SAFETY-40 review: integrator-bound WARNING gets its own notification id
A later anti-windup notice could replace a write-path BUG SIGNAL notice
under the shared goodwe_output_clamp id (escalation ignores the budget).
The WARNING now uses goodwe_integrator_bound and points to DOCS; the
cadence sentence in DOCS is corrected. Tests pin both ids (red on fd14569).
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
This commit is contained in:
co-authored by
Claude Opus 5.5
parent
fd14569a71
commit
55a6d5dcdb
@@ -1641,10 +1641,10 @@ other guard's entries out of it.
|
||||
**There is nothing to configure**, deliberately. The bound is `max_w`, which you
|
||||
already set; giving the guard a limit of its own would be a second number that
|
||||
can disagree with the first, which is exactly the failure the startup validation
|
||||
exists to prevent. The alarm's cadence - at most one notification per 150 s
|
||||
(an episode that has not yet notified does so once it has engaged 3 cycles in
|
||||
a row), cleared after 3 clean
|
||||
cycles - is fixed for the same reason `RAIL_FRAC` is: it describes the
|
||||
exists to prevent. The alarm's cadence - normally at most one notification per
|
||||
150 s (an episode that has not yet notified does so once it has engaged 3
|
||||
cycles in a row, and an over-rating has its own 150 s budget), cleared after 3
|
||||
clean cycles - is fixed for the same reason `RAIL_FRAC` is: it describes the
|
||||
notification bus, not the plant.
|
||||
|
||||
WARNING: **on a default install the engagement you will see is the integrator's,
|
||||
@@ -1657,10 +1657,12 @@ every standard configuration.
|
||||
**The integrator bound is not a bug, and it is reported as what it is.** It
|
||||
reads *"the loop's integrator reached its +5000 W anti-windup bound; the loop's
|
||||
command this cycle was +2000 W"*, titled *"the control loop is at its integrator
|
||||
bound"*, logged as a `WARNING`, with an amber (not red) status row. Brief
|
||||
bound"*, logged as a `WARNING`, with an amber (not red) status row and its own
|
||||
notification (`goodwe_integrator_bound`), so it never replaces a BUG SIGNAL
|
||||
notice still on screen. Brief
|
||||
engagements after a large load or solar step are normal. If it stays engaged,
|
||||
check that the battery is following its commands. Only a command over the rating
|
||||
carries the BUG SIGNAL text, and it never waits behind integrator-bound notices.
|
||||
carries the BUG SIGNAL text, and it has its own notification budget.
|
||||
Why: [`DECISIONS/SAFETY-40-the-integrator-bound-is-not-a-bug.md`](DECISIONS/SAFETY-40-the-integrator-bound-is-not-a-bug.md).
|
||||
|
||||