@@ -640,7 +640,18 @@ The add-on alarms when **both** of these are true at once:
- the meter's own document (power figure *and* both kWh registers) has not
changed for `meter_freeze_s` — 300 s by default; **and**
- the command standing on the wire is at the rail, within 5 % of `max_w`.
- the command standing on the wire is at the rail, within 5 % of the ceiling
the command can actually reach.
**That ceiling is `min(max_w, the setpoint device's own rating)`, not `max_w`.**
The emitted command is clipped to the device's reported range as well as to
`max_w`, so on a 4700 W inverter configured with `max_w: 5000` a rail measured
at 4750 W is one the command can never stand at — the guard could not fire, and
the status page said `armed` anyway. It now measures the rail against the
smaller number and the page names it, saying *"below max_w because …"* when the
device is what capped it. (On an install that started, the two are equal: a
`max_w` above the device rating is refused at startup. This matters when the
rating could not be read at boot — see below.)
Neither half is usable alone. A bare "unchanged for N seconds" rule false-trips
at the exact operating point this controller aims for — at a converged −10 W a
@@ -666,6 +677,13 @@ that reads the meter's own document; on `ha_dsmr`, `mqtt_p1`, `ha_signed` and
`off` there is no signal to threshold and the status page says **NOT COVERED**
rather than pretending the guard is armed.
The same row appears for a second reason: a setpoint device that reports a range
from which no command magnitude is available in both directions leaves no rail
to measure at all, and a 0 W rail would be satisfied by *every* command. That is
reported as **NOT COVERED** too, and the detector stays silent rather than
degenerating into the bare "unchanged for N seconds" rule this design exists to
avoid.
| option | default | meaning |
|---|---|---|
| `meter_freeze_s` | 300 | Seconds of an unchanged measurement, *while the command is at the rail*, before the alarm |