MAINT-05: one recalibration per pack, and only one pack moves power at a time
checks / unit (pull_request) Successful in 4m48s
checks / unit (pull_request) Successful in 4m48s
§12's monthly cycle drains a pack to empty and refills it to true its coulomb
counter. There was exactly one `Maintenance` and one un-namespaced history, so
at two packs only the first was ever recalibrated - and nothing prevented the
cycle draining pack A while the loop charged pack B, which is two power-moving
phases on one grid connection pulling against each other.
* ONE `Maintenance` PER ROSTER ENTRY, each with its own schedule, phase and
history under `unit/<name>/...`. `store.migrate_maint_keys()` moves an
install's flat history into the first pack's namespace under
`migrate_unit_keys()`'s three rules - shared in code via `_move_flat_keys()`
and `_verify_moves()`, not restated - on its own marker, because unlike
DEV-02's it runs only where the roster has more than one pack. The flat keys
are kept LIVE as the rollback view.
* ONE MAINTENANCE SLOT PER SITE (`maintenance.arbitrate()`). At most one pack
in a power-moving phase - drain, charge AND hold. The holder is DERIVED from
the packs' own stored phases, never persisted, so a restart mid-drain
re-derives it. Several packs due in the same hour: the slot goes to the one
that has gone longest without a completed cycle; roster order breaks a
numeric tie and nothing else. Nothing preempts a cycle in flight.
* THE DEFERRED PACK IS NOT STARVED AND IS NOT A FAULT. A deferral does not
stamp `last_start_attempt` and does not move the phase, so neither the 12 h
drain nor the 36 h charge timeout is reachable by waiting.
* The claim is filed on the pack whose state machine produced it, and stays
SCOPE_UNIT - ARCH-01's rule.
* `validate.py` rule 6 grades `maintenance_charge_w` against the WEAKEST cap on
the roster now, as its own comment said it must once `maint_unit` stopped
being `inverters[0]`.
* At a roster of one nothing changes, and it is asserted: no new store key, the
migration does not run, the four cycle events are the shipped strings, the
banner is the bare phase.
* RECORDED NOT FIXED: a drain pins its pack while the loop's target is a site
claim, so below the pin the allocator refuses the split and the site parks at
0 W. Pre-existing at 2d025ee. Pinned as a running check.
Verified: 19/19 suites green in the CI image; 17 mutations run through
tools/mutation_run.sh (bytecode purged), every one observed red.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
This commit is contained in:
@@ -0,0 +1,182 @@
|
||||
# MAINT-05 — one recalibration per pack, one at a time, and what the card left open
|
||||
|
||||
**Status: DECIDED 2026-09-04.** There is one `Maintenance` per roster entry,
|
||||
each with its own schedule, phase and history. The site holds exactly **one
|
||||
maintenance slot**: at most one pack may be in a power-moving phase, the slot is
|
||||
derived from the packs' own stored phases rather than persisted separately, and
|
||||
when several packs are due in the same hour it goes to the one that has gone
|
||||
**longest without a completed cycle**. The schedule is **not** staggered by
|
||||
construction — the interlock defers, and the stagger emerges from it.
|
||||
|
||||
Filed with MAINT-05. Card `6a9a9e8503872905f298d80a`.
|
||||
|
||||
---
|
||||
|
||||
## 0. What the card asked to be decided, and the answers
|
||||
|
||||
| the card's open question | the decision |
|
||||
|---|---|
|
||||
| §2 the arbitration | **one pack at a time; the other stays under the loop.** Nothing preempts a cycle in flight. |
|
||||
| §2 who wins when several are due | **the longest-waiting pack**, `last_completed` oldest first, `inf` for never-recalibrated. Roster order breaks a numeric tie and nothing else. |
|
||||
| §4 staggering | **not by construction.** The interlock defers the second pack; the stagger is what comes out of it. §3 below. |
|
||||
| AC 7 rule 6's `maint_unit` comment | **no, the first entry's cap is no longer right.** It grades against the weakest cap on the roster now, like rule 5. §4 below. |
|
||||
| the store layout at N=1 | **flat, unchanged.** The namespace appears the day the roster grows. §2 below. |
|
||||
|
||||
## 1. Why the slot is derived and not persisted
|
||||
|
||||
The holder is *"whichever pack's stored phase is not `idle`"* — a fact already on
|
||||
disk, written by the packs themselves in the per-pack history this card
|
||||
introduces. A `maint_slot_holder` key would be a **second opinion about the same
|
||||
thing**, and the two would disagree the first time the add-on was killed between
|
||||
writing the phase and writing the holder. Derived, a controller that comes back
|
||||
up mid-drain reads the drain and re-derives the holder from it; there is no
|
||||
recovery path to get wrong because there is no second fact.
|
||||
|
||||
`CHARGE` is in `POWER_MOVING` even though the control **loop** owns the setpoint
|
||||
in that phase, and that is the decision most likely to be "simplified" later.
|
||||
Pack A charging from the grid at 2000 W while pack B drains 2000 W to export is
|
||||
4 kW going round in a circle with the meter reading zero and both packs
|
||||
believing they are behaving — the circulating power [[SAFETY-31]] exists to
|
||||
detect, arriving as something this module can simply not do. `HOLD` is in the
|
||||
tuple for the other half of the sentence: it moves nothing, and it **owns the
|
||||
actuator**, so a second cycle starting under it would still be two
|
||||
recalibrations at once.
|
||||
|
||||
## 2. Why the store layout at a roster of one does not change
|
||||
|
||||
The maintenance keys are flat — `phase`, `phase_started`, `last_completed`,
|
||||
`last_start_attempt` — on every install since the add-on shipped. At one pack
|
||||
there is nothing for a namespace to distinguish that pack **from**: §6.2's
|
||||
identity, the same one `arbiter.actuator_for()` leans on when it routes every
|
||||
claim to the site actuator at N=1. So `Maintenance` is constructed with
|
||||
`unit=None` there, reads and writes the flat keys directly, and
|
||||
`migrate_maint_keys()` **returns without writing anything**. A one-inverter state
|
||||
file comes out of this card byte-identical, which is AC 6 and which
|
||||
`test_maintenance.py` part 10 asserts by driving a whole cycle and comparing the
|
||||
key set.
|
||||
|
||||
### The migration has its own marker, and that is not tidiness
|
||||
|
||||
`SCHEMA_VERSION` / `schema_version` is DEV-02's, and it is **monotone**: every
|
||||
install runs that migration exactly once. This one runs **only where the roster
|
||||
has more than one pack**, so a single counter could not express *"migrated on
|
||||
this site, deliberately not migrated on that one"* without lying to the next
|
||||
version that reads it — a one-inverter store would have to be pinned at the old
|
||||
number forever, and a genuine future v2 migration could then never be told apart
|
||||
from a site that simply never grew. `maint_schema_version` answers one question
|
||||
and answers it honestly.
|
||||
|
||||
The **three rules are shared in code**, not restated: `_move_flat_keys()` is
|
||||
rule 1 (never overwrite an existing namespaced value) and rule 2 (the flat keys
|
||||
stay in the file), `_verify_moves()` is the read-back postcondition, and the
|
||||
marker is written last. A second transcription of a migration is a second
|
||||
opinion about what "it landed" means.
|
||||
|
||||
### And the flat keys are kept LIVE, which is the half DEV-02 had to add later
|
||||
|
||||
Rule 2 originally said the flat keys are left in place and go stale. DEV-02
|
||||
amended it, for the sign latch, to *"left in place is not enough"* — and the
|
||||
same sentence holds for history. A fossil dated the day the second inverter was
|
||||
declared would hand a rolled-back single-FSM add-on a `last_completed` months
|
||||
old (it recalibrates a pack that does not need it) or a stale `phase` with a
|
||||
`phase_started` old enough to abort on the 12 h timeout the moment it comes up.
|
||||
So `UnitHistory` **mirrors the first pack's writes back onto the flat keys** for
|
||||
as long as the roster has more than one entry. Only the first pack: the flat
|
||||
spelling means `inverters[0]` on every install that has one, and a mirror from
|
||||
pack B would overwrite pack A's rollback view with pack B's phase.
|
||||
|
||||
## 3. Staggering: the interlock defers, and the stagger is the residue
|
||||
|
||||
Two packs on one monthly schedule are due in the same hour every month. The
|
||||
options were a stagger **by construction** — offset each pack's first cycle by
|
||||
`interval_days / N` — or **deferral**. Deferral, for three reasons:
|
||||
|
||||
1. **A constructed stagger cannot remove the need for the interlock.** A forced
|
||||
start, a commissioning cycle, an abort-and-retry, or a pack added mid-month
|
||||
desynchronises any static offset immediately, so the interlock has to be
|
||||
there anyway — and then the stagger is a second mechanism that must also be
|
||||
correct, for a case the first one already handles.
|
||||
2. **A deferral is observable and a stagger is not.** The deferred pack says, in
|
||||
the action log and on the status page, that it is waiting, which pack it is
|
||||
waiting for, and that it will run at the next start hour. A silent offset
|
||||
moves an operator's configured start day and explains nothing.
|
||||
3. **The stagger comes out of the deferral for free and then persists.** Pack A
|
||||
completes on day 1 and is next due on day 29; pack B, deferred, completes on
|
||||
day 2 and is next due on day 30. One contested month separates them by one
|
||||
cycle length and they stay separated.
|
||||
|
||||
**Starvation was the risk and it is closed at two points.** A deferral does
|
||||
**not** stamp `last_start_attempt` — that key is the post-abort cooldown, and at
|
||||
90 minutes inside a 60-minute start hour, stamping it would lock the deferred
|
||||
pack out of exactly the hour it is waiting for. And the winner is the
|
||||
longest-waiting pack rather than the first in the roster, so a pack that keeps
|
||||
aborting cannot monopolise the slot month after month while its sibling drifts —
|
||||
which is this card's own defect wearing a different costume.
|
||||
|
||||
**The deferral must not read as a fault.** §12's 12 h and 36 h phase timeouts
|
||||
mean *"the battery is not following commands"*. A deferred pack stays `IDLE`
|
||||
with `phase_started` untouched, so no timeout is reachable by waiting, and the
|
||||
line it logs says WAITING, names the pack it waits for and says it will run
|
||||
next — none of which any failure path in `maintenance.py` says.
|
||||
|
||||
## 4. Rule 6 (the card calls it rule 8): the first entry's cap is no longer right
|
||||
|
||||
`validate.py`'s rule 6 comment said, in as many words, that
|
||||
`maintenance_charge_w` was graded against `inverters[0]`'s cap because there was
|
||||
exactly one `Maintenance` and it could only ever recalibrate the first pack —
|
||||
and that taking `min()` would be an over-refusal, because it would refuse *"a
|
||||
5000 W pack being recalibrated beside a 2000 W sibling the cycle never
|
||||
touches"*. It closed: **"when `maint_unit` stops being `inverters[0]`, this line
|
||||
moves with it."**
|
||||
|
||||
It has stopped. Every pack is recalibrated on its own schedule, so **the sibling
|
||||
the cycle never touches does not exist** and the over-refusal argument has no
|
||||
subject. The shaping claim is filed on whichever pack is charging, so the cap
|
||||
that can contradict it is any cap on the roster and the one that contradicts it
|
||||
first is the smallest.
|
||||
|
||||
**This refuses configurations that used to start**, and that is the point rather
|
||||
than a side effect: `max_w` 5000 on pack A beside 2000 on pack B with
|
||||
`maintenance_charge_w` 3000 was correct while only pack A was ever recalibrated,
|
||||
and is now a cheap-window charge asking the arbiter for `hi = -3000` against a
|
||||
supervised `lo = -2000` — `lo > hi`, arbiter clause 3, 0 W, on the pack nobody
|
||||
was watching. Refused when it is **written**, which is rule 6's whole job. At a
|
||||
roster of one `min()` over one cap is that cap: same comparison, same message,
|
||||
same boundary.
|
||||
|
||||
## 5. The claim stays per-unit, and nothing here files a site claim
|
||||
|
||||
`arbiter.CLAIM_SCOPE` has classified `maintenance` as `SCOPE_UNIT` since it was
|
||||
written. Two FSMs mean two claims on two actuators, which the allocator consumes
|
||||
as per-unit intervals. [[ARCH-01]] is explicit that this must never become a
|
||||
site claim, because per-inverter constraints filed site-wide are the
|
||||
cross-inverter `lo > hi` contradiction at `arbiter.py:114`. The only line this
|
||||
card changed there is **which** roster entry the claim is filed on: the one whose
|
||||
state machine produced the result, rather than `inverters[0]`.
|
||||
|
||||
## 6. FOUND AND NOT FIXED: the site loop still contradicts a drain at N>=2
|
||||
|
||||
Measured while wiring this card, and **pre-existing on `release/1.0` at
|
||||
`2d025ee`** — the same drain filed on `inverters[0]` produces the identical
|
||||
refusal with the two unit names swapped.
|
||||
|
||||
The maintenance SET **pins** its pack. The loop's target is a **site** claim.
|
||||
When the site target is *below* the pin — a 2000 W drain while the house imports
|
||||
less than that, which is most of a night — the only split that sums to the site
|
||||
target asks the sibling to **charge** while the maintained pack **discharges**,
|
||||
and `allocator.plan()` refuses it by name as circulating power. The refusal is
|
||||
correct and fails safe: the whole site goes to 0 W with an `ARBITER: REFUSED`
|
||||
line in the action log.
|
||||
|
||||
**The consequence an operator would see is a misdiagnosis.** The pack is held at
|
||||
0 W while its state machine believes it is draining, so after 12 h the DRAIN
|
||||
timeout fires and reports *"drain stuck"* — §12's words for a battery that is not
|
||||
following commands. The battery is fine; the site refused to allocate.
|
||||
|
||||
**Why it is not fixed here.** The fix is to change what the site loop's target
|
||||
*means* while a unit is pinned — regulate the meter using only the unpinned
|
||||
packs — which is loop and allocator territory and changes the integrator's
|
||||
subject. MAINT-05 moves which pack is pinned and nothing else about it. It is
|
||||
pinned as a running check (`test_maintenance.py` part 12) rather than left as a
|
||||
comment, so it cannot be forgotten or quietly tuned away, and it wants a card of
|
||||
its own.
|
||||