EV-10 round 3: grade the floor case on the same landing with and without the car; per-quarter latches independent of the cover option; stricter write-mute test
Co-Authored-By: Claude <noreply@anthropic.com>
This commit is contained in:
@@ -86,18 +86,21 @@ up to 1.8 kW; the 40 Wh floor fixes that.)
|
||||
|
||||
## EV-10, EV-11, EV-12: the rig's three findings (EV-04 test F-1 to F-3)
|
||||
|
||||
- **The car is the cause when the alarm's own test says so** (EV-10).
|
||||
`car_cycle` (`_car_explains_alarm`) grades the alarm's test on the period as it
|
||||
is and on the period without the car's fresh, corroborated average
|
||||
(`car_exclude`): the car explains the alarm only if the test is true with it
|
||||
and false without it. The test is the alarm's own landing (`_car_grade`: the
|
||||
batteries give only what they still can, `load_too_high` for a saturated guard
|
||||
and for a floor with other batteries, `misses_aim` for a floor with none), not
|
||||
the plain projection, which still counts the batteries' help. So the car alone
|
||||
taking the batteries to the reserve is silent (rig: 5888 W against 6000 W),
|
||||
while a house-caused drain with a small car still alarms. No minimum car power
|
||||
is needed: a car that changes nothing cannot flip the test. A stale, stuck or
|
||||
uncorroborated figure is `None` and the normal alarms stand.
|
||||
- **The car is the cause when the alarm's own test says so, on the same
|
||||
landing** (EV-10). `car_cycle` (`_car_explains_alarm`) runs the alarm's test on
|
||||
the period as it is and on the period without the car's fresh, corroborated
|
||||
average (`car_exclude`): the car explains the alarm only if it is true with the
|
||||
car and false without it. A saturated guard, and a floor with other batteries
|
||||
left, use `load_too_high` on the landing (the batteries give only what they
|
||||
still can). A floor that leaves nothing uses SAFETY-126's `misses_aim` (the
|
||||
batteries at 0 W from now on), which is latched for the quarter; the add-on keeps
|
||||
that latch twice, with and without the car, from the same readings. Both reset
|
||||
at a new quarter and when the guard stops wanting power, and they run every
|
||||
cycle, so the cover option does not touch them. This holds with the projection
|
||||
still under the aim (rig: 5888 W against 6000 W). A car of 0 W makes the two the
|
||||
same, so it explains nothing; a stale, stuck or uncorroborated figure is `None`,
|
||||
sets the latch without the car, and the normal alarms stand. There is no minimum
|
||||
car power: the comparison itself is what separates car from house.
|
||||
- **Steady row, no hold on the alarm** (EV-11). Cause: after the car's own quarter
|
||||
became the month peak, the aim sat on the grid it made (14.04 kW +-40 W), so
|
||||
the test crossed the aim every few seconds. `car_over` (row, card, notice) now
|
||||
|
||||