SAFETY-42: a unit that stops delivering, and the discriminator the card asked for does not exist
A unit standing at a non-zero share and producing nothing is seen by NOTHING. SAFETY-30's per-unit sign gate needs OPPOSITION on both sides of 250 W and a unit at 0 W is not opposing, it is ABSENT. The site sum still agrees with the meter in direction. Circulating power is exactly zero when one unit does nothing. The only trace left is `reason == "saturated-freeze"`, which clamp.py:93-96 documents as the alarm an operator learns to ignore. It is HW-01's shape, which ran 6 h 25 m with all three layers spectators. ⚠️ THE CARD'S OWN DISCRIMINATOR WAS BUILT FIRST AND FALSIFIED, AND THAT IS THE MAIN CONTENT. SAFETY-42 asks for "saturation persisting past N while |grid error| > X, both derived". Run on the two-master rig it fails in BOTH directions, and no (N, X) fixes either: FALSE POSITIVE `plantsim.Plant.limit()` returns 0 W for a discharge command into a pack at its own floor, and a wedged unit produces 0 W too. Load 2000 W, equal weights, 2000 W per-unit cap, 120 cycles: THE TWO ARMS ARE IDENTICAL ON ALL 120 in grid, site target, every share and every measured watt. Both saturated-freeze on 116 of them, both hold |grid error| over 300 W on all 120 and settle at 1200 W, both read circulating 0.0 W. The predicate's inputs do not differ, so no threshold on them can differ. And "a cold pack at its floor must not alarm" is the card's own AC 2. FALSE NEGATIVE the standing grid error is what a HEALTHY SIBLING ERASES. Load 800 W, same config, B wedged: over the last 30 of 200 cycles the loop is frozen on 30 of 30 while the worst |grid error| is 30 W, with B standing at +770 W and delivering 0 W. Any X above 30 W is silent for the whole run on the exact fault the card describes. WHAT REPLACES IT. Per unit, for a discharge share, `share - measured`; readable because of a reduction that only exists at N>=2: a unit is named while it is short by more than `saturation_w` with NO ACCOUNT for it, and the units in that state are a PROPER SUBSET of the units asked to discharge. THE ACCOUNT keeps the cold pack out and is the only thing that can: the two cases are identical in the power domain, so the discriminator has to be a non-power fact, and there is exactly one - the pack's own SoC against its own `bms_soc_floor`, asked through `peakguard.discharge_permitted()` rather than transcribed. ⚠️ `bms_soc_floor` ALONE, not `pack_floor_pct()`'s conjunction with `peak_soc_floor`: that floor bounds a money-saving discharge only and using it would explain away a wedged unit anywhere between the two. THE PROPER SUBSET keeps a whole-site cause out - a derate this add-on cannot see hits every unit; one box that stopped listening does not - and it is what makes this INERT AT N=1, by algebra rather than by a roster guard. IT REPORTS. IT DOES NOT ACT, and the strongest argument is for acting. Dropping the wedged unit from `live` genuinely recovers a site the shipped path does not: at load 1500 W, kept in the split the site settles at 800 W with a 700 W error and NEVER comes inside 100 W in 150 cycles (the freeze pins the target, so the sibling's SHARE never grows); dropped, it delivers 1500 W from cycle 14. What refuses it is that the only re-allocation this add-on can express is all-or-nothing: a unit derated to 50 % is short by more than saturation_w with nothing to explain it, so this detector names it too, and at load 3000 W dropping it leaves the site delivering 2000 W against 2400 W kept - 400 W WORSE. A partial re-allocation is what would make acting safe and the allocator cannot express it. That is a card. control.py is NOT MODIFIED. The freeze shapes the loop; this reports on it. NUMBERS, MEASURED. The watts side is `Tuning.saturation_w`, read at runtime, so there is no fourth CFG-03 copy and it cannot drift from the number the control law itself calls "not following". `delivery_hold_s: 185` comes off 2640 closed-loop two-inverter runs in which nothing is faulty (6 gains x 5 slews over the whole schema range, across load reversals, a flapping load and ASYMMETRIC SPLITS - a family SAFETY-30's campaign did not have and the one that dominates here) plus 1890 runs at a roster of ONE as the control: threshold reversals flapping weighted N=1 control * 500 W 20.0 s 0.0 s 30.0 s 0.0 s The N=1 column is 0.0 s at EVERY threshold in all 1890 runs, and the flapping column - the family that defeated SAFETY-30's site window - is zero too, because a common stimulus makes both units short at once and the subset stops being proper. ⚠️ The curve is NOT monotone (55.0 s at 250 W against 40.0 s at 100 W): lowering the threshold can turn a proper subset into the whole roster and BREAK the run. ⚠️ THE MARGIN IS MEASURED, NOT FELT, BECAUSE INVERTER B DOES NOT PHYSICALLY EXIST. `plantsim.INVERTER_B` is A COPIED, `measured=False`, so every two-inverter figure above is two copies of A. Sweeping a different second unit: the worst legitimate episode is insensitive to B's RAMP (30.0 s at half A's) and scales with its LAG - 45.0 s at twice A's measured 10 s, 90.0 s at four times it. 185 s is 6.2x the measured worst, 2.06x the four-times-slower case, 6.2x LINK_STALE_S and 4.9x inside the 900 s quarter. Deliberately not 180, which is SAFETY-02's site hold. SAFETY-34. `unit/<name>/delivery_tripped` in the store, one notification id per unit, re-raised on the first cycle of every process, cleared by the Start press. No flat mirror: a rollback lands on a version that drives one actuator, where this check is inert. ⚠️ SCHEMA CHANGE - `delivery_hold_s` joins options: and schema:, so this needs a version bump before it ships. Additive and defaulted, so an existing options blob stays valid. STATED GAPS: charge shares are not graded (no configured charge ceiling exists, so a constant-voltage taper cannot be explained and arming it would fire on every maintenance charge); every unit wedged at once is not caught (the subset is not proper and no instrument here separates that from a plant that cannot). Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
This commit is contained in:
co-authored by
Claude Opus 5
parent
0581648c73
commit
706e625d99
@@ -485,6 +485,7 @@ behind it would trip the firmware watchdog on a system that is working fine.
|
||||
| `unit_sign_disagree_s` | 85 | **Two or more inverters only.** How long one unit's command and its own power must stay opposed before that unit is parked |
|
||||
| `site_sign_disagree_w` | 300 | **Two or more inverters only.** Threshold for the site-wide check - the sum of the commands against the meter. The same 300 W as `sign_disagree_w`, for the same reason: near zero the sign is noise |
|
||||
| `site_sign_disagree_s` | 325 | **Two or more inverters only.** How long the site's total command and the meter must stay opposed before every inverter is parked. Longer than `sign_disagree_s` because the command has to cross zero over a rail that is the sum of the roster, at a `slew_w` that is not - measured at 110 s with one inverter and 215 s with two |
|
||||
| `delivery_hold_s` | 185 | **Two or more inverters only.** How long one inverter may stand at a discharge share it is not producing - short by more than `saturation_w`, with no reason this add-on can read - while at least one sibling is **not** in that state, before it is named. **It reports; it does not act.** Nothing is commanded differently and the site goes on running short by that unit's share |
|
||||
|
||||
#### The sign-disagreement failsafe
|
||||
|
||||
@@ -584,6 +585,70 @@ agreement is 93.4 %; on the four captured fault clusters it is 0.3 %, 0.9 %,
|
||||
10.5 % and 0.0 %. There is no reason to move either value without a capture that
|
||||
says so.
|
||||
|
||||
|
||||
#### ⚠️ A unit that stops DELIVERING is a third fault again (SAFETY-42)
|
||||
|
||||
The two checks above both key on **direction**. A unit sitting at **0 W against
|
||||
a non-zero share** has no direction: it is not pushing the wrong way, it is
|
||||
**absent**. So the per-unit sign gate never opens (it needs opposition on both
|
||||
sides of `unit_sign_disagree_w`), the site sum still agrees with the meter in
|
||||
direction, and circulating power is exactly **zero** — that quantity needs two
|
||||
units pulling *against* each other, and one of these is pulling nowhere.
|
||||
|
||||
The only thing that does fire is the **saturation freeze**, and this add-on's own
|
||||
code calls that an alarm operators learn to ignore, because a loop can be legally
|
||||
saturated all day: a cold pack, a curtailed inverter, an export limit.
|
||||
|
||||
So `delivery_hold_s` grades a different quantity — **how many watts of a
|
||||
discharge share did not arrive** — and makes it readable with a reduction that
|
||||
only exists once there is more than one inverter:
|
||||
|
||||
> a unit is named while it is short of its share by more than `saturation_w`,
|
||||
> **with nothing this add-on can read to explain it**, and the units in that
|
||||
> state are **fewer than the units that were asked to discharge**.
|
||||
|
||||
Both halves matter, and the second is why this cannot fire on a
|
||||
one-inverter install at all:
|
||||
|
||||
- **"nothing explains it"** is what keeps a legitimately empty pack out. A pack
|
||||
at or below its own `bms_soc_floor` cannot discharge, and that is the *only*
|
||||
fact this add-on holds that distinguishes an empty pack from a wedged one —
|
||||
the two are otherwise identical at the unit and at the meter, watt for watt.
|
||||
A unit the add-on has already dropped from the split, or parked by a sign
|
||||
trip, is likewise accounted for.
|
||||
- **"fewer than were asked"** is what keeps a whole-site cause out. A derate this
|
||||
add-on cannot see — thermal, grid-code, DC-side — hits every unit. One box that
|
||||
has stopped listening does not. If *every* unit that was asked is short and
|
||||
unexplained, nothing is reported: there is no instrument here that tells that
|
||||
from a plant which simply cannot deliver.
|
||||
|
||||
**It reports. It does not act.** Commanding an inverter that has stopped
|
||||
listening achieves nothing — that happened on this hardware once for 6 h 25 m —
|
||||
and the only re-allocation this add-on can express is all-or-nothing, which
|
||||
would throw away the output of a unit delivering *part* of its share. So the
|
||||
loop is untouched, the sibling keeps regulating, and the site keeps running
|
||||
**short by that unit's share** until somebody looks. The status page shows it as
|
||||
a caution rather than a failure for exactly that reason: the controller has not
|
||||
stopped.
|
||||
|
||||
The report **survives a Home Assistant restart** (`unit/<name>/delivery_tripped`
|
||||
in the add-on's own state file) and the notification is re-raised on the next
|
||||
start, because a `persistent_notification` is in memory and that is precisely how
|
||||
the 2026-09-02 outage went unseen. It is cleared by pressing **Start**, like the
|
||||
other latches.
|
||||
|
||||
The banner reads **`NOT DELIVERING — <unit> …`** as a *warning*, not a failure,
|
||||
and it **displaces** `Running — holding grid at zero`. That last sentence is a
|
||||
claim the site cannot make while a unit is absent, and a page that goes on
|
||||
reading healthy while the fault runs is the whole shape this check exists to
|
||||
remove.
|
||||
|
||||
**Charge shares are not graded**, and that is a stated gap rather than an
|
||||
oversight: there is no configured charge ceiling anywhere in this add-on, so a
|
||||
pack in constant-voltage taper — which legitimately takes hundreds of watts less
|
||||
than it is told, for tens of minutes — could not be explained, and arming that
|
||||
direction would fire on the taper of every maintenance charge.
|
||||
|
||||
#### Saturation is counted in cycles, not seconds
|
||||
|
||||
The specification states the saturation window as **"> 10 s"**. This add-on counts
|
||||
|
||||