SAFETY-103: no swing on old battery readings after a drain ends
While a battery settles from its ended drain (SAFETY-95), the house point was grid + every battery's reading. A register can be 10 s older than the meter, so B swung 860 -> 1650 -> 870 W on A's old reading (rig check 5). Now the house point is held and moved only as far as the meter proves: each battery is between its last changed reading and its commands since (a reading that changed this cycle, or a refused side, as it reads). N=1 and 1 s registers are byte-identical to release/1.0. DECISIONS/SAFETY-103-old-readings-after-a-drain.md, test_safety103.py. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
This commit is contained in:
@@ -0,0 +1,79 @@
|
||||
# SAFETY-103 - no swing on old battery readings after a drain ends
|
||||
|
||||
**Status: implemented 2026-10-08, for review.** Tests: `test_safety103.py`.
|
||||
|
||||
**The defect** (SAFETY-95 rig test, check 5, F1). While a battery settles
|
||||
from its ended drain, SAFETY-95 steers on the house's point: grid + every
|
||||
battery's reading - aim. The meter is 1 s old; a battery register can be
|
||||
10 s old (the SAFETY-90 register model). At E+13 A's reading said 1238 W
|
||||
(6.8 s old) while A was at 616 W, so the house looked ~620 W bigger: B went
|
||||
860 -> 1650 -> 870 W. B's own old reading does the same the other way.
|
||||
|
||||
**The rule** (`main.py`, `_track_reads()`, `_drain_grid_w()`, N>=2, only
|
||||
while a drain's tail settles):
|
||||
|
||||
1. Each cycle, per battery: the range its power can be in. That is its last
|
||||
changed reading, widened by every command on its wire since (a lagging
|
||||
battery moves from one toward the others, never beyond). A new reading
|
||||
starts the range again.
|
||||
2. A reading that changed this cycle is taken as it reads. So is the side a
|
||||
battery refuses (SAFETY-73): it is not heading that way.
|
||||
3. The house point is held (first cycle: the loop's start from SAFETY-95).
|
||||
It moves only as far as the meter proves: to the nearest value of grid +
|
||||
the batteries' ranges - aim.
|
||||
|
||||
So the loop no longer moves on a reading that has not caught up. A real
|
||||
house step still moves it, as soon as the meter shows more than the
|
||||
batteries can explain.
|
||||
|
||||
**Why not the tester's rule** ("a battery whose reading is older than its
|
||||
last command counts at its command"). B's command changes almost every
|
||||
cycle, so B is almost always at its command. That is the plain meter, which
|
||||
chases A's tail: B swings 1420 W. A lag model needs the plant's time
|
||||
constant, which is not known for a client's inverter. Measured on the plant
|
||||
below (N=2, 1200 W, A Off; swing = a move of the others later undone):
|
||||
|
||||
| rule | 10 s lag | 5 s lag | 20 s lag | surplus, 5 s lag |
|
||||
|---|---|---|---|---|
|
||||
| release/1.0 (readings) | 760 | 840 | 150 | 800 |
|
||||
| tester's: at the command | 1420 | 1020 | 1600 | 800 |
|
||||
| lag model, tau 10 s | 70 | 140 | 80 | 580 |
|
||||
| lag model, tau 5 s, plant 20 s | | | 600 | |
|
||||
| hold all window | 0 | 0 | 0 | 0 |
|
||||
| **this rule** | **0** | **0** | **0** | **130** |
|
||||
|
||||
Holding all window ignores a house step: a 2 kW kettle at E+5 s imported
|
||||
14.4 Wh over the next 30 s (release 11.5, this rule 11.3); 2 kW more sun
|
||||
exported 16.9 Wh (release 8.5, this rule 8.9).
|
||||
|
||||
**Before -> after** (`test_safety103.py`, `tools/safety103_plant.py`: 800
|
||||
W/s ramp, 10 s lag, meter 1 s, registers 10 s at the rig's phases, B idles
|
||||
at -100 W; summed swing of the others in the 23 s after the end):
|
||||
|
||||
| case | release/1.0 | after |
|
||||
|---|---|---|
|
||||
| rig check 5: N=2, 1200 W, A Off | B 1140 -> 850 -> 1630 -> 870, swing 760 W | B holds 1140 W |
|
||||
| N=3, 1200 W / 4000 W, A Off | 680 / 630 W | 0 / 0 W |
|
||||
| solar surplus, N=2 / N=3 | 890 / 740 W | 130 / 130 W |
|
||||
| lag 5 or 20 s, registers 5 or 10 s, N=2 and N=3 | | at most 10 W |
|
||||
| registers as fresh as the meter (1 s) | | rows byte-identical |
|
||||
| refusal end | | rows byte-identical |
|
||||
| N=1, every end | | rows byte-identical (also against the release/1.0 tree) |
|
||||
|
||||
**Cost.** In the window, a house change smaller than what the batteries
|
||||
could still be doing is not followed until a reading catches up (at most a
|
||||
register period) or the window ends (23 s). Under a surplus the others
|
||||
still swing up to 130 W, a third of a slew step.
|
||||
|
||||
**Not covered.**
|
||||
- Outside the drain tail the loop steers on the meter; readings only reach
|
||||
the saturation freeze (SAFETY-96), unchanged.
|
||||
- A lost link or a refusal ends the tail at once (A is out of the split, or
|
||||
reads ~0 W). The swing after them is the loop's own on a lagging plant,
|
||||
the same with 1 s registers and on release/1.0 (up to 1.9 kW at N=3 under
|
||||
a surplus): not this card.
|
||||
- A battery that overshoots its command, or a reading offset beyond the
|
||||
range, can put the true power outside the range; the meter then moves the
|
||||
point, as before.
|
||||
- The end cycle's start (SAFETY-95 step 2) still uses the readings; the
|
||||
batteries were steady during the drain, so they are current there.
|
||||