SAFETY-57: the stale-reading verdict gets an exit, because its own consequence is what stopped it being tested
checks / unit (pull_request) Successful in 7m58s

SAFETY-37's freshness gate reports a battery-power register as MISSING when it
stops following its own command, and a missing input is "command 0 W and keep
commanding" (§11.1 rule 1). The gate's only exit was "an arrival carrying a
DIFFERENT number" - and at 0 W nothing is asking the register to be anywhere.
The state had no exit reachable from inside it, and the log line promised the
opposite in the same sentence that announced the 0 W.

REPRODUCED FROM THE WIRE, NOT MODELLED. scenarios/safety57-2026-09-21/ is 3840
verbatim frames off the RS-485 pair, read from the passive sniffer, decoded by
tools/decode_bus_capture.py (0 unparsed, 0 bad CRC, 0 unknown shapes; the
mode->sign convention is graded off the capture, not trusted). The box was
running 0.10.0, so the 0 W in the trace IS the add-on's own claim:

  10:51:24.7  0x0518 reaches -3 W. Pack at 11 %, the BMS refuses the discharge,
              the inverter idles. THE REGISTER IS HEALTHY AND TRUTHFUL.
  10:51:29.7  the command reaches +1060 W - 800 W of travel
  10:52:00    the conjunction arms. Inverter.batt becomes None
  10:52:21.7  the site commands 0 W, on the wire
  ...         0x0518 does not change value for 850.0 s. The setpoint does not
              change value for 790.0 s. The house exports 2.4 kW throughout
  ~11:04      a human restarts the add-on. That is what ends it

AND IT HAD BEEN ESCAPING BY LUCK. Replaying the committed 16-day loop capture
through the shipped conjunction finds 93 trips whose wait for the BMS
keep-alive pulse that cleared them has a median of 143.4 s, a worst case of
21440.1 s, and 17 of 93 at or beyond this episode's 710 s. That distribution
belongs to the battery's firmware, not to this code.

THE CARD'S OPTION 2 ALREADY HELD AND IS NOT THE BUG. _grade() has required
|standing| >= MOVE_W since SAFETY-37. The trip was at +1060 W and the stuck
state is at 0 W; they are different moments, and an entry-side rule cannot
reach a state entered legitimately and then persisted. Nothing in the
conjunction is weakened here.

THE RULE, SAFETY-13's SHAPE ONE MODULE OVER - which latches get an exit, not
how long the block lasts:

  the verdict is withdrawn when the obligation that produced it has been gone
  for RELEASE_S, and the register is then re-graded from scratch.

RELEASE_S is BATT_OBLIGED_S, 17.0 s - the obligation window already derived in
the file (6.0 plant + 10.0 publish + 1.0 read), taken at the FLOOR of its band
for the mirror of MOVE_W's reason. Which half is safe is the opposite of
SAFETY-13's: being wrong long is the failure being fixed, being wrong short
costs one bounded re-grading window. Below 17 s the release pre-empts the
cheaper exit - the register answering by itself - and that is graded
behaviourally, not asserted.

The whole parked interval is now stale_input_s + RELEASE_S = 32 s. On the live
episode: telemetry back at 10:52:39 instead of 11:05:35, with 0x0518 still
answering the same -3 W. RED BEFORE (release_s=inf, a graded counterfactual and
not a second implementation), GREEN AFTER.

WHAT IT COSTS, AND IT IS NOT SMALL. A register dead for good is re-graded for
ever: over 1201 reads the held number reaches a consumer on 630 (52.5 %)
against 35 (2.9 %) before. Payable only because one window is at most 35 s and
the two consumers hold for 75 s and 85 s, so neither can reach a verdict inside
one and the re-trip clears both windows. No detection SAFETY-37 had is given
back - a permanent None clears the same windows for ever too - and the command
is derived from the P1 meter, never from batt.

Two clocks, deliberately: changed_mono/unchanged_s() stay facts about the
REGISTER, graded_from/graded_s() are the VERDICT's window. Collapsing them
either lies to the operator or defeats the re-grading.

main.py's stale line had its ESCAPE CLAUSE corrected - it promised a clearance
the state could not produce - and gained a STALE WITHDRAWN edge that says in
its own words that nothing has been learned about the register. The DIAGNOSIS
half is SAFETY-56's and is deliberately untouched, with a named check asserting
it is still there so that rewrite has to be deliberate.

Battery: 22 mutations, 21 red, 1 argued equivalent, 0 unexplained survivors.
Two findings kept in DECISIONS: _release()'s move_w test swapped for
unchanged_s SURVIVED at +5 B because every fixture rested at exactly 0 W (habit
11, closed by a 0/100/300 W fixture); and the code shipped a habit-22 comment
claiming the _release/_grade order was load-bearing, which the battery
falsified - the two act on mutually exclusive predicates, so the order is not
observable. MUTATION.md gains habit 23 for a mutation that ran, fingerprinted
clean, and was a no-op on the fixture because `0.0 or x` is x.

Suite: 30/30 in the CI image, checks.yml's exact command, purged tree, :ro, one
file at a time.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
This commit is contained in:
2026-09-21 12:33:56 +02:00
co-authored by Claude Opus 5
parent 6f5e8e378a
commit 43c144b8d9
10 changed files with 1921 additions and 37 deletions
+29
View File
@@ -526,6 +526,35 @@ next 10 s publish. There is **no option to configure**: the 35 s is derived from
the ESPHome publish interval and the two watchdog windows it has to stay inside,
and the add-on's own checks refuse a value that does not.
⚠️ **AND IF THE REGISTER DOES NOT REPORT A DIFFERENT VALUE, THE ADD-ON STOPS
WAITING AFTER 17 s (SAFETY-57).** This paragraph used to end at the sentence
above, and on 2026-09-21 that turned out to be a promise the state could not
keep: at 0 W **nothing is asking the register to be anywhere**, so "report a
different value" is evidence a parked site cannot ask for. The live site sat at
0 W for **790 s** while the house exported 2.4 kW, on a register that was
working perfectly — the pack was simply at its floor and the BMS was refusing
the discharge — and it was freed by a person restarting the add-on.
So: once the standing command has been **under 250 W for 17 s**, the verdict is
**withdrawn** and the register is graded again from scratch over a fresh 35 s.
The whole parked interval is now `stale_input_s` + 17 s — **32 s at the
defaults** — and it does not depend on what the battery decides to do.
| in the action log | what it means | what to do |
|---|---|---|
| `STALE <unit>` alone, then nothing | the register stopped following and has not come back | look at the unit — comms, the ESP32, the inverter |
| `STALE <unit>` then `STALE WITHDRAWN <unit>`, **once** | the pack was probably empty or full and the BMS refused the command. The site has resumed | nothing |
| the pair repeating every ~70 s | the register really is not following, and the add-on is re-testing it | look at the unit; the site is regulating on the meter in between |
⚠️ **`STALE WITHDRAWN` IS NOT "RECOVERED", AND THE LOG LINE SAYS SO ITSELF.**
Nothing has been learned about the register when it is printed; the verdict is
withdrawn because it can no longer be *tested*, and the next 35 s are the test.
During those 35 s the held number reaches the site's telemetry again. That is
deliberate and it is bounded: 35 s is shorter than both the circulating-power
hold (75 s) and the per-unit sign hold (85 s), so neither of those alarms can be
made to say anything by a held number, and the command itself is derived from
the **meter**, never from this register.
⚠️ **What this does NOT catch: a register whose value is WRONG rather than
STOPPED**, including a dead publisher whose last two samples happen to
alternate. Detecting that needs an arrival stamp inside the ESP32 firmware