CFG-01 review: widen the rule, refuse the firmware-veto case, fix the stop footgun

Review findings, all confirmed in code before changing anything.

THE RULE DID NOT AUTHORISE ITS OWN BEST REFUSAL. The stated test was
"makes a safety mechanism inoperative, or makes a stated limit untrue",
and a blank setpoint_entity does neither - layer 1 pinning the inverter
at 0 W is the failsafe WORKING, as validate.py's own text admitted. The
real justification is a second, separate category: the add-on is inert
and indistinguishable from healthy. Stated as (a) and (b), with each
refusal tagged, and with both halves explicitly bounded - (a) is not
"any two numbers that could disagree", (b) is not "anything degraded".
Left implicit, the gap is where trivia-creep comes back in.

meter_max_age_s ABOVE THE FIRMWARE'S VETO IS NOW REFUSED. The schema
allows int(5,300); the firmware's threshold is a compile-time
`max_age_s: "30"` and it trips layer 1 at `p1_age_s >= 30`. At 120 the
add-on believes a 119 s reading is fresh and keeps commanding while the
board has already vetoed and is holding at 0 W - healthy meter, running
controller, nothing moving. Structurally identical to the max_w case,
and unlike max_w it is settable on this install, so the headline
behaviour finally has a live demonstration. That firmware file's own
comment says a lower bound on this "belongs in CFG-01, not here".

Only ABOVE is refused: below the veto the add-on gives up first, which
is fail-safe and visible on its own status page. Scoped to P1 being
enabled, because meter_max_age_s governs nothing otherwise.
FIRMWARE_INGEST_VETO_S cannot be imported from a compile-time YAML
substitution, so it carries a note on the single direction in which it
can go stale - and a warning that TEL-06 is editing `ingest_stale`, so a
matching integer may stop meaning a matching rule.

stop= WAS A LIVE FOOTGUN. It defaulted to None, which made a Controller
that cannot stop itself the DEFAULT one. On the late-refusal path that
meant: log the banner, return, and leave the process alive forever with
no control loop and no exit - the exact "inert but looks healthy"
failure this module exists to refuse. Now required and keyword-only, so
the broken shape does not construct; test_p1.py's five call sites pass
an Event.

That whole path had no test and no live demo. It has one now: it drives
run_control() against a device that only reports a narrower range once
the loop starts, and asserts it refuses, signals, returns, and writes
NOTHING - plus the converse, that an agreeing device leads to real
writes. This also covers the max_w composition that cannot be reached
through the Supervisor on the live install.

max_w <= 0 is refused. Schema-blocked in production, but
validate_startup_config() is the simulation suite's entry point too, and
a non-positive max_w inverts the arbiter's supervised bounds into a
contradiction that reads as a safety trip rather than a typo.

Verified live 2026-08-28 (backup goodwe_controller-cfg01r2-1787940076):
meter_max_age_s 120 refused with a message naming 120, 30, and THE
FIRMWARE WINS; no traceback; add-on restored byte-exact and running.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
This commit is contained in:
glenn schrooyen
2026-08-28 20:05:10 +02:00
co-authored by Claude Opus 5
parent fc9bd89dca
commit 547d796c5d
5 changed files with 310 additions and 24 deletions
+26 -3
View File
@@ -7,8 +7,14 @@ instead of logging a line and carrying on. `validate_startup_config()` runs in
`amain()` before the broker, the web server or any task exists, so a refusal
cannot leave half a controller running behind a UI.
It refuses exactly three things, all of which share one property - continuing
makes a safety mechanism inoperative or makes a stated limit untrue:
It refuses only where continuing produces one of two outcomes: **(a)** a stated
limit is untrue - the operator configured a bound and a lower layer silently
enforces a different one - or **(b)** the add-on is inert and indistinguishable
from healthy. (b) is not a special case of (a): with no `setpoint_entity`, layer
1 pinning the inverter at 0 W is the failsafe *working*. The system does not
become unsafe, it becomes a convincing impression of a working controller.
Four things qualify:
- **`max_w` above (or below) the setpoint device's own rating.** This is the one
that changed behaviour. It used to warn `the device wins` and run anyway, with
@@ -25,8 +31,25 @@ makes a safety mechanism inoperative or makes a stated limit untrue:
ingestion*, which leaves the grid reading None forever: permanent "inputs
missing", 0 W, and a status page indistinguishable from a healthy meter nobody
has sent anything to yet.
- **`meter_max_age_s` above the firmware's ingest veto.** The schema accepts
`int(5,300)`; the ESP32's threshold is a compile-time `max_age_s: "30"` and it
trips layer 1 at `p1_age_s >= 30`. Set 120 and the add-on treats a 119 s
reading as fresh and keeps commanding, while the firmware has already vetoed
and is holding the inverter at 0 W - healthy meter, running controller,
nothing moving, and no line anywhere saying the number you set was overruled.
Structurally the same fault as the `max_w` case. Only *above* the veto is
refused: below it the add-on gives up first, which is fail-safe and visible on
its own status page. Mirrored as `validate.FIRMWARE_INGEST_VETO_S` - it cannot
be imported from a compile-time YAML substitution, so it carries a note about
the one direction in which it can go stale.
The predicates for the last group still live in `p1.validate_meter_options()`,
`max_w` at or below zero is refused too. Schema-blocked on a real install, but
`validate_startup_config()` is now also the simulation suite's entry point, and
a non-positive `max_w` inverts the arbiter's `supervised` bounds into a
contradiction that resolves to 0 W - i.e. it would read as a safety trip rather
than as the typo it is.
The predicates for the meter group still live in `p1.validate_meter_options()`,
which `build_source()` also calls - one definition, two callers, not two
competing validators. Two transports gained a check they never had: `ha_dsmr`
with only one of its two entities, and `mqtt_p1` with a blank topic, both of
+14 -4
View File
@@ -57,13 +57,20 @@ def load_options() -> dict:
class Controller:
def __init__(self, opts: dict, hass: HomeAssistant, store, mqtt_pub, stop=None):
def __init__(self, opts: dict, hass: HomeAssistant, store, mqtt_pub, *, stop):
self.o = opts
self.hass = hass
self.store = store
self.mqtt = mqtt_pub
# Set by run_control() if the startup gate could not see a conflict
# because the setpoint device had not appeared yet. See run_control().
# ⚠️ REQUIRED, AND KEYWORD-ONLY, AFTER A REVIEW CATCH. This started life
# as `stop=None`, which made a Controller that CANNOT STOP ITSELF the
# default one. On the late-refusal path in run_control() that default
# meant: log the banner, return, and leave the process alive forever
# with no control loop, no exit and no further output - the exact
# "inert but looks healthy" failure this whole module exists to refuse.
# amain() always passed a real Event, so it was latent, but test_p1.py
# was already constructing Controllers without one. No default now, so
# the broken shape does not typecheck.
self.stop_event = stop
self.refused: list[str] | None = None
@@ -325,7 +332,10 @@ class Controller:
refuse(problems)
self.refused = problems
self.log_event("REFUSED: " + problems[0])
if self.stop_event is not None:
# Signal, then return WITHOUT entering the loop. amain() wakes
# on this, runs the normal wind-down (which commands 0 W) and
# re-raises ConfigRefused afterwards, so the exit code is 78 and
# the inverter is left at zero rather than latched.
self.stop_event.set()
return
+104 -10
View File
@@ -15,25 +15,45 @@ told is refused at startup, not survived at runtime.
WHERE THE LINE IS DRAWN, and why it is not further out. A validator that refuses
on trivia gets switched off by the first person it inconveniences, so this one
refuses on exactly three things, all of which share one property: **continuing
makes a safety mechanism inoperative or makes a stated limit untrue.**
refuses only where **continuing produces one of two outcomes:**
1. `max_w` outside the setpoint device's own rating.
(a) **a stated limit is untrue** - the operator configured a bound, a lower
layer silently enforces a different one, and nothing says which won; or
(b) **the add-on is inert and indistinguishable from healthy** - it starts,
serves its UI, reports green, and moves no energy, with no symptom that
separates it from a correctly-idle system.
⚠️ (b) IS NOT A SPECIAL CASE OF (a), and an earlier draft of this file wrongly
implied it was by claiming every refusal here "makes a safety mechanism
inoperative". It does not: when `setpoint_entity` is blank, layer 1 pinning the
inverter at 0 W is the failsafe WORKING. The problem is not that the system
becomes unsafe, it is that it becomes a very convincing impression of a working
controller - and an operator has no way to tell. That is its own reason to
refuse, and stating it as one is what stops the rule being stretched later to
cover mere untidiness.
Both halves have to stay narrow. (a) is not "any two numbers that could
disagree"; it is a bound the operator SET being overridden by a layer they
cannot see. (b) is not "anything degraded"; it is inert AND silent - if a red
NOT READY banner already names the problem, (b) does not apply.
1. `max_w` outside the setpoint device's own rating. [(a)]
The stated limit is untrue. arbiter.py's `supervised` SAFETY claim says the
output is bounded by ±max_w; it is not, it is bounded by the device, and the
two numbers disagree. Which one wins is a coin toss to anyone reading the
config.
2. No `setpoint_entity`.
This is a controller with no actuator, and nothing about it looks broken.
2. No `setpoint_entity`. [(b)]
A controller with no actuator, and nothing about it looks broken.
`write_setpoint()` returns immediately on a blank entity, so: no device
rating is ever read (the `device` SAFETY claim is never made at all), and
the ESP32 heartbeat - the thing that feeds LAYER 1 - never happens. The
add-on serves a UI, publishes MQTT, resolves claims, and moves nothing. It
is fail-safe by accident, not by design, and it is indistinguishable from
working.
add-on serves a UI, publishes MQTT, resolves claims, and moves nothing.
Layer 1 then holds the inverter at 0 W, which is the failsafe working
exactly as designed - this is (b), not (a). Nothing is unsafe; it is simply
impossible to tell from the outside that the thing is doing nothing.
3. A `meter_source` that can never produce a reading.
3. A `meter_source` that can never produce a reading. [(b)]
§5.1 makes P1 the only authoritative measurement and deliberately provides
no fallback, so a transport that cannot be built means `grid` is None
forever: permanent "inputs missing", 0 W, and a status page that reports a
@@ -41,6 +61,19 @@ makes a safety mechanism inoperative or makes a stated limit untrue.**
sent anything to yet. The predicates live in `p1.validate_meter_options()`,
which is also what `build_source()` uses - one definition, two callers.
4. `meter_max_age_s` above the firmware's own ingest veto. [(a)]
The purest example of (a) in the system, and structurally the same fault as
1. The add-on's schema accepts `int(5,300)`. The firmware's threshold is a
COMPILE-TIME SUBSTITUTION - `max_age_s: "30"` in
goodwe-master-stage4-failsafe.yaml - used by both its monotonic receipt
clock and its `ingest_stale` veto, which trips layer 1 on
`p1_age_s >= 30`. Set 120 and the add-on believes a 119 s reading is fresh
and keeps commanding into it, while the firmware vetoed at 30 s and is
holding the inverter at 0 W. Status page: healthy meter, running
controller, nothing moving, and no line anywhere saying the number you set
was overruled. That firmware file's own comment says a lower bound on this
"belongs in CFG-01, not here" - so here it is.
WHAT IS DELIBERATELY *NOT* REFUSED, because it is untidy rather than unsafe:
- `integrator_max_w` above `max_w`. DOCS.md is right that the only thing the
@@ -62,10 +95,29 @@ WHAT IS DELIBERATELY *NOT* REFUSED, because it is untidy rather than unsafe:
import logging
from .p1 import validate_meter_options
from .p1 import is_enabled, validate_meter_options
_LOG = logging.getLogger("goodwe.config")
# ⚠️ A MIRROR OF A FIRMWARE CONSTANT, AND IT CANNOT BE IMPORTED. The firmware
# threshold is a compile-time YAML substitution baked into the ESP32 image
# (`max_age_s: "30"`, master/goodwe-master-stage4-failsafe.yaml), so nothing at
# runtime can ask the board what value it was built with. This number is a copy,
# and a copy of a constant in another repo is a thing that goes stale.
#
# What makes that acceptable here: the copy can only ever be WRONG IN THE SAFE
# DIRECTION for the check below. If the firmware's veto is raised above 30, this
# refuses some configs that would in fact have worked - annoying, visible
# immediately, and fixed by editing one line. It cannot start accepting a config
# the firmware vetoes unless the firmware's number goes DOWN, which would be a
# tightening nobody does silently.
#
# ⚠️ TEL-06 IS EDITING `ingest_stale` DIRECTLY. If that ticket changes what the
# veto MEANS - e.g. thresholding arrival rather than the sensor's value - this
# constant's justification has to be re-read, not just its number. Do not assume
# a matching integer means a matching rule.
FIRMWARE_INGEST_VETO_S = 30.0
# ⚠️ The complete set of option keys through which this add-on can reach an
# actuator. specs §1.5 makes "any configuration in which two writers can reach
# one actuator" a non-goal, and the way that non-goal is ENFORCED here is by
@@ -117,6 +169,21 @@ def validate_startup_config(opts: dict, dev_min=None, dev_max=None) -> list[str]
max_w = _number(opts, "max_w", 2000.0)
if max_w is None:
problems.append(f"max_w {opts.get('max_w')!r} is not a number")
# ⚠️ config.yaml's int(100,5000) already blocks this on a real install, so
# the check is not for the Supervisor path - it is because
# validate_startup_config() is now also sim/inject.py's entry point and can
# be handed any dict at all. A max_w of 0 or below inverts the arbiter's
# `supervised` bounds (lo=-max_w becomes the HIGHER number), and a limit
# claim whose lo exceeds its hi is exactly the contradiction the arbiter
# resolves to 0 W - i.e. it would look like a safety trip rather than the
# nonsense config it is.
elif max_w <= 0:
problems.append(
f"max_w is {max_w:.0f} W and must be positive - it is a magnitude, "
"not a signed setpoint. At or below zero the arbiter's supervised "
f"limit becomes lo={-max_w:.0f} / hi={max_w:.0f}, which is a "
"contradiction it resolves to 0 W, so the controller would look "
"like it was tripping rather than misconfigured.")
elif dev_max is not None and max_w > dev_max:
problems.append(
f"max_w is {max_w:.0f} W but {opts.get('setpoint_entity') or 'the setpoint device'} accepts at "
@@ -144,6 +211,33 @@ def validate_startup_config(opts: dict, dev_min=None, dev_max=None) -> list[str]
else:
problems.extend(validate_meter_options(opts, int(phases), max_age_s))
# --- 4. the staleness window the FIRMWARE will actually enforce -----------
# ⚠️ Only when P1 ingestion is on, and that is a real scope limit rather than
# caution: meter_max_age_s is read by nothing but P1Ingest, and the veto it
# collides with keys off `p1_age_s.has_state()`, which is only ever published
# when ingestion is running (see Controller.publish()). With meter_source off
# there is no sensor, the veto is inert, and the number governs nothing.
#
# Strictly greater, not >=: the firmware trips at `>= 30` and P1Ingest goes
# stale at `> max_age_s`, so 30 against 30 has the firmware fractionally
# stricter by one sample. That is the shipped default and the tested pair.
# BELOW 30 is fine and deliberately not refused - the add-on then gives up
# first, which is fail-safe and visible on its own status page. Only ABOVE is
# the silent case, where the add-on keeps commanding into a reading the board
# has already rejected.
if (is_enabled(opts) and max_age_s is not None
and max_age_s > FIRMWARE_INGEST_VETO_S):
problems.append(
f"meter_max_age_s is {max_age_s:.0f} s but the ESP32 firmware vetoes "
f"any P1 sample at {FIRMWARE_INGEST_VETO_S:.0f} s and forces the "
"layer-1 failsafe - THE FIRMWARE WINS, and it wins silently. This "
f"add-on would treat a {max_age_s - 1:.0f} s reading as fresh and "
"keep commanding, while the inverter sat at 0 W with a healthy-"
"looking meter on the status page. Lower meter_max_age_s to "
f"{FIRMWARE_INGEST_VETO_S:.0f} s or less (30 s is the tested value), "
"or rebuild the firmware with a matching max_age_s and update "
"validate.FIRMWARE_INGEST_VETO_S.")
# --- warnings: real, but not worth refusing over -------------------------
integ = opts.get("integrator_max_w")
integ_w = None if not integ else _number(opts, "integrator_max_w", None)
+16 -5
View File
@@ -1346,6 +1346,17 @@ check("with P1 on the age sensor IS announced",
from app.main import Controller # noqa: E402
def _never():
"""A stop Event these publish-only tests never set.
`stop` is a REQUIRED keyword argument (CFG-01): a Controller that cannot
stop itself used to be the default one, and on the late-refusal path that
meant a live process with no control loop and no exit. These cases only call
publish(), so any Event will do - but they may not skip it.
"""
return asyncio.Event()
class _Store:
data = {}
@@ -1368,14 +1379,14 @@ class _Pub:
pub_off = _Pub()
Controller({"meter_source": "off"}, None, _Store(), pub_off).publish()
Controller({"meter_source": "off"}, None, _Store(), pub_off, stop=_never()).publish()
check("with P1 off, p1_age is absent from the published payload",
"p1_age" not in pub_off.last)
check("...while the normal status keys are still published",
"setpoint" in pub_off.last and "grid" in pub_off.last)
pub_on = _Pub()
Controller({"meter_source": SOURCE_HA}, None, _Store(), pub_on).publish()
Controller({"meter_source": SOURCE_HA}, None, _Store(), pub_on, stop=_never()).publish()
check("with P1 on, p1_age is published", "p1_age" in pub_on.last)
check("...as a number, so has_state() becomes true only once we feed it",
isinstance(pub_on.last["p1_age"], float))
@@ -1384,14 +1395,14 @@ check("...as a number, so has_state() becomes true only once we feed it",
# age sensor is a hard prerequisite for the FW-01 flash, and it has to appear on
# the transport that can actually read the meter in this house.
pub_sig = _Pub()
Controller({"meter_source": SOURCE_HA_SIGNED}, None, _Store(), pub_sig).publish()
Controller({"meter_source": SOURCE_HA_SIGNED}, None, _Store(), pub_sig, stop=_never()).publish()
check("with ha_signed selected, p1_age is published too",
"p1_age" in pub_sig.last and isinstance(pub_sig.last["p1_age"], float))
# ⚠️ And on homewizard_local, where it is the one age FW-01 may actually
# threshold - every other transport's age measures when the VALUE changed.
pub_hw = _Pub()
Controller({"meter_source": SOURCE_HOMEWIZARD}, None, _Store(), pub_hw).publish()
Controller({"meter_source": SOURCE_HOMEWIZARD}, None, _Store(), pub_hw, stop=_never()).publish()
check("with homewizard_local selected, p1_age is published",
"p1_age" in pub_hw.last and isinstance(pub_hw.last["p1_age"], float))
@@ -1421,7 +1432,7 @@ def p1_rows(ctl):
def _fed(source):
ctl = Controller({"meter_source": source}, None, _Store(), _Pub())
ctl = Controller({"meter_source": source}, None, _Store(), _Pub(), stop=_never())
ctl.p1.submit(make_sample(source, 350.0, 0.0, phases=1,
ingest_mono=time.monotonic()))
return ctl
+149 -1
View File
@@ -7,10 +7,12 @@ a validator dies is not by missing a fault, it is by refusing something harmless
until somebody deletes the call.
"""
import asyncio
import sys
from app.validate import (
ACTUATOR_WRITE_KEYS, ConfigRefused, refuse, validate_startup_config,
ACTUATOR_WRITE_KEYS, FIRMWARE_INGEST_VETO_S, ConfigRefused, refuse,
validate_startup_config,
)
fails = []
@@ -120,6 +122,47 @@ check("a misspelt meter_source is refused rather than silently ignored",
why(validate_startup_config(base(meter_source="ha_signd"), -5000, 5000),
"is not one of"))
# --------------------------------------------------------------------------- #
print("4. meter_max_age_s against the firmware's compile-time veto")
# ⚠️ The schema allows int(5,300); the firmware's threshold is baked in at 30 s
# and wins silently. Same shape as the max_w case: a configured bound overridden
# by a lower layer, with nothing saying so.
hw = dict(meter_source="homewizard_local", p1_host="m")
p = validate_startup_config(base(**hw, meter_max_age_s=120), -5000, 5000)
check("a meter_max_age_s above the firmware veto is refused", len(p) == 1)
check("...naming the configured value", why(p, "120"))
check("...naming the firmware's value", why(p, "30"))
check("...and saying which one wins", why(p, "THE FIRMWARE WINS"))
check("the tested pair 30/30 is accepted",
validate_startup_config(base(**hw, meter_max_age_s=30), -5000, 5000) == [])
check("one second above it is refused",
validate_startup_config(base(**hw, meter_max_age_s=31), -5000, 5000) != [])
# Below the veto the add-on gives up FIRST, which is fail-safe and visible on
# its own status page. Only above is the silent case.
check("below the veto is fine - the add-on being stricter is not a conflict",
validate_startup_config(base(**hw, meter_max_age_s=10,
meter_poll_s=4), -5000, 5000) == [])
# ⚠️ Scope: meter_max_age_s is read by nothing but P1Ingest, and the veto keys
# off a sensor only published when ingestion runs. With the meter off it governs
# nothing, so refusing would be pure trivia.
check("with meter_source off the number governs nothing and is not refused",
validate_startup_config(base(meter_source="off", meter_max_age_s=300),
-5000, 5000) == [])
check("the constant is the firmware's, not a rounded guess",
FIRMWARE_INGEST_VETO_S == 30.0)
# --------------------------------------------------------------------------- #
print("max_w must be a positive magnitude")
# Schema-blocked on a real install, but validate_startup_config() is also
# sim/inject.py's entry point and can be handed any dict at all.
for bad in (0, -1, -2000):
p = validate_startup_config(base(max_w=bad), -5000, 5000)
check(f"max_w {bad} is refused", len(p) == 1 and why(p, "must be positive"))
check("...and the message explains it would read as a trip, not a mistake",
why(validate_startup_config(base(max_w=0), -5000, 5000), "contradiction"))
check("the smallest sane max_w still starts",
validate_startup_config(base(max_w=1), -5000, 5000) == [])
# --------------------------------------------------------------------------- #
print("what must NOT be refused - a validator that fires on trivia gets deleted")
# DOCS.md: the arbiter's `supervised` limit still binds the wire to +-max_w, so
@@ -153,6 +196,111 @@ err = ConfigRefused(p)
check("ConfigRefused carries every problem", err.problems == p)
check("...and str() names one of them", str(err) == p[0])
# --------------------------------------------------------------------------- #
print("the LATE refusal, when the device only shows up after the gate has run")
# ⚠️ This path had no test at all and no live demonstration - the review's
# catch. ESPHome is routinely not up when the add-on boots, so hass.limits()
# returns (None, None), the range checks are skipped, and run_control() is the
# first place the device's real rating is ever known. Everything below is about
# what happens when it turns out to conflict.
from app.main import Controller # noqa: E402
class _LateHass:
"""Reports the range only run_control() gets to see."""
def __init__(self, lo, hi):
self.lo, self.hi = lo, hi
self.writes = []
async def limits(self, entity):
return (self.lo, self.hi, 1.0)
async def number(self, *a, **k):
return 0.0
async def set_number(self, entity, value):
self.writes.append(value)
return True
class _Store2:
data = {}
def set(self, *a):
pass
class _Pub2:
enabled = False
def publish(self, *a, **k):
pass
def close(self):
pass
def late(opts_over, lo, hi):
"""Drive run_control() against a device that only reports (lo, hi) now.
⚠️ Returns whether run_control() EXITED ON ITS OWN. That is the assertion
that matters: on a refusal it must return without entering the while loop,
and on a clean config it must not return at all. So the clean case is stopped
from outside after it has had time to write, rather than waited on - a
wait_for() here would just time out, which is the correct behaviour dressed
up as a failure.
"""
async def go():
stop = asyncio.Event()
hass = _LateHass(lo, hi)
# A device narrower than the shipped 5000 W schema ceiling is exactly
# the case that cannot be reached through the Supervisor on the live
# install, so it is reached here instead.
c = Controller(base(**opts_over), hass, _Store2(), _Pub2(), stop=stop)
c.auto = True
task = asyncio.create_task(c.run_control())
for _ in range(30): # up to ~3 s
if task.done():
break
await asyncio.sleep(0.1)
exited = task.done()
if not exited:
c.stopping = True
await asyncio.wait_for(task, timeout=5)
return c, stop, hass, exited
return asyncio.run(go())
c, stop, hass, exited = late({"max_w": 5000}, -3600.0, 3600.0)
check("a device narrower than max_w, discovered late, is refused",
c.refused is not None and len(c.refused) == 1)
check("...naming both values", why(c.refused, "5000") and why(c.refused, "3600"))
check("...signalling amain to wind down", stop.is_set())
check("...and returning instead of looping forever", exited)
# The whole point: run_control() must not fall through into the while loop. A
# single write here would mean it commanded the inverter under a config it had
# just declared unusable.
check("...having never entered the control loop, so it wrote nothing",
hass.writes == [])
check("...and it is recorded in the event log an operator reads",
any("REFUSED" in e for e in c.events))
# The same path when there is no conflict: it must NOT refuse, and it must
# actually regulate - asserted by a write reaching the device, not by absence.
c2, stop2, hass2, exited2 = late({"max_w": 2000}, -5000.0, 5000.0)
check("a late device that agrees does not trip the re-check", c2.refused is None)
check("...and the control loop runs, writing to the device", hass2.writes != [])
check("...and does not signal a shutdown", not stop2.is_set() and not exited2)
# ⚠️ THE FOOTGUN THE REVIEW FOUND. `stop` used to default to None, so this
# construction was legal and the refusal path then returned into a live process
# with no control loop, no exit and no further output.
try:
Controller(base(), _LateHass(-5000.0, 5000.0), _Store2(), _Pub2())
check("a Controller with no stop Event is rejected at construction", False)
except TypeError:
check("a Controller with no stop Event is rejected at construction", True)
# --------------------------------------------------------------------------- #
print()
if fails: