SAFETY-13: the output freeze gets an exit, and only where it needs one
checks / unit (pull_request) Successful in 5m30s

While the loop is frozen the command's magnitude may fall but never rise. At
prev_w == 0 there is no magnitude left to fall, so a charge cannot START. That
refusal is deliberate and it is kept: the inverter reporting power we did not
command means another writer is on the actuator, which is the §1.5 non-goal.
What it did not have was an END - nothing cleared it but the other writer
leaving.

Reproduced on release/1.0 @ c8dcb38, at the live install's shape (max_w 5000,
slew_w 400, target_grid_w -10), with another writer holding the pack at +700 W.
The route is not the obvious one: entering from an export, the slew limit moves
the command off zero before the counter reaches 3. It is entered from the
DEADBAND - a site resting at its target counts saturated cycles while nothing is
wrong - and 0 W is then a fixed point: a 2 kW export arriving afterwards leaves
the command at exactly 0.0 W on every subsequent cycle.

And prev_w == 0 is not where it stops. The same tuning pins at -800 W against
its own integrator standing at -2388 W, with the same absence of an exit. So the
change is written against the output freeze, not against a special case of it.

THE DECISION IS WHICH FREEZES GET AN EXIT, NOT HOW LONG THE BLOCK LASTS.

  - A divergence a LIMIT could have produced - the inverter doing less than the
    command, in the command's own direction - clears itself, because the command
    is pinned at something the inverter can reach. No exit. release/1.0
    unchanged, and asserted so: a curtailed inverter is never released over 30
    cycles.
  - A divergence a limit could NOT have produced - overshooting the command, or
    the opposite sign - cannot clear itself, because clearing it needs the
    inverter to track OUR command. That one releases.

unasked_power() is that predicate and it is physical, not statistical: a limit
can only make the inverter do less, in the command's own direction, so
everything a limit can produce lies in the interval spanned by 0 and prev_w
widened by saturation_w. At prev_w == 0 it IS the saturation test, which is
exactly why the zero case is the one that strands.

The bound is not a new number. SETTLE_CYCLES = ceil(PLANT_SETTLE_S /
LOOP_TICK_S) = 9, SAFETY-39's two measured constants and the reciprocal of
SLEW_RAIL_FRAC: a divergence still standing after the plant's own settling time
is not this plant catching up. _SAT_COUNT_CAP is written as SETTLE_CYCLES + 1;
its value is unchanged at 10.

RELEASING THE OUTPUT FREEZE DOES NOT UNFREEZE THE LOOP, which is what makes this
bounded. The integrator freeze is untouched, so a released cycle can only move
the command toward an accumulator that stopped accumulating, by at most one slew
step, and never past it - swept over 107 625 released states. On the run above
the command starts on the ninth saturated cycle and settles at -1190 W against a
frozen integrator of -1194 W, not at the 5000 W rail.

Graded against a transcription of release/1.0 over the 3024-case sweep, which
was NOT taught the new rule: 2592 cases bit-identical, 432 releases, and 27 of
those change the command - every one a charge from prev_w == 0 that release/1.0
refused to start.

SAFETY-04's deliberate assertion is kept rather than inverted: its fixture sits
below the bound, so it still asserts the block, and the release is asserted
beside it on the other side of the bound.

Coverage audit re-measured, same mutation form, __pycache__ purged: output
freeze 2 -> 11 (2 reproduced on a pristine c8dcb38 first), the exit 4,
unasked_power 6.

saturation_cycles at 9 or 10 removes the block entirely, because the freeze
cannot engage before its own exit is due. Not refused at startup; asserted in
the tests and written in DOCS.md.

Nothing was measured on two inverters: inverter B does not physically exist
(NOTES.md §1.1b) and sim/plantsim.py:216 INVERTER_B is INVERTER_A copied with
measured=False. The N=2 escalation is stated from the code (actual_w is
site_batt_w, the SUM) and is labelled as such.

22/22 test files pass in goodwe-addon-ci, mounted :ro, bytecode purged first.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
This commit is contained in:
2026-09-06 13:56:26 +02:00
co-authored by Claude Opus 5
parent c8dcb38a95
commit 6c4565659b
5 changed files with 761 additions and 13 deletions
+141 -3
View File
@@ -16,6 +16,7 @@ the short version is in the comments below. Do not "clean this up" - each rule
exists because its absence produced a specific, observed failure.
"""
import math
from dataclasses import dataclass
# ---------------------------------------------------------------------------
@@ -86,6 +87,56 @@ PLANT_SETTLE_S = 18.0
LOOP_TICK_S = 2.0
SLEW_RAIL_FRAC = LOOP_TICK_S / PLANT_SETTLE_S # 0.111..., i.e. 9 ticks
# ---------------------------------------------------------------------------
# SAFETY-13. HOW LONG THE PLANT STAYS A CANDIDATE EXPLANATION.
#
# The output freeze below stops the command growing while the inverter is not
# following. Two completely different things produce that divergence and the
# freeze cannot tell them apart on magnitude alone:
#
# (a) THE PLANT HAS NOT CAUGHT UP YET, or it is at a limit - a cold pack, a
# curtailment, an export cap. Asking for more is pointless, and the
# freeze is right to hold. It also CLEARS ITSELF: the command is pinned
# at something the inverter can do, so the inverter catches up to it and
# `saturated_now` goes false.
#
# (b) SOMETHING ELSE IS DRIVING THE ACTUATOR - the §1.5 non-goal, two writers
# on one actuator. The freeze CANNOT clear itself here, because clearing
# it needs the inverter to track OUR command and the other writer is what
# stops it. Nothing ends this but the other writer going away.
#
# ⚠️ SO THE BOUND BELONGS TO (b) AND ONLY TO (b), and this constant is what
# separates them in TIME rather than by guessing. Case (a) is bounded by the
# plant: PLANT_SETTLE_S is how long this plant takes to settle, measured, and
# after that the plant has run out of alibi. A divergence still standing after
# PLANT_SETTLE_S is not this plant catching up.
#
# SETTLE_CYCLES = ceil(PLANT_SETTLE_S / LOOP_TICK_S)
#
# ⚠️ THE SAME TWO MEASURED NUMBERS SAFETY-39 USES, AND DELIBERATELY NOT A NEW
# ONE. It is the reciprocal of SLEW_RAIL_FRAC - the slew limit takes exactly
# this many ticks to traverse the rail, for exactly this reason. A new constant
# here would be a second thing to re-derive when the plant is re-measured, and
# a number that outlives its derivation is the defect SAFETY-39 was about.
#
# ⚠️ AND IT INHERITS SAFETY-39's CAVEAT ABOUT LOOP_TICK_S, in the opposite
# direction, which is why it is repeated rather than cross-referenced. A meter
# SLOWER than 2 s makes these 9 cycles cover MORE than 18 s, so the freeze
# holds longer than the plant needs: that costs energy - see the case in
# DOCS.md - and never safety. A meter FASTER than 2 s makes them cover LESS,
# so the freeze can release while the plant is genuinely still moving. That one
# is bounded twice over and by neither this constant nor luck: the INTEGRATOR
# freeze is not released with the output freeze, so the command can only reach
# the integrator's frozen value, and the output clamp bounds that in turn.
SETTLE_CYCLES = math.ceil(PLANT_SETTLE_S / LOOP_TICK_S) # 9
# The saturation counter's ceiling. It has always been 10 and still is; it is
# written against SETTLE_CYCLES rather than as a literal so that a counter
# capped BELOW the longest bound read from it - which would silently make that
# bound unreachable, i.e. delete the exit condition - cannot happen by editing
# one of the two.
_SAT_COUNT_CAP = SETTLE_CYCLES + 1 # 10
@dataclass(frozen=True)
class Tuning:
@@ -185,6 +236,48 @@ def slew_limit_w(tuning: Tuning) -> float:
return SLEW_RAIL_FRAC * abs(float(tuning.max_w))
def unasked_power(prev_w: float, actual_w: float, saturation_w: float) -> bool:
"""True when `actual_w` cannot be explained by the command not being met.
SAFETY-13. The one question the saturation magnitude test cannot answer:
is the inverter FAILING TO REACH what we asked, or is it doing something we
never asked for at all?
⚠️ THE ANSWER IS PHYSICAL, NOT STATISTICAL, WHICH IS WHY IT IS A PREDICATE
AND NOT A THRESHOLD. A limit can only make the inverter do LESS than the
command, in the command's own direction. It cannot make it overshoot the
command, and it cannot make it produce power of the OPPOSITE sign. So the
whole set of readings a limit can produce is the closed interval spanned by
0 and `prev_w`, widened by `saturation_w` for measurement noise, ramp lag
and the inverter's own idle draw. Anything outside that interval was put
there by something other than this loop.
Worked, at `saturation_w = 500`:
prev +2000, actual +700 -> inside [0, 2000] a limit. False.
prev -5000, actual -700 -> inside [-5000, 0] a limit. False.
prev 0, actual +700 -> outside [-500, 500] unasked. True.
prev -800, actual +700 -> outside [-1300, 500] unasked. True.
⚠️ AT `prev_w == 0` THIS IS EXACTLY `saturated_now`, and that is not a
coincidence to be tidied away - it is the reason the freeze's zero case is
the one the card was written about. With nothing commanded there is no
interval left for a limit to live in, so every saturated cycle at zero is a
cycle in which the actuator is being driven by someone else.
⚠️ IT IS NOT A DETECTOR AND MUST NOT BE ALARMED ON. A saturated inverter
whose reading is stale, wrong-signed or simply noisy lands outside the
interval too. All this predicate decides is whether the output freeze gets
an EXIT; being wrong about it costs at most a bounded command that the
frozen integrator and the output clamp both still bound. SAFETY-30's
`unit_sign_disagree_w` is the thing that alarms on sign, and it is
deliberately a different test with a different threshold.
"""
lo = min(0.0, float(prev_w)) - abs(float(saturation_w))
hi = max(0.0, float(prev_w)) + abs(float(saturation_w))
return not (lo <= float(actual_w) <= hi)
def compute(
prev_w: float,
grid_w: float,
@@ -232,7 +325,7 @@ def compute(
# clockless; the remaining ceiling is that saturation_cycles expresses a
# bound in seconds rather than an exact number of them.
saturated_now = abs(prev_w - actual_w) > tuning.saturation_w
sat_count = min(sat_count + 1, 10) if saturated_now else 0
sat_count = min(sat_count + 1, _SAT_COUNT_CAP) if saturated_now else 0
frozen = sat_count >= tuning.saturation_cycles
# --- deadband ----------------------------------------------------------
@@ -346,8 +439,53 @@ def compute(
# implementation: commanding 0 while the inverter reports >500 W means
# something else is driving the bus, and that is not the moment to
# start pushing power the other way.
target = min(target, prev_w) if prev_w > 0 else max(target, prev_w)
reason = "saturated-freeze"
#
# --- SAFETY-13: ...AND IT IS NOT THE MOMENT FOREVER EITHER ----------
# Everything above stands. What was missing is an END. Held at
# `prev_w == 0` this is a refusal to START, and nothing in this
# function or above it clears it - not the error growing, not the
# integrator moving, not time. Measured on release/1.0 @ c8dcb38, at
# the live install's shape (max_w 5000, slew_w 400, target_grid_w -10):
# a site resting in the deadband with another writer holding the pack
# at +700 W reaches sat_count 3 with the command at 0, and 0 W is then
# a FIXED POINT - a 2 kW export arriving afterwards leaves the command
# at exactly 0.0 W on every subsequent cycle, with the integrator
# standing at -1194 W the whole time.
#
# ⚠️ AND THE ZERO CASE IS NOT SPECIAL, WHICH IS WHY THE FIX IS NOT
# SPECIAL EITHER. The same run pinned at prev_w == -800 W, against its
# own integrator standing at -2388 W, for as long as it ran.
# `prev_w == 0` is only the instance where the pinned magnitude happens
# to be zero - i.e. where the standing cost is the whole of what the
# battery could have done.
# A rule written for the zero case alone would have left the other
# instances exactly as unbounded as it found them.
#
# ⚠️ WHAT DECIDES IS NOT HOW LONG, IT IS WHETHER THE FREEZE CAN EVER
# END ON ITS OWN. See SETTLE_CYCLES and `unasked_power()` at the top:
# a divergence a LIMIT could produce clears itself once the inverter
# catches up to the pinned command, so it needs no exit and gets none -
# unbounded, exactly as shipped. A divergence a limit CANNOT produce is
# another writer, which by construction stops our command ever being
# tracked, so it can only end when the other writer leaves. That is the
# one this releases, and only after the divergence has outlasted the
# plant that would otherwise have explained it.
#
# ⚠️ RELEASING IS NOT UNFREEZING. The INTEGRATOR freeze above is not
# lifted, and that is what makes this bounded rather than merely
# different: the command is free to move, but only as far as an
# integrator that stopped accumulating cycles ago, through the same
# slew limit as any other cycle. It buys back the standing error, not
# the rail.
#
# `reason` is authoritative here in a way it is not elsewhere in this
# function: nothing after this line writes it.
if unasked_power(prev_w, actual_w, tuning.saturation_w) \
and sat_count >= SETTLE_CYCLES:
reason = "freeze-released"
else:
target = min(target, prev_w) if prev_w > 0 else max(target, prev_w)
reason = "saturated-freeze"
# --- quantise ----------------------------------------------------------
# 10 W. The register is 1 W and the inverter reports at 1 W, but its