SAFETY-52: a battery that refuses is asked for 0 W, with a 200 W probe every 15 min
At the BMS cut-out the saturation freeze held the last request for hours (+5000 W for 11.87 h on 09-06, +1940 W for 3 h 55 m on 09-19) until the grid error changed sign. compute() now carries a refused direction: after SETTLE_CYCLES of a ~0 W reading against a larger ask it holds that direction at 0 W, probes 200 W (below the gate's 250 W) every 15 minutes, and lets go on charge, an answered probe, stop/start or another writer. A stale-reading trip on a frozen ~0 W reading seeds the same hold, which ends SAFETY-59's ~70 s cycle. One inverter only; no SoC in the loop (SAFETY-25 Option A). test_refusal.py drives the real Controller and gate; tools/replay_refusal.py replays the 16-day capture. test_clamp.py and test_delivery.py re-baselined where they asserted the old hold. DECISIONS/SAFETY-52 has the record and what SAFETY-58/59 must take into account. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
This commit is contained in:
co-authored by
Claude Opus 5.5
parent
d1f7e3336e
commit
1f97c7652f
@@ -526,7 +526,7 @@ accumulator is doing:
|
||||
| `Loop integrator lead` | W | that value minus **the command it was computed against**, i.e. the command the previous cycle left standing |
|
||||
| `Loop reason` | — | the law's own word for this cycle |
|
||||
|
||||
`Loop reason` takes one of eight values:
|
||||
`Loop reason` takes one of ten values:
|
||||
|
||||
| value | what happened |
|
||||
|---|---|
|
||||
@@ -538,6 +538,21 @@ accumulator is doing:
|
||||
| `saturated-freeze` | the inverter is not following, so the command's magnitude may fall but not rise |
|
||||
| `freeze-released` | the freeze had run out of plant-shaped explanations and the command was let move again |
|
||||
| `not-running` | control is stopped **and** shadow mode is off, so the loop did not run |
|
||||
| `battery refuses` | the battery gave nothing for a minute while asked for more than 500 W, so the add-on asks 0 W in that direction (see below) |
|
||||
| `battery probe` | the add-on asks 200 W to test whether a refusing battery gives power again |
|
||||
|
||||
**When the battery refuses.** At its cut-out level the battery gives nothing,
|
||||
whatever it is asked. The add-on then asks 0 W instead of repeating its last
|
||||
request, and the `Why` row reads *The battery refuses to give power: 0 W*. Every
|
||||
15 minutes it asks 200 W for about half a minute; if the battery answers,
|
||||
control resumes. It also resumes when the grid needs charging instead, and when
|
||||
control is stopped or started. 200 W is below the 250 W the stale-reading check
|
||||
needs, so a test never trips it. One inverter only: with several, the battery
|
||||
level limit already moves an empty battery's share to the others.
|
||||
|
||||
*For installers:* SAFETY-52. The event log reads `BATTERY REFUSES …` and
|
||||
`BATTERY REFUSES ENDED: …`, and the INFO line ends in `BATTERY_REFUSES`.
|
||||
`DECISIONS/SAFETY-52-a-battery-that-refuses.md` has the replay figures.
|
||||
|
||||
⚠️ **`Loop reason` is not the `Why` row on the status page, and the two will
|
||||
often disagree.** `Why` is the *arbiter's* answer in words — *Keeping the grid
|
||||
|
||||