []
def check(name, cond):
print(f" {'ok ' if cond else 'FAIL'} {name}")
if not cond:
fails.append(name)
CH = sc.MAINT_CHARGE
MONTH_PEAK = 6000.0
AIM = MONTH_PEAK - 50.0
DRAIN_R = MaintResult(DRAIN, True, 2000.0, False, [])
T0 = sc.at(2.0) # a quarter boundary
PRE, LOAD, POST = 300.0, 1200.0, 600.0 # s
def stepped_house(base_w, hi_w):
"""[(t_utc, W)]: base_w, then hi_w from PRE for LOAD s, +-50 W per 5 s."""
rnd = random.Random(28)
out = [(sc.UTC0.timestamp() - 10, base_w)]
for t in range(0, int(PRE + LOAD + POST), 5):
w = hi_w if PRE <= t < PRE + LOAD else base_w
out.append((T0.timestamp() + t, w + rnd.uniform(-50.0, 50.0)))
return out
def scen(*, a=None, soc=(49.0, 30.0), house=None, house_w=3000.0,
peak=MONTH_PEAK, fc="grid", n=2, variant="p3_ch_sell", dur=2700.0):
"""`a`: A's forced maintenance result. `fc`: "grid" (follows the grid),
"quarter" (quarter average so far, the rest at the present grid, like the
live sensor) or None (no forecast entity). Returns (rows, stats, c)."""
rows = []
q = dict(q=None, s=0.0, last=None, start=None)
def patch(c):
if a is not None:
c.maints[0].tick = (
lambda now, soc_, blocked_by=None, gate_open=True: a)
if peak is not None:
orig_peak = c.peak.peak
def peak_(now):
r = orig_peak(now)
return tariff.PeakReading(tariff.OBSERVED,
getattr(r, "month", ""), peak)
c.peak.peak = peak_
orig = c.cycle
susp = []
c._m28_susp = susp
async def cyc():
c.cheap = True
if fc and c.grid is not None:
g = float(c.grid)
if fc == "grid":
c.peak_fc = g
else:
now = main_files.live.datetime.now()
qi = int(now.timestamp() // 900)
if q["q"] != qi:
q.update(q=qi, s=0.0, last=now, start=now)
el = (now - q["start"]).total_seconds()
q["s"] += g * (now - q["last"]).total_seconds()
q["last"] = now
c.peak_fc = (q["s"] + g * (900.0 - el)) / 900.0
await orig()
susp.append(bool(c._maint_shape_suspended))
c.cycle = cyc
def cb(c, h, now, pr):
sh = dict(c.allocation.shares) if c.allocation is not None \
and c.allocation.shares else {}
rows.append(dict(
now=now, grid=h.grid(), shares=sh,
action=getattr(c.arb, "action", None),
reason=getattr(c.arb, "reason", None) or "",
roles=dict(c.mode_tick.roles) if c.mode_tick else {},
why=c.mode_tick.why if c.mode_tick else None,
p={u: p.p for u, p in h.plants.items()},
t=(now - T0).total_seconds(), a=h.plants["a"].p,
susp=c._m28_susp[-1]))
src = house if house is not None else [(sc.UTC0.timestamp() - 10, house_w)]
stats, c = rp.run(variant, src, sc.WPTS, T0, dur, check=cb, lag=sc.LAG,
n=n, soc0={"a": soc[0], "b": soc[1]},
choice=sc.CH_CH, refuse=(), patch=patch,
extra={"cycle_cost_threshold_eur": 0.10})
return rows, stats, c
def flips(rs):
"""Reversals of A between charging and giving (beyond 50 W)."""
n, s = 0, 0
for r in rs:
v = 1 if r["a"] > 50 else -1 if r["a"] < -50 else 0
if v and s and v != s:
n += 1
if v:
s = v
return n
# ============================================================================ #
print("1. a real peak: house 3000 W, 6500 W for 20 min, 3000 W")
rows, st, c = scen(a=CH, house=stepped_house(3000.0, 6500.0), fc="quarter",
dur=PRE + LOAD + POST)
end = PRE + LOAD
trip = next((r["t"] for r in rows if r["t"] >= PRE and r["a"] > 50), None)
load = [r for r in rows if trip is not None and trip <= r["t"] < end]
after = [r for r in rows if r["t"] >= end]
back = next((r["t"] - end for r in after if r["a"] < -50), None)
print(f" first give at {trip}, flips in the load {flips(load)}, charge s in"
f" the load {sum(1 for r in load if r['a'] < -50)}, charge back "
f"{back} s after it, quarters "
f"{[round(a[0] / a[1]) for a in st['quarters'].values()]}")
check("the guard stepped in once the projection went over the aim",
trip is not None)
check("from the first give to the load's end A does not flip",
flips(load) == 0)
check("...and does not charge at all", not any(r["a"] < -50 for r in load))
check("...the pause is on in every one of those cycles",
all(r["susp"] for r in load))
check("every quarter at or under the month aim",
max(a[0] / a[1] for a in st["quarters"].values()) <= AIM + 1.0)
check("after the load A's charge is back within 10 cycles",
back is not None and back <= 10.0)
tail = [r["a"] for r in after if r["t"] >= end + 10.0]
check("...and stays on: at least 150 W (half the resume margin), no give",
tail and sum(tail) / len(tail) <= -150.0 and max(tail) <= 50.0)
# ============================================================================ #
print("\n2. peakguard.shaping_held()")
held = peakguard.shaping_held
U = peakguard.MAINT_RESUME_UNDER_W
eng = peakguard.PeakDecision(engaged=True, floor_w=100.0, ceiling_w=6000.0,
ceiling_from="x", target_w=AIM)
idle = peakguard.PeakDecision(engaged=False, floor_w=None, ceiling_w=6000.0,
ceiling_from="x", target_w=AIM)
check("the old conjunction still pauses: forecast over the aim; guard engaged",
held(False, idle, AIM + 1, AIM, 3000.0)
and held(False, eng, None, AIM, 3000.0))
check("not held and not suspended: not paused", not held(False, idle, AIM - 1,
AIM, 6500.0))
check("held: stays paused while the house is over the aim minus the margin",
held(True, idle, AIM - 1, AIM, 6500.0)
and held(True, idle, AIM - 1, AIM, AIM - U + 1))
check("held: resumes when the house is the margin under the aim",
not held(True, idle, AIM - 1, AIM, AIM - U)
and not held(True, idle, AIM - 1, AIM, 3000.0))
check("held, house unread: the forecast stands in; neither read: resumes "
"(SAFETY-63)",
held(True, idle, AIM - 1, AIM, None)
and not held(True, idle, AIM - U, AIM, None)
and not held(True, idle, None, AIM, None))
check("a guard that is engaged pauses whatever the house reads",
held(True, eng, AIM - 1, AIM, 3000.0))
# ============================================================================ #
print("\n3. unchanged: the live shape, N=1, the drain, modes off")
rl, sl, cl = scen(a=CH)
body = rl[len(rl) // 6:]
mean_a = sum(r["a"] for r in body) / len(body)
print(f" A {mean_a:+.0f} W, paused {sum(cl._m28_susp)} cycles")
check("MAINT-24 live shape: A charges 1475 W and the pause never comes",
-1500.0 <= mean_a <= -1440.0 and not any(cl._m28_susp))
d1 = sc.digest(scen(a=CH, n=1, fc=None, peak=None)[0])
dd = sc.digest(scen(a=DRAIN_R, soc=(60.0, 30.0), peak=None, fc=None)[0])
dm = sc.digest(scen(a=CH, variant="modes_off", peak=None, fc=None)[0])
AT_BASE = {
"n1": "44816d132984ecd64d5a2510223debe102f29decd1d5127ae2b255b45dbf8bd4",
"drain": "8fd86d0816626ee5ae86bc973cb0121b1b5108e56c3b0fdd4b4be6c1f403f748",
"off": "a007f962793611bce15b11f576a76aa52063adcfde82b2a2dc0b0c075b60e60b",
}
got = {"n1": d1, "drain": dd, "off": dm}
for k in AT_BASE:
print(f" {k} {'same' if got[k] == AT_BASE[k] else 'DIFFERS'} "
f"{got[k][:16]}")
check("N=1 with A in maintenance charge and no forecast entity: equal to "
"release/1.0 02eac3b", got["n1"] == AT_BASE["n1"])
check("the SAFETY-78 drain beside a charger: equal to 02eac3b",
got["drain"] == AT_BASE["drain"])
check("battery modes off: equal to 02eac3b", got["off"] == AT_BASE["off"])
print()
if fails:
print(f"{len(fails)} FAILED:")
for f in fails:
print(f" - {f}")
sys.exit(1)
print("all checks passed")