SAFETY-13: the output freeze gets an exit, and only where it needs one
checks / unit (pull_request) Successful in 5m30s
checks / unit (pull_request) Successful in 5m30s
While the loop is frozen the command's magnitude may fall but never rise. At prev_w == 0 there is no magnitude left to fall, so a charge cannot START. That refusal is deliberate and it is kept: the inverter reporting power we did not command means another writer is on the actuator, which is the §1.5 non-goal. What it did not have was an END - nothing cleared it but the other writer leaving. Reproduced on release/1.0 @c8dcb38, at the live install's shape (max_w 5000, slew_w 400, target_grid_w -10), with another writer holding the pack at +700 W. The route is not the obvious one: entering from an export, the slew limit moves the command off zero before the counter reaches 3. It is entered from the DEADBAND - a site resting at its target counts saturated cycles while nothing is wrong - and 0 W is then a fixed point: a 2 kW export arriving afterwards leaves the command at exactly 0.0 W on every subsequent cycle. And prev_w == 0 is not where it stops. The same tuning pins at -800 W against its own integrator standing at -2388 W, with the same absence of an exit. So the change is written against the output freeze, not against a special case of it. THE DECISION IS WHICH FREEZES GET AN EXIT, NOT HOW LONG THE BLOCK LASTS. - A divergence a LIMIT could have produced - the inverter doing less than the command, in the command's own direction - clears itself, because the command is pinned at something the inverter can reach. No exit. release/1.0 unchanged, and asserted so: a curtailed inverter is never released over 30 cycles. - A divergence a limit could NOT have produced - overshooting the command, or the opposite sign - cannot clear itself, because clearing it needs the inverter to track OUR command. That one releases. unasked_power() is that predicate and it is physical, not statistical: a limit can only make the inverter do less, in the command's own direction, so everything a limit can produce lies in the interval spanned by 0 and prev_w widened by saturation_w. At prev_w == 0 it IS the saturation test, which is exactly why the zero case is the one that strands. The bound is not a new number. SETTLE_CYCLES = ceil(PLANT_SETTLE_S / LOOP_TICK_S) = 9, SAFETY-39's two measured constants and the reciprocal of SLEW_RAIL_FRAC: a divergence still standing after the plant's own settling time is not this plant catching up. _SAT_COUNT_CAP is written as SETTLE_CYCLES + 1; its value is unchanged at 10. RELEASING THE OUTPUT FREEZE DOES NOT UNFREEZE THE LOOP, which is what makes this bounded. The integrator freeze is untouched, so a released cycle can only move the command toward an accumulator that stopped accumulating, by at most one slew step, and never past it - swept over 107 625 released states. On the run above the command starts on the ninth saturated cycle and settles at -1190 W against a frozen integrator of -1194 W, not at the 5000 W rail. Graded against a transcription of release/1.0 over the 3024-case sweep, which was NOT taught the new rule: 2592 cases bit-identical, 432 releases, and 27 of those change the command - every one a charge from prev_w == 0 that release/1.0 refused to start. SAFETY-04's deliberate assertion is kept rather than inverted: its fixture sits below the bound, so it still asserts the block, and the release is asserted beside it on the other side of the bound. Coverage audit re-measured, same mutation form, __pycache__ purged: output freeze 2 -> 11 (2 reproduced on a pristinec8dcb38first), the exit 4, unasked_power 6. saturation_cycles at 9 or 10 removes the block entirely, because the freeze cannot engage before its own exit is due. Not refused at startup; asserted in the tests and written in DOCS.md. Nothing was measured on two inverters: inverter B does not physically exist (NOTES.md §1.1b) and sim/plantsim.py:216 INVERTER_B is INVERTER_A copied with measured=False. The N=2 escalation is stated from the code (actual_w is site_batt_w, the SUM) and is labelled as such. 22/22 test files pass in goodwe-addon-ci, mounted :ro, bytecode purged first. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
This commit is contained in:
@@ -16,6 +16,7 @@ the short version is in the comments below. Do not "clean this up" - each rule
|
||||
exists because its absence produced a specific, observed failure.
|
||||
"""
|
||||
|
||||
import math
|
||||
from dataclasses import dataclass
|
||||
|
||||
# ---------------------------------------------------------------------------
|
||||
@@ -86,6 +87,56 @@ PLANT_SETTLE_S = 18.0
|
||||
LOOP_TICK_S = 2.0
|
||||
SLEW_RAIL_FRAC = LOOP_TICK_S / PLANT_SETTLE_S # 0.111..., i.e. 9 ticks
|
||||
|
||||
# ---------------------------------------------------------------------------
|
||||
# SAFETY-13. HOW LONG THE PLANT STAYS A CANDIDATE EXPLANATION.
|
||||
#
|
||||
# The output freeze below stops the command growing while the inverter is not
|
||||
# following. Two completely different things produce that divergence and the
|
||||
# freeze cannot tell them apart on magnitude alone:
|
||||
#
|
||||
# (a) THE PLANT HAS NOT CAUGHT UP YET, or it is at a limit - a cold pack, a
|
||||
# curtailment, an export cap. Asking for more is pointless, and the
|
||||
# freeze is right to hold. It also CLEARS ITSELF: the command is pinned
|
||||
# at something the inverter can do, so the inverter catches up to it and
|
||||
# `saturated_now` goes false.
|
||||
#
|
||||
# (b) SOMETHING ELSE IS DRIVING THE ACTUATOR - the §1.5 non-goal, two writers
|
||||
# on one actuator. The freeze CANNOT clear itself here, because clearing
|
||||
# it needs the inverter to track OUR command and the other writer is what
|
||||
# stops it. Nothing ends this but the other writer going away.
|
||||
#
|
||||
# ⚠️ SO THE BOUND BELONGS TO (b) AND ONLY TO (b), and this constant is what
|
||||
# separates them in TIME rather than by guessing. Case (a) is bounded by the
|
||||
# plant: PLANT_SETTLE_S is how long this plant takes to settle, measured, and
|
||||
# after that the plant has run out of alibi. A divergence still standing after
|
||||
# PLANT_SETTLE_S is not this plant catching up.
|
||||
#
|
||||
# SETTLE_CYCLES = ceil(PLANT_SETTLE_S / LOOP_TICK_S)
|
||||
#
|
||||
# ⚠️ THE SAME TWO MEASURED NUMBERS SAFETY-39 USES, AND DELIBERATELY NOT A NEW
|
||||
# ONE. It is the reciprocal of SLEW_RAIL_FRAC - the slew limit takes exactly
|
||||
# this many ticks to traverse the rail, for exactly this reason. A new constant
|
||||
# here would be a second thing to re-derive when the plant is re-measured, and
|
||||
# a number that outlives its derivation is the defect SAFETY-39 was about.
|
||||
#
|
||||
# ⚠️ AND IT INHERITS SAFETY-39's CAVEAT ABOUT LOOP_TICK_S, in the opposite
|
||||
# direction, which is why it is repeated rather than cross-referenced. A meter
|
||||
# SLOWER than 2 s makes these 9 cycles cover MORE than 18 s, so the freeze
|
||||
# holds longer than the plant needs: that costs energy - see the case in
|
||||
# DOCS.md - and never safety. A meter FASTER than 2 s makes them cover LESS,
|
||||
# so the freeze can release while the plant is genuinely still moving. That one
|
||||
# is bounded twice over and by neither this constant nor luck: the INTEGRATOR
|
||||
# freeze is not released with the output freeze, so the command can only reach
|
||||
# the integrator's frozen value, and the output clamp bounds that in turn.
|
||||
SETTLE_CYCLES = math.ceil(PLANT_SETTLE_S / LOOP_TICK_S) # 9
|
||||
|
||||
# The saturation counter's ceiling. It has always been 10 and still is; it is
|
||||
# written against SETTLE_CYCLES rather than as a literal so that a counter
|
||||
# capped BELOW the longest bound read from it - which would silently make that
|
||||
# bound unreachable, i.e. delete the exit condition - cannot happen by editing
|
||||
# one of the two.
|
||||
_SAT_COUNT_CAP = SETTLE_CYCLES + 1 # 10
|
||||
|
||||
|
||||
@dataclass(frozen=True)
|
||||
class Tuning:
|
||||
@@ -185,6 +236,48 @@ def slew_limit_w(tuning: Tuning) -> float:
|
||||
return SLEW_RAIL_FRAC * abs(float(tuning.max_w))
|
||||
|
||||
|
||||
def unasked_power(prev_w: float, actual_w: float, saturation_w: float) -> bool:
|
||||
"""True when `actual_w` cannot be explained by the command not being met.
|
||||
|
||||
SAFETY-13. The one question the saturation magnitude test cannot answer:
|
||||
is the inverter FAILING TO REACH what we asked, or is it doing something we
|
||||
never asked for at all?
|
||||
|
||||
⚠️ THE ANSWER IS PHYSICAL, NOT STATISTICAL, WHICH IS WHY IT IS A PREDICATE
|
||||
AND NOT A THRESHOLD. A limit can only make the inverter do LESS than the
|
||||
command, in the command's own direction. It cannot make it overshoot the
|
||||
command, and it cannot make it produce power of the OPPOSITE sign. So the
|
||||
whole set of readings a limit can produce is the closed interval spanned by
|
||||
0 and `prev_w`, widened by `saturation_w` for measurement noise, ramp lag
|
||||
and the inverter's own idle draw. Anything outside that interval was put
|
||||
there by something other than this loop.
|
||||
|
||||
Worked, at `saturation_w = 500`:
|
||||
|
||||
prev +2000, actual +700 -> inside [0, 2000] a limit. False.
|
||||
prev -5000, actual -700 -> inside [-5000, 0] a limit. False.
|
||||
prev 0, actual +700 -> outside [-500, 500] unasked. True.
|
||||
prev -800, actual +700 -> outside [-1300, 500] unasked. True.
|
||||
|
||||
⚠️ AT `prev_w == 0` THIS IS EXACTLY `saturated_now`, and that is not a
|
||||
coincidence to be tidied away - it is the reason the freeze's zero case is
|
||||
the one the card was written about. With nothing commanded there is no
|
||||
interval left for a limit to live in, so every saturated cycle at zero is a
|
||||
cycle in which the actuator is being driven by someone else.
|
||||
|
||||
⚠️ IT IS NOT A DETECTOR AND MUST NOT BE ALARMED ON. A saturated inverter
|
||||
whose reading is stale, wrong-signed or simply noisy lands outside the
|
||||
interval too. All this predicate decides is whether the output freeze gets
|
||||
an EXIT; being wrong about it costs at most a bounded command that the
|
||||
frozen integrator and the output clamp both still bound. SAFETY-30's
|
||||
`unit_sign_disagree_w` is the thing that alarms on sign, and it is
|
||||
deliberately a different test with a different threshold.
|
||||
"""
|
||||
lo = min(0.0, float(prev_w)) - abs(float(saturation_w))
|
||||
hi = max(0.0, float(prev_w)) + abs(float(saturation_w))
|
||||
return not (lo <= float(actual_w) <= hi)
|
||||
|
||||
|
||||
def compute(
|
||||
prev_w: float,
|
||||
grid_w: float,
|
||||
@@ -232,7 +325,7 @@ def compute(
|
||||
# clockless; the remaining ceiling is that saturation_cycles expresses a
|
||||
# bound in seconds rather than an exact number of them.
|
||||
saturated_now = abs(prev_w - actual_w) > tuning.saturation_w
|
||||
sat_count = min(sat_count + 1, 10) if saturated_now else 0
|
||||
sat_count = min(sat_count + 1, _SAT_COUNT_CAP) if saturated_now else 0
|
||||
frozen = sat_count >= tuning.saturation_cycles
|
||||
|
||||
# --- deadband ----------------------------------------------------------
|
||||
@@ -346,8 +439,53 @@ def compute(
|
||||
# implementation: commanding 0 while the inverter reports >500 W means
|
||||
# something else is driving the bus, and that is not the moment to
|
||||
# start pushing power the other way.
|
||||
target = min(target, prev_w) if prev_w > 0 else max(target, prev_w)
|
||||
reason = "saturated-freeze"
|
||||
#
|
||||
# --- SAFETY-13: ...AND IT IS NOT THE MOMENT FOREVER EITHER ----------
|
||||
# Everything above stands. What was missing is an END. Held at
|
||||
# `prev_w == 0` this is a refusal to START, and nothing in this
|
||||
# function or above it clears it - not the error growing, not the
|
||||
# integrator moving, not time. Measured on release/1.0 @ c8dcb38, at
|
||||
# the live install's shape (max_w 5000, slew_w 400, target_grid_w -10):
|
||||
# a site resting in the deadband with another writer holding the pack
|
||||
# at +700 W reaches sat_count 3 with the command at 0, and 0 W is then
|
||||
# a FIXED POINT - a 2 kW export arriving afterwards leaves the command
|
||||
# at exactly 0.0 W on every subsequent cycle, with the integrator
|
||||
# standing at -1194 W the whole time.
|
||||
#
|
||||
# ⚠️ AND THE ZERO CASE IS NOT SPECIAL, WHICH IS WHY THE FIX IS NOT
|
||||
# SPECIAL EITHER. The same run pinned at prev_w == -800 W, against its
|
||||
# own integrator standing at -2388 W, for as long as it ran.
|
||||
# `prev_w == 0` is only the instance where the pinned magnitude happens
|
||||
# to be zero - i.e. where the standing cost is the whole of what the
|
||||
# battery could have done.
|
||||
# A rule written for the zero case alone would have left the other
|
||||
# instances exactly as unbounded as it found them.
|
||||
#
|
||||
# ⚠️ WHAT DECIDES IS NOT HOW LONG, IT IS WHETHER THE FREEZE CAN EVER
|
||||
# END ON ITS OWN. See SETTLE_CYCLES and `unasked_power()` at the top:
|
||||
# a divergence a LIMIT could produce clears itself once the inverter
|
||||
# catches up to the pinned command, so it needs no exit and gets none -
|
||||
# unbounded, exactly as shipped. A divergence a limit CANNOT produce is
|
||||
# another writer, which by construction stops our command ever being
|
||||
# tracked, so it can only end when the other writer leaves. That is the
|
||||
# one this releases, and only after the divergence has outlasted the
|
||||
# plant that would otherwise have explained it.
|
||||
#
|
||||
# ⚠️ RELEASING IS NOT UNFREEZING. The INTEGRATOR freeze above is not
|
||||
# lifted, and that is what makes this bounded rather than merely
|
||||
# different: the command is free to move, but only as far as an
|
||||
# integrator that stopped accumulating cycles ago, through the same
|
||||
# slew limit as any other cycle. It buys back the standing error, not
|
||||
# the rail.
|
||||
#
|
||||
# `reason` is authoritative here in a way it is not elsewhere in this
|
||||
# function: nothing after this line writes it.
|
||||
if unasked_power(prev_w, actual_w, tuning.saturation_w) \
|
||||
and sat_count >= SETTLE_CYCLES:
|
||||
reason = "freeze-released"
|
||||
else:
|
||||
target = min(target, prev_w) if prev_w > 0 else max(target, prev_w)
|
||||
reason = "saturated-freeze"
|
||||
|
||||
# --- quantise ----------------------------------------------------------
|
||||
# 10 W. The register is 1 W and the inverter reports at 1 W, but its
|
||||
|
||||
Reference in New Issue