CI-02 probe F: the ORIGINAL gate, unchanged, on the same unmergeable PR
checks / unit (pull_request) Successful in 3m38s
checks / unit (pull_request) Successful in 3m38s
This commit is contained in:
@@ -640,7 +640,18 @@ The add-on alarms when **both** of these are true at once:
|
||||
|
||||
- the meter's own document (power figure *and* both kWh registers) has not
|
||||
changed for `meter_freeze_s` — 300 s by default; **and**
|
||||
- the command standing on the wire is at the rail, within 5 % of `max_w`.
|
||||
- the command standing on the wire is at the rail, within 5 % of the ceiling
|
||||
the command can actually reach.
|
||||
|
||||
**That ceiling is `min(max_w, the setpoint device's own rating)`, not `max_w`.**
|
||||
The emitted command is clipped to the device's reported range as well as to
|
||||
`max_w`, so on a 4700 W inverter configured with `max_w: 5000` a rail measured
|
||||
at 4750 W is one the command can never stand at — the guard could not fire, and
|
||||
the status page said `armed` anyway. It now measures the rail against the
|
||||
smaller number and the page names it, saying *"below max_w because …"* when the
|
||||
device is what capped it. (On an install that started, the two are equal: a
|
||||
`max_w` above the device rating is refused at startup. This matters when the
|
||||
rating could not be read at boot — see below.)
|
||||
|
||||
Neither half is usable alone. A bare "unchanged for N seconds" rule false-trips
|
||||
at the exact operating point this controller aims for — at a converged −10 W a
|
||||
@@ -666,6 +677,13 @@ that reads the meter's own document; on `ha_dsmr`, `mqtt_p1`, `ha_signed` and
|
||||
`off` there is no signal to threshold and the status page says **NOT COVERED**
|
||||
rather than pretending the guard is armed.
|
||||
|
||||
The same row appears for a second reason: a setpoint device that reports a range
|
||||
from which no command magnitude is available in both directions leaves no rail
|
||||
to measure at all, and a 0 W rail would be satisfied by *every* command. That is
|
||||
reported as **NOT COVERED** too, and the detector stays silent rather than
|
||||
degenerating into the bare "unchanged for N seconds" rule this design exists to
|
||||
avoid.
|
||||
|
||||
| option | default | meaning |
|
||||
|---|---|---|
|
||||
| `meter_freeze_s` | 300 | Seconds of an unchanged measurement, *while the command is at the rail*, before the alarm |
|
||||
|
||||
Reference in New Issue
Block a user