@@ -28,8 +28,6 @@ Contents of this release, in merge order since 0.21.0 (`5e00cbb`):
### Known issues
### Known issues
- A false "Battery is not keeping up" can still show when the peak guard pauses a maintenance charge ([[SAFETY-92]]).
- A battery capped at a low limit with a perfectly flat reading can still trip the stale check ([[SAFETY-74]]).
- A battery whose reading at rest is beyond about ±175 W is still not caught when it refuses ([[SAFETY-97]]).
@@ -42,7 +40,7 @@ Contents of this release, in merge order since 0.21.0 (`5e00cbb`):
- Two inverters: after a drain ends, a change in house use can go unanswered for about 9 s, because some readings are old ([[SAFETY-106]]).
- Two inverters: when one battery's level is missing, both batteries are held at 0 W, and for about 15 s the last command stays on ([[SAFETY-108]]).
- Two inverters: if one battery's level stays missing for 12 h, the other battery's cycle can be marked failed, with a 7-day wait and a notice, though it is healthy. This comes from reading the code; it has not been seen on a site ([[MAINT-17]]).
- When the 15-minute demand forecast sensor counts the battery's own charge, the maintenance charge runs at about half the power the peak limit leaves, so it takes about twice as long. Seen on a site: about 1.2 kW instead of 2.5 kW, and the peak limit was kept Since 0.22.0 the other battery's grid charge waits while this charge runs. At the start of a month, before a peak above the limit has been seen, this charge can give about 2 kWh a night (a rig test) and need about 4 nights, longer than its 36 h limit, and the other battery loses those cheap nights ([[SAFETY-111]]).
- When the 15-minute demand forecast sensor counts the battery's own charge, the maintenance charge runs at about half the power the peak limit leaves, so it takes about twice as long. Seen on a site: about 1.2 kW instead of 2.5 kW, and the peak limit was kept. Since 0.22.0 the other battery's grid charge waits while this charge runs. At the start of a month, before a peak above the limit has been seen, this charge can give about 2 kWh a night (a rig test) and need about 4 nights, longer than its 36 h limit, and the other battery loses those cheap nights ([[SAFETY-111]]).
- One inverter: after a link drop, the battery's own safety stop to 0 W can be taken as a refusal, and the site stays at 0 W for up to 15 min ([[SAFETY-102]]).
- After a Home Assistant restart, control still waits until Home Assistant has finished starting, which can take several minutes, though the readings are already there ([[SAFETY-115]]).
- While Home Assistant is not answering, the page can list inverters as refusing commands and sensors as missing, and send you to Developer Tools, though they are fine ([[UX-37]]).