Every HA notification the add-on raises now has a title of at most 5 everyday words and a one-sentence body; a red alarm may use three so no action is lost. The texts live in app/messages.py, the rule in STYLE.md, and the detail that moved out in DOCS.md "Notifications", which each body links to. No notification_id, trigger or cadence changed. test_messages.py enforces the rule on every notification, fails any notification worded outside app/messages.py, and ratchets the kinds not yet rewritten (rows, banners, refusals, logs, options) through a shrinking allowlist of 200. Six tests re-pinned from prose to meaning. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01LyR88rXETvwhTgx6yHE39p
This commit is contained in:
co-authored by
Claude Opus 5.5
parent
2503de124e
commit
50ccea3dd7
@@ -2802,6 +2802,119 @@ it.
|
||||
| `estop_fitted` | Whether the RS485 e-stop is installed. Drives the warning banner |
|
||||
| `log_level` | `trace`/`debug`/`info`/`warning`/`error` |
|
||||
|
||||
## Notifications
|
||||
|
||||
Each Home Assistant notification this add-on raises has a short title, one
|
||||
sentence (a red alarm may use three), and a **Details** link to the add-on
|
||||
documentation that names the section below. This section holds what the
|
||||
notification leaves out. The wording rule is `STYLE.md` in the repository; the
|
||||
texts live in `app/messages.py`. Every notification keeps a fixed
|
||||
`notification_id`, so a repeat replaces the card instead of adding one.
|
||||
|
||||
| Title | Severity | id |
|
||||
|---|---|---|
|
||||
| Battery is not keeping up | warning | `goodwe_integrator_bound` |
|
||||
| Power request too high | alarm | `goodwe_output_clamp` |
|
||||
| Load too high for battery | alarm | `goodwe_peak_saturated` |
|
||||
| Battery at its peak reserve | alarm | `goodwe_peak_soc_floor` |
|
||||
| Inverters working against each other | alarm | `goodwe_circulating_power` |
|
||||
| *name* is not delivering | alarm | `goodwe_not_delivering_<name>` |
|
||||
| Meter reading may be stuck | alarm | `goodwe_meter_frozen` |
|
||||
|
||||
### Battery is not keeping up
|
||||
|
||||
The grid-following loop's integrator reached its anti-windup bound
|
||||
(`integrator_max_w`): the controller has been asking for more than the battery
|
||||
delivers for a while. This is SAFETY-40, and it is **not** a fault. No command
|
||||
went over the rating and control keeps running. Short spells after a big load
|
||||
or solar step are normal. If it keeps coming back, check that the battery
|
||||
follows its commands. The bound and the command of that tick are in the add-on
|
||||
log (WARNING, reason code `OUTPUT_CLAMP`). See *The winding-loop alarm* for the
|
||||
full story.
|
||||
|
||||
### Power request too high
|
||||
|
||||
The controller computed a command above a limit, and the command was cut to that
|
||||
limit before it was written. The notification names what was asked, what was
|
||||
sent, and which limit cut it: the configured inverter rating (`max_w`), the
|
||||
inverter's own limit (the setpoint device's range), or the inverter rating on
|
||||
the loop side. Asked always comes first. This is a **software fault** (the old
|
||||
wording was "BUG SIGNAL"). It is not the inverter failing to follow a legal
|
||||
command, which is the saturation freeze and does not alarm. Control keeps
|
||||
running. Report it with the add-on log, whose ERROR line carries the reason code
|
||||
`OUTPUT_CLAMP` and the full figures. See *The winding-loop alarm*.
|
||||
|
||||
### Load too high for battery
|
||||
|
||||
The capacity-peak guard (SAFETY-07) is asking for everything the inverter can
|
||||
discharge, and the running 15-minute average is still projected over the peak
|
||||
limit. That 15-minute period will set or raise the month's billed peak
|
||||
(capaciteitstarief). The controller is not at fault: the house load is larger
|
||||
than the inverter. Switching off load in the next few minutes is the only thing
|
||||
that still changes the bill. The projection and the watts are in the add-on log
|
||||
and on the status page. See *The capacity-peak guard*.
|
||||
|
||||
### Battery at its peak reserve
|
||||
|
||||
The peak guard wanted to discharge to hold the 15-minute peak, but it may not go
|
||||
below the peak reserve (`peak_soc_floor`, SAFETY-24). It also stops when the
|
||||
battery level cannot be read, or when no reserve is set. So this 15-minute
|
||||
period will go over the peak limit and set or raise the month's billed peak.
|
||||
Charging from the grid stays blocked meanwhile. On a site with several inverters
|
||||
the notification names the battery at its limit (SAFETY-32): each battery is
|
||||
graded against its own cut-out level (`bms_soc_floor`), and raising the other
|
||||
batteries' settings will not change this one.
|
||||
|
||||
⚠️ **The reserve binds the peak guard only (SAFETY-25).** It is not a
|
||||
whole-battery reserve. Ordinary self-consumption has no such floor and goes on
|
||||
discharging below it, down to the battery's own cut-out level. See *What
|
||||
`peak_soc_floor` does not protect*.
|
||||
|
||||
### Inverters working against each other
|
||||
|
||||
Two inverters were pushing power into each other: one discharging while another
|
||||
charged (SAFETY-31). **The meter cannot see this.** The two flows cancel at the
|
||||
P1 meter, so the site reads idle while both batteries cycle through two
|
||||
conversion stages. Every other guard reads that net figure, so none of them
|
||||
fires. The add-on has **stopped control and commands 0 W on every inverter**.
|
||||
If the grid reading does not move after that, one inverter is no longer
|
||||
listening to the add-on; this has happened on this hardware, once for
|
||||
6 h 25 min. Switch the inverters off at the isolator. The alarm is latched: a
|
||||
Home Assistant or add-on restart does not clear it, and the card is raised
|
||||
again every 5 min until you start control on the add-on page. The watts and the time
|
||||
window are in the add-on log and on the status page. See *The circulating-power
|
||||
alarm*.
|
||||
|
||||
### An inverter is not delivering
|
||||
|
||||
One inverter has stood well short of its share of the site target for longer
|
||||
than the hold time (SAFETY-42), while the others have not. No other check sees
|
||||
this. A unit at 0 W is absent rather than pushing the wrong way, so the per-unit
|
||||
sign check and the circulation check stay quiet. **Nothing is commanded
|
||||
differently.** The guard only reports: commanding an inverter that has stopped
|
||||
listening achieves nothing, and the only fallback the add-on has is
|
||||
all-or-nothing. The other inverters keep regulating, and the site is short by up
|
||||
to the missing unit's rating. Check, in this order:
|
||||
|
||||
1. Is the inverter answering on RS485 at all?
|
||||
2. Is its battery colder or emptier than its configured cut-out level
|
||||
(`bms_soc_floor`) says? If so, that setting does not describe this battery.
|
||||
3. Is anything else writing to it?
|
||||
|
||||
The alarm is latched and survives restarts; start control on the add-on page
|
||||
once you know why. See *A unit that stops DELIVERING is a third fault again*.
|
||||
|
||||
### Meter reading may be stuck
|
||||
|
||||
The meter keeps answering, but its value has not changed for longer than the
|
||||
hold time while the command stands at the power limit (SAFETY-18). The loop is
|
||||
regulating against a number that has stopped moving. The age is still fresh, so
|
||||
no other guard stops it. This is an alarm only: control keeps running and keeps
|
||||
following the reading. Held for a whole 15-minute period, it can set the month's
|
||||
billed peak. Check the meter; if it is stuck, stop control on the add-on page.
|
||||
The limit and command figures are in the add-on log and on the status page. See
|
||||
*The frozen-meter alarm*.
|
||||
|
||||