SAFETY-81: no false 'Load too high' alarms
The alarm now also needs peakguard.load_too_high(): with the battery at full power, the quarter still ends more than 10 W over the real limit. The battery reading is the lower of this cycle's and the last, so a meter sample from before the battery's last increase is not counted twice. At most one alarm per quarter. Control outputs unchanged. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
This commit is contained in:
@@ -0,0 +1,47 @@
|
||||
# SAFETY-81 — no false "Load too high for battery" alarms
|
||||
|
||||
**Status: 2026-09-29, owner go for the card. The 10 W tolerance is this PR's choice, for review.**
|
||||
|
||||
## Defect
|
||||
|
||||
The SAFETY-79 test (SAFETY-79-test-report.md, F1/F2) saw 6 false alarms in 7.
|
||||
The alarm fired whenever `decide()` clamped its floor to the rating
|
||||
(`saturated`). Three things set that while the quarter landed on target:
|
||||
|
||||
- **Double count.** `decide()` sizes from the held meter reading plus the
|
||||
battery reading. When the meter sample predates the battery's last increase,
|
||||
the increase is counted twice. It happens under noise, and at each quarter
|
||||
start, where the battery is back while the held sample is still the spike.
|
||||
- **The aim, not the cap.** `saturated` is graded against cap − margin, so at
|
||||
margin 50 noise needs 50 W less to trip it (F2).
|
||||
- **Last seconds.** The gain 900 / remaining turns a few W over the aim into
|
||||
thousands of W wanted, with the battery far from its rating.
|
||||
|
||||
## Decision
|
||||
|
||||
The alarm needs `saturated` and `peakguard.load_too_high()`: with the battery
|
||||
at full power from now on, the quarter still ends more than `ALARM_MISS_W`
|
||||
(10 W) over the real limit (`ceiling_w`). That is the miss itself, without the
|
||||
gain. The battery reading it uses is the lower of this cycle's and the last
|
||||
one's. At most one alarm per quarter, because near the threshold the test
|
||||
flickers with the meter.
|
||||
|
||||
**Why 10 W:** at margin 0 the guard itself lands up to +5.7 W over (SAFETY-79
|
||||
test, check 5), and those misses are real but tiny; the alarm would fire in
|
||||
the last second of most guarded quarters. The margin (default 50) is the fix
|
||||
for them. Cost: a real miss of 10 W or less is not alarmed.
|
||||
|
||||
**Cost:** a load that climbs slowly through the band between the aim and the
|
||||
cap alarms when the quarter will end over the cap, not at the aim (10 s later
|
||||
in `ramp6500`). A step overload alarms in the same cycle as before; a real
|
||||
overload shows on the meter before the battery moves, so the lower reading
|
||||
costs it nothing. A quarter already over that the battery cannot win back
|
||||
still alarms (test_peakguard.py's saturated fixture).
|
||||
|
||||
## Not changed: the 1 s spike itself
|
||||
|
||||
The cycle after a quarter boundary and before the new quarter's first meter
|
||||
sample still sees 0 s left, files no claim, and an Off battery drops to 0 W for
|
||||
one cycle. That is the same edge tick as OPT-15 F1, so it is left to OPT-15.
|
||||
Control is unchanged here: every command in `tools/safety81_sim.py` is
|
||||
byte-identical to 5a4cdc2 (test_safety81.py part 1).
|
||||