SAFETY-85 review: grade discharge only, over the plant's settle time
Rule 2 graded each battery against last cycle's command and graded charges too. On plantsim's battery (10 s lag) at the 2 s meter it warned at every drain or charge start and 15 times an hour under the peak guard at N=2; a charge tapering near full warned 11 times in 50 min (SAFETY-42 section 7). Now a discharge is graded against the least it stood at over SHORT_CYCLES / SHORT_SPAN_S. DOCS lists `mode-bound` under Loop reason. test_safety85 part 7: peak guard with a dead battery, lagging plant, taper; part 3: the bound ends with maintenance. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
This commit is contained in:
@@ -577,7 +577,7 @@ accumulator is doing:
|
||||
| `Loop integrator lead` | W | that value minus **the command it was computed against**, i.e. the command the previous cycle left standing |
|
||||
| `Loop reason` | — | the law's own word for this cycle |
|
||||
|
||||
`Loop reason` takes one of ten values:
|
||||
`Loop reason` takes one of eleven values:
|
||||
|
||||
| value | what happened |
|
||||
|---|---|
|
||||
@@ -588,6 +588,7 @@ accumulator is doing:
|
||||
| `slew-limited` | the command could not move as far as the integrator asked for; `slew_w` is what stopped it |
|
||||
| `saturated-freeze` | the inverter is not following, so the command's magnitude may fall but not rise |
|
||||
| `freeze-released` | the freeze had run out of plant-shaped explanations and the command was let move again |
|
||||
| `mode-bound` | the batteries' limits set the command, not the meter: their battery modes, or, with two or more inverters, a battery in its monthly maintenance |
|
||||
| `not-running` | control is stopped **and** shadow mode is off, so the loop did not run |
|
||||
| `battery refuses` | the battery gave less than 100 W for 12 cycles (a minute at a 5-second meter) while asked for more than 500 W, so the add-on asks 0 W in that direction (see below) |
|
||||
| `battery probe` | the add-on asks 200 W to test whether a refusing battery gives power again |
|
||||
@@ -1954,10 +1955,12 @@ notification budget.
|
||||
Why: [`DECISIONS/SAFETY-40-the-integrator-bound-is-not-a-bug.md`](DECISIONS/SAFETY-40-the-integrator-bound-is-not-a-bug.md).
|
||||
|
||||
The integrator bound counts only on a cycle the loop decided. While
|
||||
maintenance, the peak guard or a safety limit sets a battery, the same alarm
|
||||
fires only when that battery gives more than `saturation_w` less than it was
|
||||
told, for `saturation_cycles` cycles. At two or more inverters the loop does not
|
||||
wind while maintenance holds a battery.
|
||||
maintenance, the peak guard or a safety limit sets a battery to discharge, the
|
||||
same alarm fires only when that battery gives more than `saturation_w` less
|
||||
than the least it was told over the plant's settle time (at least 23 s), for
|
||||
`saturation_cycles` cycles. A charge is not graded: a full battery takes less
|
||||
as it tops up. At two or more inverters the loop does not wind while
|
||||
maintenance holds a battery.
|
||||
Why: [`DECISIONS/SAFETY-85-no-false-not-keeping-up.md`](DECISIONS/SAFETY-85-no-false-not-keeping-up.md).
|
||||
|
||||
### The frozen-meter alarm
|
||||
@@ -3130,8 +3133,9 @@ short time, for example just after a large load switches on or the sun comes
|
||||
out. It is not a fault, and control keeps running. If it keeps coming back,
|
||||
check that the battery is switched on, and that it is not empty (when it should
|
||||
give power) or full (when it should charge). During the monthly maintenance or
|
||||
while the peak limit is guarded, it only shows when the battery gives less than
|
||||
it was told. The status page counts how many times it happened.
|
||||
while the peak limit is guarded, it only shows when the battery gives
|
||||
clearly less than it was told. The status page counts how many times it
|
||||
happened.
|
||||
|
||||
### Power request too high
|
||||
|
||||
@@ -3237,8 +3241,8 @@ link cannot jump to the section.
|
||||
|
||||
**Battery is not keeping up.** The grid-following loop's integrator reached its
|
||||
anti-windup bound (`integrator_max_w`, SAFETY-40), or a battery that another
|
||||
owner set gave less than it was told (SAFETY-85). No command went over the
|
||||
rating. The log line is a WARNING with reason code `OUTPUT_CLAMP`. See *The
|
||||
owner set to discharge gave less than it was told (SAFETY-85). No command went
|
||||
over the rating. The log line is a WARNING with reason code `OUTPUT_CLAMP`. See *The
|
||||
winding-loop alarm*.
|
||||
|
||||
**Power request too high.** A computed command above a limit was cut before it
|
||||
|
||||