SAFETY-85 review: grade discharge only, over the plant's settle time
Rule 2 graded each battery against last cycle's command and graded charges too. On plantsim's battery (10 s lag) at the 2 s meter it warned at every drain or charge start and 15 times an hour under the peak guard at N=2; a charge tapering near full warned 11 times in 50 min (SAFETY-42 section 7). Now a discharge is graded against the least it stood at over SHORT_CYCLES / SHORT_SPAN_S. DOCS lists `mode-bound` under Loop reason. test_safety85 part 7: peak guard with a dead battery, lagging plant, taper; part 3: the bound ends with maintenance. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
This commit is contained in:
@@ -25,14 +25,16 @@ counter counted cycles (861), not episodes.
|
||||
the loop. Its number is on the wire, or only a rating (`device`,
|
||||
`supervised`) cut it. No bound held it, and nothing was unmet.
|
||||
(`Controller._loop_alarm_input`.)
|
||||
2. **A battery another owner set alarms when it gives less than it was told.**
|
||||
This covers every battery on a cycle the loop did not decide, and a battery
|
||||
with its own pin otherwise. The test is more than `saturation_w` short in
|
||||
the told direction, for `saturation_cycles` cycles in a row, against what
|
||||
stands on the wire (`clamp.delivery_short`). It covers a real shortfall
|
||||
during maintenance. Before, that shortfall was silent unless the kick
|
||||
happened to reach the rail (house 1000 W, drain 2000 W, battery gives
|
||||
nothing: 0 warnings before, 4 in 10 min now).
|
||||
2. **A battery another owner set to discharge alarms when it gives less than
|
||||
it was told.** This covers every battery on a cycle the loop did not
|
||||
decide, and a battery with its own pin otherwise. The test is more than
|
||||
`saturation_w` short of the least it stood at over `SHORT_CYCLES` cycles
|
||||
and `SHORT_SPAN_S` (the plant's measured settle, SAFETY-13/73), for
|
||||
`saturation_cycles` cycles in a row (`clamp.delivery_short`). It covers a
|
||||
real shortfall during maintenance or under the peak guard. Before, that
|
||||
shortfall was silent unless the kick happened to reach the rail (house
|
||||
1000 W, drain 2000 W, battery gives nothing: 0 warnings before, 4 in 10 min
|
||||
now).
|
||||
3. **At N>=2, while maintenance holds a battery, the loop is bounded** by
|
||||
OPT-11's `loop_bound()` (what the batteries may place). It does not wind,
|
||||
and control comes back one slew step a cycle. Why maintenance only: that is
|
||||
@@ -69,12 +71,21 @@ batteries can give. The `alarmed()` helpers in test_safety84/86 also read
|
||||
SAFETY-81's quarter stamp, because ALLOCATOR rows can push its row out of
|
||||
the 40-row log.
|
||||
|
||||
**Review (PR #163).** The first draft graded each battery against last
|
||||
cycle's command and graded charges too. On plantsim's battery (10 s lag) at
|
||||
the live 2 s meter, every drain or charge start warned once, and an N=2 drain
|
||||
or HOLD under the peak guard with a stepping house warned 15 times an hour. A
|
||||
maintenance charge tapering near full warned 11 times in 50 min, which
|
||||
SAFETY-42 section 7 had ruled out. With the settle window and discharge only:
|
||||
0 in all of those cases. A battery that gives nothing still warns, lagging
|
||||
or not. At a hypothetical 20 s lag, it warns at most twice an hour. The cost:
|
||||
a battery that does not take a charge another owner set is not named by this
|
||||
alarm (the same gap SAFETY-42 states; the charge has its 36 h timeout).
|
||||
`test_safety85.py` part 7.
|
||||
|
||||
**Not changed, open for the owner.**
|
||||
- With the loop in charge and the house above the batteries' total rating,
|
||||
it still warns (SAFETY-40). On the rig's 2 x 2000 W N=2, most of SAFETY-84's
|
||||
count came from houses of 4500 and 6500 W.
|
||||
- A battery that tapers near full during a charge, more than `saturation_w`
|
||||
under its command for 15 s, now warns (rule 2). The text already says
|
||||
"check it is not empty or full".
|
||||
- TEL-10's `loop_reason` reads `mode-bound` while the maintenance bound holds
|
||||
the loop, with modes off.
|
||||
- TEL-10's `Loop reason` reads `mode-bound` while the maintenance bound holds
|
||||
the loop, with modes off. DOCS lists the value with both meanings.
|
||||
|
||||
@@ -577,7 +577,7 @@ accumulator is doing:
|
||||
| `Loop integrator lead` | W | that value minus **the command it was computed against**, i.e. the command the previous cycle left standing |
|
||||
| `Loop reason` | — | the law's own word for this cycle |
|
||||
|
||||
`Loop reason` takes one of ten values:
|
||||
`Loop reason` takes one of eleven values:
|
||||
|
||||
| value | what happened |
|
||||
|---|---|
|
||||
@@ -588,6 +588,7 @@ accumulator is doing:
|
||||
| `slew-limited` | the command could not move as far as the integrator asked for; `slew_w` is what stopped it |
|
||||
| `saturated-freeze` | the inverter is not following, so the command's magnitude may fall but not rise |
|
||||
| `freeze-released` | the freeze had run out of plant-shaped explanations and the command was let move again |
|
||||
| `mode-bound` | the batteries' limits set the command, not the meter: their battery modes, or, with two or more inverters, a battery in its monthly maintenance |
|
||||
| `not-running` | control is stopped **and** shadow mode is off, so the loop did not run |
|
||||
| `battery refuses` | the battery gave less than 100 W for 12 cycles (a minute at a 5-second meter) while asked for more than 500 W, so the add-on asks 0 W in that direction (see below) |
|
||||
| `battery probe` | the add-on asks 200 W to test whether a refusing battery gives power again |
|
||||
@@ -1954,10 +1955,12 @@ notification budget.
|
||||
Why: [`DECISIONS/SAFETY-40-the-integrator-bound-is-not-a-bug.md`](DECISIONS/SAFETY-40-the-integrator-bound-is-not-a-bug.md).
|
||||
|
||||
The integrator bound counts only on a cycle the loop decided. While
|
||||
maintenance, the peak guard or a safety limit sets a battery, the same alarm
|
||||
fires only when that battery gives more than `saturation_w` less than it was
|
||||
told, for `saturation_cycles` cycles. At two or more inverters the loop does not
|
||||
wind while maintenance holds a battery.
|
||||
maintenance, the peak guard or a safety limit sets a battery to discharge, the
|
||||
same alarm fires only when that battery gives more than `saturation_w` less
|
||||
than the least it was told over the plant's settle time (at least 23 s), for
|
||||
`saturation_cycles` cycles. A charge is not graded: a full battery takes less
|
||||
as it tops up. At two or more inverters the loop does not wind while
|
||||
maintenance holds a battery.
|
||||
Why: [`DECISIONS/SAFETY-85-no-false-not-keeping-up.md`](DECISIONS/SAFETY-85-no-false-not-keeping-up.md).
|
||||
|
||||
### The frozen-meter alarm
|
||||
@@ -3130,8 +3133,9 @@ short time, for example just after a large load switches on or the sun comes
|
||||
out. It is not a fault, and control keeps running. If it keeps coming back,
|
||||
check that the battery is switched on, and that it is not empty (when it should
|
||||
give power) or full (when it should charge). During the monthly maintenance or
|
||||
while the peak limit is guarded, it only shows when the battery gives less than
|
||||
it was told. The status page counts how many times it happened.
|
||||
while the peak limit is guarded, it only shows when the battery gives
|
||||
clearly less than it was told. The status page counts how many times it
|
||||
happened.
|
||||
|
||||
### Power request too high
|
||||
|
||||
@@ -3237,8 +3241,8 @@ link cannot jump to the section.
|
||||
|
||||
**Battery is not keeping up.** The grid-following loop's integrator reached its
|
||||
anti-windup bound (`integrator_max_w`, SAFETY-40), or a battery that another
|
||||
owner set gave less than it was told (SAFETY-85). No command went over the
|
||||
rating. The log line is a WARNING with reason code `OUTPUT_CLAMP`. See *The
|
||||
owner set to discharge gave less than it was told (SAFETY-85). No command went
|
||||
over the rating. The log line is a WARNING with reason code `OUTPUT_CLAMP`. See *The
|
||||
winding-loop alarm*.
|
||||
|
||||
**Power request too high.** A computed command above a limit was cut before it
|
||||
|
||||
@@ -270,12 +270,10 @@ def shortfall_note(named) -> str:
|
||||
|
||||
|
||||
def delivery_short(asked_w, given_w, margin_w) -> bool:
|
||||
"""SAFETY-85: did a battery give more than `margin_w` less than asked, in
|
||||
the asked direction? Giving more than asked, or 0 W asked, is not short."""
|
||||
"""SAFETY-85: did a battery asked to discharge give more than `margin_w`
|
||||
less? A charge is never short: a full pack tapers (SAFETY-42 section 7)."""
|
||||
asked, given = float(asked_w), float(given_w)
|
||||
if asked == 0.0:
|
||||
return False
|
||||
return (asked - given) * (1.0 if asked > 0 else -1.0) > abs(float(margin_w))
|
||||
return asked > 0.0 and asked - given > abs(float(margin_w))
|
||||
|
||||
|
||||
def write_clamp_note(named) -> str:
|
||||
|
||||
@@ -281,6 +281,11 @@ def pack_energy_of(inv):
|
||||
# ordinary load steps. At 2 s and slower this changes nothing.
|
||||
REFUSED_SPAN_S = (_ctl.SETTLE_CYCLES - 1) * _ctl.LOOP_TICK_S
|
||||
|
||||
# SAFETY-85 review: a battery another owner set is graded against the least it
|
||||
# was told over the same span as above (the plant's measured settle time), so
|
||||
# a healthy battery still settling on a new command is not short.
|
||||
SHORT_CYCLES, SHORT_SPAN_S = _ctl.SETTLE_CYCLES, REFUSED_SPAN_S
|
||||
|
||||
|
||||
def _refused_interval(sign: int) -> tuple:
|
||||
"""SAFETY-73: the (lo, hi) a refusing unit may be asked: 0 W that way."""
|
||||
@@ -1180,9 +1185,11 @@ class Controller:
|
||||
self.loop_clamped: tuple[bool, str, bool] = (False, "", False)
|
||||
# UX-08: the numbers of a loop-side over-rating, for the notification.
|
||||
self.loop_clamp_facts: tuple = ()
|
||||
# SAFETY-85: this cycle's loop Decision, and how many cycles in a row
|
||||
# a battery set by another owner gave less than asked.
|
||||
# SAFETY-85: this cycle's loop Decision, each battery's recent
|
||||
# standing commands, and how many cycles in a row a battery set by
|
||||
# another owner gave less than asked.
|
||||
self._loop_decision = None
|
||||
self._asked_hist: dict = {}
|
||||
self._short_run = 0
|
||||
self.stopping = False
|
||||
# SAFETY-61. time.monotonic() at the end of the last run_control() pass.
|
||||
@@ -5084,25 +5091,36 @@ class Controller:
|
||||
|
||||
def _loop_alarm_input(self, resolution) -> None:
|
||||
"""SAFETY-85. The loop's clamp counts only on a cycle the loop decided
|
||||
(a rating may cut it). A battery another owner set counts when it gave
|
||||
less than it was told for `saturation_cycles` cycles in a row.
|
||||
DECISIONS/SAFETY-85-no-false-not-keeping-up.md."""
|
||||
(a rating may cut it). A battery another owner set to discharge counts
|
||||
when it gave less than it was told for `saturation_cycles` cycles in a
|
||||
row. DECISIONS/SAFETY-85-no-false-not-keeping-up.md."""
|
||||
d = self._loop_decision
|
||||
if d is None:
|
||||
self._short_run = 0
|
||||
self._asked_hist = {}
|
||||
return
|
||||
unmet = self.allocation.unmet_w if self.allocation is not None else 0
|
||||
cut = (resolution.bound_by or "").split("(")[0]
|
||||
owns = (resolution.winner == "loop" and not d.held and not unmet
|
||||
and (resolution.target_w == d.target_w
|
||||
or cut in ("device", "supervised")))
|
||||
# Graded against what stands on the wire (0 W in shadow mode).
|
||||
# Graded against the least that stood on the wire (0 W in shadow
|
||||
# mode) over SHORT_CYCLES cycles and SHORT_SPAN_S seconds.
|
||||
now, asked = self._now_mono, {}
|
||||
for inv in self.inverters:
|
||||
h = self._asked_hist.setdefault(inv.name, [])
|
||||
h.append((now, inv.standing_w()))
|
||||
while len(h) > SHORT_CYCLES and (
|
||||
now is None or h[0][0] is None
|
||||
or now - h[0][0] > SHORT_SPAN_S):
|
||||
h.pop(0)
|
||||
asked[inv.name] = min(w for _t, w in h)
|
||||
others = [inv for inv in self.inverters if not owns
|
||||
or allocator.pin_w(resolution.unit_bounds.get(inv.name))
|
||||
is not None]
|
||||
short = [(inv, inv.standing_w(), inv.batt) for inv in others
|
||||
short = [(inv, asked[inv.name], inv.batt) for inv in others
|
||||
if inv.batt is not None
|
||||
and delivery_short(inv.standing_w(), inv.batt,
|
||||
and delivery_short(asked[inv.name], inv.batt,
|
||||
self.tuning.saturation_w)]
|
||||
self._short_run = self._short_run + 1 if short else 0
|
||||
if owns and self.loop_clamped[0]:
|
||||
|
||||
@@ -19,6 +19,8 @@ while maintenance holds a battery. Drives the REAL Controller
|
||||
(a battery at its cut-out) does not warn.
|
||||
5. The status row counts episodes, not cycles.
|
||||
6. The rules at their boundaries.
|
||||
7. Review: a battery the peak guard sets that gives nothing warns; a battery
|
||||
that lags (10 s) and a charge that tapers do not.
|
||||
|
||||
Mutations (MUTATION.md, purged copies) are listed in the pull request.
|
||||
"""
|
||||
@@ -82,13 +84,15 @@ def store(n, phase):
|
||||
|
||||
def run(n, phase, house, cap, *, dur=HOUR, soc=None, cut=None, extra=None,
|
||||
maint=True):
|
||||
"""Rows and controller; `cap` is the peak limit (20000: never binds)."""
|
||||
"""Rows and controller; `cap` is the peak limit (20000: never binds);
|
||||
`house` is watts or a function of time."""
|
||||
s84.OPT = dict(OPT0, peak_cap_w=cap, maintenance_enabled=maint)
|
||||
if soc is None:
|
||||
def soc(u, t):
|
||||
return 99.0 if phase == "hold" and u == "a" else 60.0
|
||||
try:
|
||||
return s84.run(n, load=lambda t: house, cheap=(phase == "charge"),
|
||||
load = house if callable(house) else (lambda t: house)
|
||||
return s84.run(n, load=load, cheap=(phase == "charge"),
|
||||
store=store(n, phase), soc=soc, dur=dur, cut=cut,
|
||||
extra=dict({"maintenance_hold_min": 600,
|
||||
"maintenance_discharge_w": 2000},
|
||||
@@ -209,7 +213,20 @@ check("a dip of two cycles is not an alarm", warned(_dip[1]) == (0, 0, 0))
|
||||
# ============================================================================ #
|
||||
print("\n3. control coming back from maintenance does not jump")
|
||||
END = {"maintenance_hold_min": 10}
|
||||
_h2 = run(2, "hold", 4500.0, 20000, dur=900.0, extra=END)
|
||||
_bounds = []
|
||||
_real_compute = app_main.compute
|
||||
|
||||
|
||||
def _spy_compute(*a, **kw):
|
||||
_bounds.append(kw.get("bound"))
|
||||
return _real_compute(*a, **kw)
|
||||
|
||||
|
||||
app_main.compute = _spy_compute
|
||||
try:
|
||||
_h2 = run(2, "hold", 4500.0, 20000, dur=900.0, extra=END)
|
||||
finally:
|
||||
app_main.compute = _real_compute
|
||||
_h2_old = no_bound(lambda: run(2, "hold", 4500.0, 20000, dur=900.0,
|
||||
extra=END))
|
||||
_h1 = run(1, "hold", 4500.0, 20000, dur=900.0, extra=END)
|
||||
@@ -224,6 +241,14 @@ print(f" N=2 hold end: largest step {steps(_h2[0], 560, 700):.0f} W "
|
||||
check("⭐ N=2, the HOLD ends under a 4500 W house: the batteries move at most "
|
||||
"one slew step a cycle",
|
||||
_h2[1].maints[0].phase != "hold" and steps(_h2[0], 560, 700) <= SLEW)
|
||||
_held = [any(p != "idle" for p in r[-1][3]) for r in _h2[0]]
|
||||
print(f" bound per cycle: {len(_bounds)} calls, {len(_held)} rows, "
|
||||
f"{sum(_held)} in maintenance, "
|
||||
f"{sum(b is not None for b in _bounds)} bounded")
|
||||
check("...and the bound is on while A holds and off from the cycle the HOLD "
|
||||
"ends (review)",
|
||||
len(_bounds) == len(_held) and any(not h for h in _held)
|
||||
and all((b is not None) == h for b, h in zip(_bounds, _held)))
|
||||
check("⭐ N=2, A's charge pin lifts at a quarter's start: at most one slew "
|
||||
"step a cycle", steps(_cd[0], 1780, 1840) <= SLEW)
|
||||
check("...and N=1 already moved one slew step at a time (re-seeded each "
|
||||
@@ -283,12 +308,11 @@ check("⭐ the page row reads the episodes, not the cycles "
|
||||
# ============================================================================ #
|
||||
print("\n6. the rules at their boundaries")
|
||||
DS = [((2000, 1499, 500), True), ((2000, 1500, 500), False),
|
||||
((2000, 2600, 500), False), ((-2000, -1499, 500), True),
|
||||
((-2000, -2600, 500), False), ((0, -900, 500), False),
|
||||
((0, 900, 500), False),
|
||||
((2000, -4, 500), True), ((-2000, 600, 500), True)]
|
||||
check("delivery_short: more than the margin short in the asked direction; "
|
||||
"more than asked, or 0 W asked, is never short",
|
||||
((2000, 2600, 500), False), ((2000, -4, 500), True),
|
||||
((0, -900, 500), False), ((0, 900, 500), False),
|
||||
((-2000, -1499, 500), False), ((-2000, 600, 500), False)]
|
||||
check("delivery_short: a discharge more than the margin short; more than "
|
||||
"asked, 0 W asked, or a charge (a full pack tapers) is never short",
|
||||
all(clamp.delivery_short(*a) is want for a, want in DS))
|
||||
check("the note names each battery, asked before given",
|
||||
clamp.shortfall_note([("inverter-a", 2000.0, -4.0)])
|
||||
@@ -296,6 +320,129 @@ check("the note names each battery, asked before given",
|
||||
and clamp.shortfall_note([(None, -2000.0, 0.0)])
|
||||
== "OUTPUT_CLAMP: the battery gives +0 W of the -2000 W asked")
|
||||
|
||||
# ============================================================================ #
|
||||
print("\n7. review: the peak guard, a battery that lags, a charge that tapers")
|
||||
import math # noqa: E402
|
||||
|
||||
|
||||
def under_guard(n, cut):
|
||||
"""A HOLD the peak guard raises (house 6500, limit 3500), 20 min."""
|
||||
return run(n, "hold", 6500.0, 3500, dur=1200.0, cut=cut)
|
||||
|
||||
|
||||
_g1 = under_guard(1, lambda u, t: t >= 600)
|
||||
_g2 = under_guard(2, lambda u, t: u == "a" and t >= 600)
|
||||
print(f" under the guard, the battery gives nothing: N=1 {warned(_g1[1])}, "
|
||||
f"N=2 {warned(_g2[1])}")
|
||||
check("⭐ the peak guard sets the battery and it gives nothing: it warns at "
|
||||
"N=1, and at N=2 (A, raised for the peak, gives nothing; B gives all "
|
||||
"it is told)",
|
||||
warned(_g1[1])[0] >= 1 and warned(_g2[1])[0] >= 1
|
||||
and all("peak" in r[6] for rows, _c in (_g1, _g2) for r in rows
|
||||
if 600 <= r[0] <= 620))
|
||||
check("...and it gives what it is told until then (no warning before 600 s)",
|
||||
all(e.split(" ", 1)[0] >= "11:10:00" for c in (_g1[1], _g2[1])
|
||||
for e in c.events if "OUTPUT_CLAMP" in e))
|
||||
|
||||
|
||||
def lagging(fn, lag=10.0):
|
||||
"""Run `fn` on plantsim's battery (800 W/s ramp, `lag` s first-order lag)
|
||||
at the live 2 s meter tick."""
|
||||
real_p, real_t = rig._Hass.power, rig.TICK
|
||||
|
||||
def power(self, u):
|
||||
st = self.__dict__.setdefault("_plant", {})
|
||||
a, tgt, tl = st.get(u, (0.0, 0.0, self.t))
|
||||
for _ in range(int(round((self.t - tl) / 0.1))):
|
||||
d = self.cmd[u] - tgt
|
||||
tgt += math.copysign(min(abs(d), 80.0), d)
|
||||
a += (tgt - a) * (1 - math.exp(-0.1 / lag))
|
||||
st[u] = (a, tgt, self.t)
|
||||
if self.cut(u, self.t) and self.cmd[u] >= -4.0:
|
||||
return -4.0
|
||||
return float(round(a))
|
||||
rig._Hass.power, rig.TICK = power, 2.0
|
||||
try:
|
||||
return fn()
|
||||
finally:
|
||||
rig._Hass.power, rig.TICK = real_p, real_t
|
||||
|
||||
|
||||
def kettle(t):
|
||||
"""800 W, plus 2 kW 3 min in 10, plus 3 kW 1 min in 4."""
|
||||
return (800.0 + (2000.0 if t % 600 < 180 else 0.0)
|
||||
+ (3000.0 if t % 240 < 60 else 0.0))
|
||||
|
||||
|
||||
def lag_runs():
|
||||
return [run(n, ph, kettle, 3500, dur=1800.0)
|
||||
for n, ph in ((1, "drain"), (2, "drain"), (2, "hold"))]
|
||||
|
||||
|
||||
_lag = lagging(lag_runs)
|
||||
_lag_old = patched(app_main, "SHORT_CYCLES", 1)(
|
||||
lambda: patched(app_main, "SHORT_SPAN_S", 0.0)(
|
||||
lambda: lagging(lag_runs)))
|
||||
_lag_dead = lagging(lambda: run(1, "drain", 1000.0, 20000, dur=900.0,
|
||||
cut=gone(600, 900)))
|
||||
print(f" lagging battery, house steps under the guard: "
|
||||
f"{[warned(c) for _r, c in _lag]}, graded on last cycle's command "
|
||||
f"{[warned(c) for _r, c in _lag_old]}; gives nothing "
|
||||
f"{warned(_lag_dead[1])}")
|
||||
check("⭐ a battery that lags (10 s) behind maintenance and peak-guard steps "
|
||||
"at a 2 s meter does not warn (N=1 drain, N=2 drain and HOLD, 30 min)",
|
||||
all(warned(c) == (0, 0, 0) for _r, c in _lag))
|
||||
check("non-vacuous: graded on last cycle's command alone, it warns",
|
||||
sum(warned(c)[0] for _r, c in _lag_old) >= 3)
|
||||
check("...and a lagging battery that gives nothing still warns",
|
||||
warned(_lag_dead[1])[0] >= 1)
|
||||
|
||||
|
||||
def taper(fn):
|
||||
"""Battery A takes the full charge until 600 s, then its acceptance falls
|
||||
to 150 W over 30 min (constant-voltage taper)."""
|
||||
real_p = rig._Hass.power
|
||||
|
||||
def power(self, u):
|
||||
c = self.cmd[u]
|
||||
if c < 0 and u == "a":
|
||||
c = max(c, -max(150.0, 2500.0 - max(0.0, self.t - 600) / 1800
|
||||
* 2350.0))
|
||||
return float(round(c))
|
||||
rig._Hass.power = power
|
||||
try:
|
||||
return fn()
|
||||
finally:
|
||||
rig._Hass.power = real_p
|
||||
|
||||
|
||||
def charge_runs():
|
||||
s84.OPT = dict(OPT0, peak_cap_w=20000)
|
||||
try:
|
||||
return [s84.run(n, load=lambda t: 800.0, cheap=True,
|
||||
store=s79.store_charging(n), soc=lambda u, t: 60.0,
|
||||
dur=2400.0) for n in (1, 2)]
|
||||
finally:
|
||||
s84.OPT = OPT0
|
||||
|
||||
|
||||
def both_ways(asked, given, margin):
|
||||
asked, given = float(asked), float(given)
|
||||
return asked != 0.0 and (asked - given) * math.copysign(1.0, asked) > margin
|
||||
|
||||
|
||||
_tp = taper(charge_runs)
|
||||
_tp_old = patched(app_main, "delivery_short", both_ways)(
|
||||
lambda: taper(charge_runs))
|
||||
print(f" a charge that tapers: {[warned(c) for _r, c in _tp]}, grading "
|
||||
f"charges too {[warned(c) for _r, c in _tp_old]}")
|
||||
check("⭐ a maintenance charge that tapers near full does not warn (N=1, N=2)",
|
||||
all(warned(c) == (0, 0, 0) for _r, c in _tp)
|
||||
and all("charge" in {p for r in rows for p in r[-1][3]}
|
||||
for rows, _c in _tp))
|
||||
check("non-vacuous: grading charges too, the taper warns",
|
||||
all(warned(c)[0] >= 3 for _r, c in _tp_old))
|
||||
|
||||
print()
|
||||
if fails:
|
||||
print(f"{len(fails)} FAILED: " + ", ".join(fails))
|
||||
|
||||