SAFETY-94: a healthy battery that lags or reverses is not flagged as frozen or refusing
The stale-reading gate counted its 35 s from the register's last change, so after a rest the first read after a new command tripped it (SAFETY-58; live 2026-10-03, four trips 1 s after the command). It now counts only the time the command asked the register to move. At N=1 the refusal engaged after 12 frozen cycles if the reading was under 100 W at that moment, which a battery reversing through its lag passes at a 1 s meter. The refusal now needs the N>1 evidence at every roster size: under 100 W, one way, for 12 cycles spanning 22 s, restarting when the reading moves 50 W towards the ask. DECISIONS/SAFETY-94-lagging-battery.md; test_safety94.py. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
This commit is contained in:
@@ -590,7 +590,7 @@ accumulator is doing:
|
||||
| `freeze-released` | the freeze had run out of plant-shaped explanations and the command was let move again |
|
||||
| `mode-bound` | the batteries' limits set the command, not the meter: their battery modes, or, with two or more inverters, a battery in its monthly maintenance |
|
||||
| `not-running` | control is stopped **and** shadow mode is off, so the loop did not run |
|
||||
| `battery refuses` | the battery gave less than 100 W for 12 cycles (a minute at a 5-second meter) while asked for more than 500 W, so the add-on asks 0 W in that direction (see below) |
|
||||
| `battery refuses` | the battery gave less than 100 W for 12 cycles and at least 22 s (a minute at a 5-second meter) while asked for more than 500 W, so the add-on asks 0 W in that direction (see below) |
|
||||
| `battery probe` | the add-on asks 200 W to test whether a refusing battery gives power again |
|
||||
|
||||
**When the battery refuses.** At its cut-out level the battery gives nothing,
|
||||
@@ -600,7 +600,9 @@ request, and the `Why` row reads *The battery refuses to give power: 0 W*. Every
|
||||
the battery gives 100 W or more, when the grid needs charging instead, and when
|
||||
control is stopped or started. 200 W is below the 250 W the stale-reading check
|
||||
needs, so a test never trips it. A battery that gives some power, even 100 W,
|
||||
is not refusing and keeps its request.
|
||||
is not refusing and keeps its request. Nor is a battery whose reading is
|
||||
still moving towards the request, such as one turning from charging to
|
||||
giving (SAFETY-94).
|
||||
|
||||
**With two or more inverters** the same rule works per inverter. An inverter
|
||||
whose battery gives less than 100 W for 12 cycles, and at least 22 s, while
|
||||
@@ -3457,7 +3459,8 @@ reason code, and its full figures are on the DEBUG line right after it and in
|
||||
…`, and the peak guard's full reason is on the DEBUG line after its ERROR.
|
||||
- ***name*: battery power reading stopped changing** is SAFETY-37/56/57. The
|
||||
ERROR line says when it clears and names `STALE_READING`. The full reason,
|
||||
with both possible causes, is on the DEBUG line after it.
|
||||
with both possible causes, is on the DEBUG line after it. The 35 s counts
|
||||
only while the command asks the reading to move (SAFETY-94).
|
||||
- **Meter: no reading for …** (red): the add-on logs one WARNING when the
|
||||
meter goes quiet, "No meter reading for …", and an INFO line when readings
|
||||
return, at most once every 10 minutes. Past `stale_input_s` the **Why**
|
||||
|
||||