SAFETY-118: a missing peak forecast reading keeps the unit-fault state
A missing reading (unavailable, unknown, failed read, non-numeric) no longer clears the fault: no false 'used again' INFO, no repeated WARNING, the status row stays. Adds pv.has_reading(). DECISIONS wording fixed; tests added. Co-Authored-By: Claude <noreply@anthropic.com>
This commit is contained in:
co-authored by
Claude
parent
f0b4e68e49
commit
7d52dc1c0f
@@ -4,8 +4,8 @@
|
||||
|
||||
`peak_forecast_entity` was read as a bare number, and anything under 50 was
|
||||
multiplied by 1000 ("accept kW or W"). A W sensor reading 17 to 45 W, which a
|
||||
real site did 430 times in one morning, was taken as 17 to 45 kW. The validator
|
||||
also called a kW sensor wrong, which was false for this entity.
|
||||
real site did 430 times in one morning, would be taken as 17 to 45 kW. The
|
||||
validator also called a kW sensor wrong, which was false for this entity.
|
||||
|
||||
Decision: the size rule is gone. The entity is read through `pv.watts()`, the
|
||||
same unit table and reader as the solar entities, so W, kW, MW and the rest
|
||||
|
||||
Reference in New Issue