At N>=2 a cheap-window maintenance charge files a site `hi` (`charge`,
P_MAINT_SHAPE) equal to what the charging pack's own `hi` places, so the
other pack never has to give against it. The charge is sized to the
quarter's headroom under the peak aim so it yields to the peak guard, and
to 0 W under a site safety stop. N=1 byte-identical (safety84_identity).

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
This commit is contained in:
glenn schrooyen
2026-09-30 19:47:15 +02:00
co-authored by Claude Opus 5.5
parent 9d5b7d129a
commit 43a52e7f60
12 changed files with 709 additions and 17 deletions
@@ -40,4 +40,4 @@ direction. Opposite splits stay forbidden.
- At N=2 a maintenance CHARGE in a cheap window has the same stall: the
charging pack's `hi = -floor` against the loop asking the other to give is
refused on 141 of 261 cycles. The mirror fix is a site `hi`, which can meet
the peak floor's `lo` (0 W), so it is not this card.
the peak floor's `lo` (0 W), so it is not this card. Fixed by [[SAFETY-84]].
@@ -0,0 +1,46 @@
# SAFETY-84 - a maintenance charge at two inverters
**Status: DECIDED 2026-09-30.** Follows SAFETY-78's "Not changed" list.
Tests: `test_safety84.py`; identity: `tools/safety84_identity.py`.
**The defect.** In a cheap window the charging pack files its own
`hi = -charge` (P_MAINT_SHAPE). At N>=2 the loop's site target sat above it
(a house to cover, or its 400 W slew step from 0 W), so the other pack had to
give while this one charged. The allocator refuses opposite directions
(SAFETY-31), so the site sat at 0 W whatever the house
(`tools/safety84_identity.py` on 9d5b7d1: 436 of 480 cycles refused). N=1
was fine.
**The fix.**
- While a pack's own limits make it charge at N>=2, `main.py` files a site
limit `charge`, `hi` = what that pack's own `hi` places
(`allocator.hi_w()`, whole W as the allocator rounds). The site target is
never above it, so the other pack only adds power in the same direction.
Opposite splits stay forbidden. Mirror of SAFETY-78's `drain` floor.
- Peak guard first (owner order, SAFETY-83). The charge is sized to the
quarter's headroom under the aim (`charge_headroom_w()`, cap or banked peak
minus `peak_margin_w`), so it charges less instead of stopping: the meter
sits on the aim and the guard does not need to step in. Where the house
alone is over the aim the guard engages, the shaping is suspended as before
(`shaping_suspended()`) and no `charge` is filed, so the guard's `lo` and
this `hi` never meet in one cycle (no `lo > hi`, no park at 0 W).
Without the headroom sizing the aim still held (the suspension did it), but
a battery gave power back on 285 of 540 cycles at a 3000 W house
(test_safety84.py part 2).
- A site stop (a safety SET above P_MAINT_SHAPE) sizes the charge to 0 W:
the unit `hi` is a hard limit, so a charge under a 0 W stop needs the other
pack to give. It was refused, with an ARBITER line, on most cycles of the
stop (test_safety84.py part 4). The stop still parked the site at 0 W.
- A pack that cannot take the charge (a refusal, a full pack, a stale link)
files no ceiling; the other pack follows the loop.
- Not filed at N=1: byte-identical (`tools/safety84_identity.py`, which hashes
every claim, in and out of a cheap window and under a banked peak).
**Not changed.**
- At N=1 the charge is not sized to the headroom: the guard still suspends it
and the battery gives until the quarter is safe. The same sizing would fit
there; that is an owner question, not this fix.
- Outside a cheap window (`hi = 0`, solar only) nothing is filed, at any N.
- A HOLD (SAFETY-86) and the "Battery is not keeping up" alarm (SAFETY-85)
are untouched. In the identity runs that alarm's log line comes as often at
N=2 as at N=1 (2 in 480 cycles).