SAFETY-81: no false 'Load too high' alarms
The alarm now also needs peakguard.load_too_high(): with the battery at full power, the quarter still ends more than 10 W over the real limit. The battery reading is the lower of this cycle's and the last, so a meter sample from before the battery's last increase is not counted twice. At most one alarm per quarter. Control outputs unchanged. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
This commit is contained in:
@@ -0,0 +1,47 @@
|
||||
# SAFETY-81 — no false "Load too high for battery" alarms
|
||||
|
||||
**Status: 2026-09-29, owner go for the card. The 10 W tolerance is this PR's choice, for review.**
|
||||
|
||||
## Defect
|
||||
|
||||
The SAFETY-79 test (SAFETY-79-test-report.md, F1/F2) saw 6 false alarms in 7.
|
||||
The alarm fired whenever `decide()` clamped its floor to the rating
|
||||
(`saturated`). Three things set that while the quarter landed on target:
|
||||
|
||||
- **Double count.** `decide()` sizes from the held meter reading plus the
|
||||
battery reading. When the meter sample predates the battery's last increase,
|
||||
the increase is counted twice. It happens under noise, and at each quarter
|
||||
start, where the battery is back while the held sample is still the spike.
|
||||
- **The aim, not the cap.** `saturated` is graded against cap − margin, so at
|
||||
margin 50 noise needs 50 W less to trip it (F2).
|
||||
- **Last seconds.** The gain 900 / remaining turns a few W over the aim into
|
||||
thousands of W wanted, with the battery far from its rating.
|
||||
|
||||
## Decision
|
||||
|
||||
The alarm needs `saturated` and `peakguard.load_too_high()`: with the battery
|
||||
at full power from now on, the quarter still ends more than `ALARM_MISS_W`
|
||||
(10 W) over the real limit (`ceiling_w`). That is the miss itself, without the
|
||||
gain. The battery reading it uses is the lower of this cycle's and the last
|
||||
one's. At most one alarm per quarter, because near the threshold the test
|
||||
flickers with the meter.
|
||||
|
||||
**Why 10 W:** at margin 0 the guard itself lands up to +5.7 W over (SAFETY-79
|
||||
test, check 5), and those misses are real but tiny; the alarm would fire in
|
||||
the last second of most guarded quarters. The margin (default 50) is the fix
|
||||
for them. Cost: a real miss of 10 W or less is not alarmed.
|
||||
|
||||
**Cost:** a load that climbs slowly through the band between the aim and the
|
||||
cap alarms when the quarter will end over the cap, not at the aim (10 s later
|
||||
in `ramp6500`). A step overload alarms in the same cycle as before; a real
|
||||
overload shows on the meter before the battery moves, so the lower reading
|
||||
costs it nothing. A quarter already over that the battery cannot win back
|
||||
still alarms (test_peakguard.py's saturated fixture).
|
||||
|
||||
## Not changed: the 1 s spike itself
|
||||
|
||||
The cycle after a quarter boundary and before the new quarter's first meter
|
||||
sample still sees 0 s left, files no claim, and an Off battery drops to 0 W for
|
||||
one cycle. That is the same edge tick as OPT-15 F1, so it is left to OPT-15.
|
||||
Control is unchanged here: every command in `tools/safety81_sim.py` is
|
||||
byte-identical to 5a4cdc2 (test_safety81.py part 1).
|
||||
@@ -1739,7 +1739,8 @@ control action and goes to the action log and the status page. A *saturated*
|
||||
guard — asking for everything the inverter has while the quarter is still
|
||||
projected over — raises one notification (`goodwe_peak_saturated`), because that
|
||||
is the one state where the money will be spent and shedding load is the only
|
||||
thing left that changes the bill.
|
||||
thing left that changes the bill. SAFETY-81 keeps a 1 s meter spike, noise and
|
||||
a quarter's last seconds from raising it: see `peakguard.load_too_high()`.
|
||||
|
||||
**And it sizes a price-driven charge, not only a forced discharge (SAFETY-45).**
|
||||
The same arithmetic read the other way answers *"how hard may this site charge
|
||||
@@ -3211,9 +3212,11 @@ reason code `OUTPUT_CLAMP`.
|
||||
**Load too high for battery.** The capacity-peak guard (SAFETY-07) asks for
|
||||
everything the inverter can discharge and the running 15-minute average is
|
||||
still projected over the peak limit, so the month's billed peak
|
||||
(capaciteitstarief) goes up. In shadow mode the guard's projection is made on a
|
||||
plant that did not respond (SAFETY-47), and the text says so. See *The
|
||||
capacity-peak guard*.
|
||||
(capaciteitstarief) goes up. It fires only when, with the battery at full
|
||||
power, the period will still end more than 10 W over the real limit (not the
|
||||
margin's aim), and at most once per period (SAFETY-81). In shadow mode the
|
||||
guard's projection is made on a plant that did not respond (SAFETY-47), and
|
||||
the text says so. See *The capacity-peak guard*.
|
||||
|
||||
**Battery stopped limiting the peak.** The peak guard may not discharge below
|
||||
`peak_soc_floor` (label “Peak reserve”, SAFETY-24). It also stops when the
|
||||
|
||||
@@ -922,6 +922,10 @@ class Controller:
|
||||
"peak_margin_w", peakguard.PEAK_OPTION_DEFAULTS["peak_margin_w"]))
|
||||
self._peak_engaged = False
|
||||
self._peak_saturated = False
|
||||
# SAFETY-81: what the alarm is graded on, beside the guard's decision.
|
||||
self._peak_proj = None
|
||||
self._peak_batt_prev = None
|
||||
self._peak_alarm_block = None
|
||||
self._peak_floor_limited = False
|
||||
self._maint_shape_suspended = False
|
||||
# OPT-11. Battery modes, off by default so an install that has not
|
||||
@@ -3712,8 +3716,10 @@ class Controller:
|
||||
# is not measured on that path, and the honest report is NOT COVERED -
|
||||
# the same answer, for the same reason, that the status page already
|
||||
# gives for SAFETY-18 on a transport that cannot see `unchanged_s`.
|
||||
self._peak_proj = (None if not self.p1_enabled
|
||||
else self.peak.project(self.p1.averager, now))
|
||||
self.peak_guard = None if not self.p1_enabled else peakguard.decide(
|
||||
self.peak.project(self.p1.averager, now),
|
||||
self._peak_proj,
|
||||
# ⚠️ THE SITE SUM. The guard sizes a floor from what the battery is
|
||||
# ALREADY removing from the meter, and the meter sees every
|
||||
# inverter. One unit's power here would size the floor from a
|
||||
@@ -4816,15 +4822,34 @@ class Controller:
|
||||
available to it. That is the one state where the money is going to be
|
||||
spent and a human is the only remaining actuator.
|
||||
|
||||
SAFETY-81: `g.saturated` alone is not enough. It is graded against the
|
||||
aim, and a 1 s meter spike, noise or the last seconds of a quarter set
|
||||
it while the quarter lands on target; `peakguard.load_too_high()` must
|
||||
agree too. The battery reading it gets is the lower of this cycle's and
|
||||
the last one's - see there.
|
||||
|
||||
Edge-triggered, and de-asserting arms it again - the same shape as
|
||||
FreezeWatchdog's `evaluate()`, and for the same reason: one notification
|
||||
per episode, not one per cycle.
|
||||
per episode, not one per cycle. SAFETY-81: and at most one per quarter.
|
||||
"""
|
||||
g = self.peak_guard
|
||||
saturated = bool(g is not None and g.saturated)
|
||||
batt, prev = self.site_batt_w, self._peak_batt_prev
|
||||
self._peak_batt_prev = batt
|
||||
if batt is not None and prev is not None:
|
||||
batt = min(float(batt), float(prev))
|
||||
saturated = bool(
|
||||
g is not None and g.saturated and self._peak_proj is not None
|
||||
and peakguard.load_too_high(
|
||||
self._peak_proj, batt_w=batt, ceiling_w=g.ceiling_w,
|
||||
achievable_w=self.site_rating_w))
|
||||
was, self._peak_saturated = self._peak_saturated, saturated
|
||||
if not saturated or was:
|
||||
return
|
||||
# SAFETY-81: at most once per quarter. Near its threshold the test
|
||||
# above flickers with the meter, and each flicker would re-alarm.
|
||||
if self._peak_proj.block_start == self._peak_alarm_block:
|
||||
return
|
||||
self._peak_alarm_block = self._peak_proj.block_start
|
||||
self.log_event("PEAK_GUARD_SATURATED - " + g.reason,
|
||||
hint=messages.hint("peak_saturated"))
|
||||
_LOG.error(
|
||||
|
||||
@@ -866,6 +866,37 @@ def decide(projection, *, batt_w, cap_w, margin_w, reading, achievable_w, soc,
|
||||
if saturated else "")))
|
||||
|
||||
|
||||
# SAFETY-81. A quarter must end this many W over the real limit before
|
||||
# "Load too high for battery" fires. Above the guard's own landing error at
|
||||
# margin 0 (up to +5.7 W, SAFETY-79 test check 5), which margin 0 accepts.
|
||||
ALARM_MISS_W = 10.0
|
||||
|
||||
|
||||
def load_too_high(projection, *, batt_w, ceiling_w, achievable_w) -> bool:
|
||||
"""SAFETY-81. May "Load too high for battery" fire? Only if, with the
|
||||
battery at full power from now on, the quarter still ends more than
|
||||
`ALARM_MISS_W` over the real limit (`ceiling_w`, not the aim).
|
||||
|
||||
This is the miss itself, in W of the quarter average, so it does not have
|
||||
`decide()`'s gain (900 / remaining): near a quarter's end that gain turns
|
||||
a watt over the aim into thousands of W wanted.
|
||||
|
||||
The load is the held meter reading plus `batt_w`. The caller passes the
|
||||
lower of this cycle's and the last cycle's battery reading, so a meter
|
||||
sample taken before the battery's last increase is not counted twice
|
||||
(DECISIONS/SAFETY-81-load-too-high.md). A real overload shows on the meter
|
||||
before the battery moves, so that filter costs it no cycle.
|
||||
"""
|
||||
remaining = QUARTER_S - float(projection.elapsed_s)
|
||||
if batt_w is None or remaining <= 0.0:
|
||||
return False
|
||||
rest = float(projection.held_w) + float(batt_w) - float(achievable_w)
|
||||
done_ws = (QUARTER_S * float(projection.projected_w)
|
||||
- max(float(projection.held_w), 0.0) * remaining)
|
||||
ends_w = (done_ws + max(rest, 0.0) * remaining) / QUARTER_S
|
||||
return ends_w - float(ceiling_w) > ALARM_MISS_W
|
||||
|
||||
|
||||
def charge_headroom_w(decision) -> float | None:
|
||||
"""SAFETY-45. The hardest this SITE may charge without putting the billed
|
||||
quarter over the ceiling, in W, positive - or None when nothing measured it.
|
||||
|
||||
@@ -0,0 +1,117 @@
|
||||
"""Runnable check for SAFETY-81, no false "Load too high for battery" alarms.
|
||||
`python3 test_safety81.py`
|
||||
|
||||
Drives the REAL Controller through tools/safety81_sim.py (a 1 s cycle on a
|
||||
plant shaped like the SAFETY-79 rig, one sample in ten late).
|
||||
DECISIONS/SAFETY-81-load-too-high.md has the record.
|
||||
|
||||
1. Every command is byte-identical to release/1.0 5a4cdc2.
|
||||
2. No alarm on the quarter-edge spike, the last seconds, noise (margin 50
|
||||
and 0) or a burst the quarter absorbs.
|
||||
3. Real overloads still alarm, as fast as on 5a4cdc2.
|
||||
4. peakguard.load_too_high() on its own.
|
||||
|
||||
Mutations (MUTATION.md, purged copies) are listed in the pull request.
|
||||
"""
|
||||
|
||||
import os
|
||||
import sys
|
||||
from types import SimpleNamespace
|
||||
|
||||
HERE = os.path.dirname(os.path.abspath(__file__))
|
||||
sys.path.insert(0, os.path.join(HERE, "tools"))
|
||||
|
||||
import safety81_sim as sim # noqa: E402
|
||||
from app.peakguard import load_too_high # noqa: E402
|
||||
|
||||
fails = []
|
||||
|
||||
|
||||
def check(name, cond):
|
||||
print(f" {'ok ' if cond else 'FAIL'} {name}")
|
||||
if not cond:
|
||||
fails.append(name)
|
||||
|
||||
|
||||
# Printed by `python3 tools/safety81_sim.py` on release/1.0 5a4cdc2 (the tool
|
||||
# copied in, nothing else changed), in the CI image: (alarm times, digest).
|
||||
BASE = {
|
||||
"const4500": ([2699.0], "6ba6b8634f0df9526adc04f03c82db7d083973268deda0d1f07c5519bc2e5e9d"),
|
||||
"const4500_m0": ([2699.0], "2bede28f3ea6ba9294be134c9b9733e43d22a7c24deac3bf8210bbbbe09b2039"),
|
||||
"sine4500": ([2699.0], "bf70c2c23a0eede40c34478d1354b7daa1858e0a0f920693e2dd15fb5046120f"),
|
||||
"edge4600": ([2.0, 902.0, 1802.0, 2699.0], "3cc0c6fec0c70f138530955babc2b416fe7307373037c1b2e927b6ccdaad3a4d"),
|
||||
"edge4600_m0": ([2.0, 902.0, 1802.0, 2699.0], "ba9ba2c042ee42b043315b996ece38b3478dc9866aaf833256c9c29c02f0fe9f"),
|
||||
"burst_end": ([881.0, 1781.0, 2681.0], "5f70e1eb4244820f1d44b494cb80e51f1a4486dee03357c9a8e8f7d371c5d9af"),
|
||||
"noise5000_m50": ([292.0, 2551.0, 2698.0], "48b446e1a78e6d6032b31cb68a4eadb0f74e3aec4cc1e184162e9c65449bfdc5"),
|
||||
"noise5000_m0": ([292.0, 2552.0, 2698.0], "1a0527dee6c2b03dc95a90b4682858c7bf5edf7205c2aced249112f04328c960"),
|
||||
"step6500": ([1201.0, 1801.0], "95e5c90e4a6814526cb4f3bea76286063b449d86a420f888c014531fb6e913a3"),
|
||||
"miss5560": ([1201.0, 1801.0], "cd991cfe1685750598236701a5a2f2f0342d66645609c536d42ab7ba07216e6c"),
|
||||
"ramp6500": ([1296.0, 1801.0], "8db7675535f1a01abf38bd6bfb996a6fe57711d3ecca53541bb1c0870748c46b"),
|
||||
"step7500_reserve": ([], "21eb9c07a4582f47f347084d1c75a28a5d767bc068bc3f74f32433d3239e9ccb"),
|
||||
}
|
||||
RUN = {k: sim.run(**v)[:2] for k, v in sim.SCENARIOS.items()}
|
||||
|
||||
# ============================================================================ #
|
||||
print("1. every command byte-identical to release/1.0 5a4cdc2")
|
||||
check("the same scenarios as 5a4cdc2", set(RUN) == set(BASE))
|
||||
for k, (alarms, digest) in RUN.items():
|
||||
check(f"{k}: digest {digest[:12]}", digest == BASE[k][1])
|
||||
|
||||
# ============================================================================ #
|
||||
print("2. no false alarm (5a4cdc2's are listed)")
|
||||
for k in ("edge4600", "edge4600_m0", "const4500", "const4500_m0", "sine4500",
|
||||
"noise5000_m50", "noise5000_m0", "burst_end"):
|
||||
check(f"{k}: none (5a4cdc2: {BASE[k][0]})", RUN[k][0] == [])
|
||||
|
||||
# ============================================================================ #
|
||||
print("3. real overloads still alarm, as fast as 5a4cdc2")
|
||||
for k in ("step6500", "miss5560"):
|
||||
print(f" {k}: load steps up at 1200 s; alarms at {RUN[k][0]}, "
|
||||
f"5a4cdc2 {BASE[k][0]}")
|
||||
check(f"{k}: the same second as 5a4cdc2, and again only at the next "
|
||||
f"quarter (at most once per quarter)", RUN[k][0] == BASE[k][0])
|
||||
# By design: until 1306 s this quarter would end at most ALARM_MISS_W over the
|
||||
# real 3500 W cap; 5a4cdc2 alarmed when it crossed the aim (cap - 50).
|
||||
print(f" ramp6500: alarms at {RUN['ramp6500'][0]}, "
|
||||
f"5a4cdc2 {BASE['ramp6500'][0]}")
|
||||
check("ramp6500: alarms once the quarter will end over the real cap by "
|
||||
"more than ALARM_MISS_W",
|
||||
RUN["ramp6500"][0] == [1306.0, 1801.0])
|
||||
check("step7500 under the peak reserve: not this alarm (the guard is not "
|
||||
"allowed to discharge)", RUN["step7500_reserve"][0] == [])
|
||||
|
||||
# ============================================================================ #
|
||||
print("4. load_too_high()")
|
||||
|
||||
|
||||
def proj(elapsed, done_avg, held):
|
||||
"""A projection `elapsed` s in, averaging `done_avg` so far."""
|
||||
r = 900.0 - elapsed
|
||||
return SimpleNamespace(elapsed_s=elapsed, held_w=held,
|
||||
projected_w=(done_avg * elapsed + max(held, 0) * r)
|
||||
/ 900.0)
|
||||
|
||||
|
||||
def ltl(p, batt, cap=3500.0, rail=2000.0):
|
||||
return load_too_high(p, batt_w=batt, ceiling_w=cap, achievable_w=rail)
|
||||
|
||||
|
||||
check("load 6000 W vs 3500 + 2000: yes", ltl(proj(300, 3450, 4000), 2000))
|
||||
check("already over, the battery can carry the load but not catch up: yes",
|
||||
ltl(proj(450, 7200, 7200), 0, rail=5000))
|
||||
check("the last second, a 7 W miss (under ALARM_MISS_W): no",
|
||||
not ltl(proj(899, 3509, 2500), 1000))
|
||||
check("a miss of exactly ALARM_MISS_W: no",
|
||||
not ltl(proj(450, 3520, 3500), 2000))
|
||||
check("...and 1 W more: yes", ltl(proj(450, 3522, 3500), 2000))
|
||||
check("over cap + battery, but the quarter lands under the cap: no",
|
||||
not ltl(proj(880, 3450, 4000), 2000))
|
||||
check("...and when it does not: yes", ltl(proj(700, 3450, 4000), 2000))
|
||||
check("no battery reading: no", not ltl(proj(300, 3450, 5000), None))
|
||||
check("no seconds left: no", not ltl(proj(900, 4000, 5000), 2000))
|
||||
|
||||
print()
|
||||
if fails:
|
||||
print(f"FAILED: {len(fails)} check(s)")
|
||||
sys.exit(1)
|
||||
print("all checks passed")
|
||||
@@ -0,0 +1,203 @@
|
||||
#!/usr/bin/env python3
|
||||
"""SAFETY-81: when does "Load too high for battery" fire?
|
||||
|
||||
python3 tools/safety81_sim.py # alarms and a control digest per run
|
||||
|
||||
The REAL Controller (read_inputs + cycle) at a 1 s cycle, on a plant shaped
|
||||
like the SAFETY-79 test rig: one battery switched Off (so only the peak guard
|
||||
makes it give, max 2000 W), a 3500 W cap, and a P1 meter that publishes
|
||||
0.3 s before each cycle. The battery reaches a new command 0.5 s after it is
|
||||
written. One meter sample in ten arrives late (the add-on still holds the one
|
||||
before), so the held meter reading can predate the battery's last change:
|
||||
the double count behind the rig's false alarms. The cycle on a quarter
|
||||
boundary, before the new quarter's first sample, files no peak claim, which
|
||||
is the rig's 1 s grid spike at each quarter change. Each run returns the
|
||||
alarm times and a digest of every command, so the same runs show both what
|
||||
changed and what did not.
|
||||
"""
|
||||
|
||||
import asyncio
|
||||
import hashlib
|
||||
import os
|
||||
import random
|
||||
import sys
|
||||
import tempfile
|
||||
import time
|
||||
from datetime import timedelta
|
||||
|
||||
sys.path.insert(0, os.path.dirname(os.path.abspath(__file__)))
|
||||
|
||||
import opt11_identity as rig # noqa: E402
|
||||
import app.main as m # noqa: E402
|
||||
from app import packmode # noqa: E402
|
||||
from app.main import Controller # noqa: E402
|
||||
from app.p1 import make_sample, split_signed # noqa: E402
|
||||
from app.store import unit_key # noqa: E402
|
||||
|
||||
TICK = 1.0
|
||||
SAMPLE_LEAD_S = 0.3 # the meter publishes this long before each cycle
|
||||
RESPONSE_S = 0.5 # a new command reaches the battery this much later
|
||||
LATE_P = 0.1 # share of meter samples that arrive late
|
||||
ALARM = "goodwe_peak_saturated"
|
||||
|
||||
|
||||
def constant(w):
|
||||
return lambda t: w
|
||||
|
||||
|
||||
def noisy(mean, amp, seed=81):
|
||||
"""`mean` +/- `amp`, a new uniform value every second."""
|
||||
rnd = random.Random(seed)
|
||||
table = {}
|
||||
|
||||
def f(t):
|
||||
k = int(t)
|
||||
if k not in table:
|
||||
table[k] = mean + rnd.uniform(-amp, amp)
|
||||
return table[k]
|
||||
return f
|
||||
|
||||
|
||||
def sine(mean, amp, period=120.0, noise=50.0):
|
||||
import math
|
||||
n = noisy(0.0, noise, seed=79)
|
||||
return lambda t: mean + amp * math.sin(2 * math.pi * t / period) + n(t)
|
||||
|
||||
|
||||
def step(before, after, at):
|
||||
return lambda t: before if t < at else after
|
||||
|
||||
|
||||
def ramp(before, after, at, secs):
|
||||
return lambda t: before + (after - before) * min(max(t - at, 0.0) / secs, 1.0)
|
||||
|
||||
|
||||
class _Plant:
|
||||
"""One battery that reaches its command RESPONSE_S after the write."""
|
||||
|
||||
def __init__(self, load, rating, soc):
|
||||
self.load, self.rating, self.soc = load, rating, soc
|
||||
self.t = 0.0
|
||||
self.hist = [(-1e9, 0.0)] # (time the command takes effect, W)
|
||||
self.notes = []
|
||||
self.meter = 0.0 # the last meter reading delivered
|
||||
|
||||
def batt(self, at):
|
||||
w = 0.0
|
||||
for when, v in self.hist:
|
||||
if when <= at:
|
||||
w = v
|
||||
return max(-self.rating, min(self.rating, float(round(w))))
|
||||
|
||||
def grid(self, at):
|
||||
return self.load(at) - self.batt(at)
|
||||
|
||||
async def limits(self, e):
|
||||
return (-5000.0, 5000.0, 1.0)
|
||||
|
||||
async def call(self, domain, service, data):
|
||||
if service == "create":
|
||||
self.notes.append((self.t, data.get("notification_id")))
|
||||
return True
|
||||
|
||||
async def number(self, e, invert=False):
|
||||
if e in ("sensor.grid", "sensor.net"):
|
||||
return self.meter
|
||||
if e.startswith("sensor.soc"):
|
||||
return self.soc
|
||||
if e.startswith("sensor.batt"):
|
||||
return self.batt(self.t)
|
||||
return None
|
||||
|
||||
async def set_number(self, e, v):
|
||||
self.hist.append((self.t + RESPONSE_S, float(v)))
|
||||
return True
|
||||
|
||||
|
||||
def run(load, *, margin=50, dur=2700.0, rating=2000.0, cap=3500.0,
|
||||
late_at=(), soc=60.0):
|
||||
"""Alarm times (s from the start of the first quarter) and a digest of
|
||||
every cycle's target and written command. A sample is also late at each
|
||||
`t % 900` in `late_at`."""
|
||||
opts = rig._options(1, {
|
||||
"meter_source": "ha_signed", "p1_net_entity": "sensor.net",
|
||||
"meter_phases": 1, "peak_cap_w": cap, "peak_margin_w": margin,
|
||||
"battery_modes_enabled": True, "max_w": rating})
|
||||
store = rig._Store()
|
||||
store.data[unit_key("inverter-a", packmode.USE_KEY)] = False
|
||||
store.data[packmode.USE_KEY] = False
|
||||
db = os.path.join(tempfile.mkdtemp(prefix="s81-"), "tariff.db")
|
||||
|
||||
async def go():
|
||||
plant = _Plant(load, rating, soc)
|
||||
c = Controller(opts, plant, store, rig._Pub(), stop=asyncio.Event(),
|
||||
peak_db_path=db)
|
||||
for i in c.inverters:
|
||||
i.dev_min, i.dev_max = -5000.0, 5000.0
|
||||
c.auto = True
|
||||
real_dt, clock = m.datetime, [0.0]
|
||||
|
||||
class _DT(real_dt):
|
||||
@classmethod
|
||||
def now(cls, tz=None):
|
||||
return rig.BASE + timedelta(seconds=clock[0])
|
||||
m.datetime = _DT
|
||||
rows, late = [], random.Random(8100)
|
||||
try:
|
||||
t = 0.0
|
||||
while t < dur:
|
||||
plant.t = clock[0] = t
|
||||
ts = t - SAMPLE_LEAD_S
|
||||
if late.random() >= LATE_P and t % 900 not in late_at:
|
||||
plant.meter = plant.grid(ts)
|
||||
imp, exp = split_signed(plant.meter)
|
||||
c.p1.submit(make_sample(
|
||||
"ha_signed", imp, exp, phases=1,
|
||||
ingest_ts=rig.BASE + timedelta(seconds=ts),
|
||||
ingest_mono=time.monotonic()))
|
||||
await c.read_inputs(now_mono=t)
|
||||
await c.cycle()
|
||||
rows.append((t, c.target, round(plant.hist[-1][1], 6)))
|
||||
t += TICK
|
||||
finally:
|
||||
m.datetime = real_dt
|
||||
return plant, c, rows
|
||||
plant, c, rows = asyncio.run(go())
|
||||
alarms = [t for t, nid in plant.notes if nid == ALARM]
|
||||
return alarms, hashlib.sha256(repr(rows).encode()).hexdigest(), c, rows
|
||||
|
||||
|
||||
# Three quarters each (2700 s); a new quarter starts at 900 s and 1800 s.
|
||||
SCENARIOS = {
|
||||
# F1: constant and sine loads the battery carries, across quarter edges.
|
||||
"const4500": dict(load=constant(4500.0)),
|
||||
"const4500_m0": dict(load=constant(4500.0), margin=0),
|
||||
"sine4500": dict(load=sine(4500.0, 400.0)),
|
||||
# F1 at the start of a quarter: the sample after the battery's return
|
||||
# is late, so the held reading is the 1 s spike (the battery at 0 W).
|
||||
"edge4600": dict(load=constant(4600.0), late_at=(2.0,)),
|
||||
"edge4600_m0": dict(load=constant(4600.0), margin=0, late_at=(2.0,)),
|
||||
# 6000 W in a quarter's last 20 s: over cap + battery, but the quarter
|
||||
# still lands between the aim and the cap.
|
||||
"burst_end": dict(load=lambda t: 6000.0 if t % 900 >= 880 else 4500.0),
|
||||
# F2: a noisy load the battery carries, at margin 50 and 0.
|
||||
"noise5000_m50": dict(load=noisy(5000.0, 150.0)),
|
||||
"noise5000_m0": dict(load=noisy(5000.0, 150.0), margin=0),
|
||||
# Real: from 1200 s the house needs 1000 W more than cap + battery.
|
||||
"step6500": dict(load=step(4500.0, 6500.0, 1200.0)),
|
||||
# Real, small: from 1200 s, 60 W (+/- 20 W noise) more than cap + battery.
|
||||
"miss5560": dict(load=lambda t: step(4500.0, 5560.0, 1200.0)(t)
|
||||
+ noisy(0.0, 20.0)(t)),
|
||||
# Real, slow: 4500 -> 6500 W over 200 s from 1200 s, through the band
|
||||
# between the aim (cap - 50) and the real cap.
|
||||
"ramp6500": dict(load=ramp(4500.0, 6500.0, 1200.0, 200.0)),
|
||||
# The pack under its peak reserve (20 %), and a load far over cap +
|
||||
# battery: that is "Battery stopped limiting the peak", not this alarm.
|
||||
"step7500_reserve": dict(load=step(4500.0, 7500.0, 1200.0), soc=15.0),
|
||||
}
|
||||
|
||||
|
||||
if __name__ == "__main__":
|
||||
for k, v in SCENARIOS.items():
|
||||
a, d, _, _ = run(**v)
|
||||
print(f"{k:16s} alarms at {a} digest {d}")
|
||||